| 2003-09-12 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | THE INTERNAL PRESSURE COEFFICIENT FOR AN |
| | ENCLOSED STRUCTURE IS + OR - 0.18. |
| | SPECIFY THIS INFORMATION ON THE PLAN FOR |
| | THE ADDITION. SOME OF THIS IS ON THE |
| | PLANS UNDER ROOF NOTES, HOWEVER ALL OF |
| | THE ADDITION IS REQUIRED TO COMPLY. |
| | |
| | 4) SPECIFY THE POSITIVE AND NEGATIVE |
| | WIND LOAD PRESSURES FOR THE WINDOW AND |
| | DOOR OPENINGS IN THE ADDITION. |
| | |
| | 5) ON SHEET S-2 SECTION B-B IS INDICATED |
| | ON THE FOUNDATION PLAN AND THE DETAIL IS |
| | MARKED G-G. PLEASE CORRECT. SPECIFY THE |
| | SPACING OF THE DOWELS SHOWEN IN THE |
| | DETAIL. |
| | |
| | 6) SPECIFY THE LENGTH OF THE 1/2" BOLT |
| | IN THE DETAIL ON S-2. THE SPACING OF THE |
| | BOLTS IS 4 FT. ON CENTER ON S-2 AND 2 FT |
| | ON CENTER ON THE SLOPE AND FLAT ROOF |
| | SECTIONS ON D-1. THE FLAT ROOF SECTION |
| | SPECS. A 6" EMBED AND THE SLOPED ROOF |
| | SECTION HAS 4" EMBED FOR BOLTS. PLEASE |
| | CLARIFY. |
| | |
| | 7) SPECIFY THE SIZE OF THE NEW BATHROOM |
| | DOOR. FBC 11-43.23.2 REQUIRES ONE BATH |
| | ROOM WITH AT LEAST A 29" CLEAR OPENING. |
| | |
| | 8) THE RTPGA STRAPS SPECIFIED IN THE |
| | ANCHOR SCHEDULE ON R-1 ARE NOT LISTED IN |
| | THE 2003 USP CATALOG. PLEASE UPDATE. |
| | |
| | 9) THE WALL SECTIONS ON D-1 SPECIFY 5/8" |
| | STUCCO. ASTM C 926 REQUIRES STUCCO OVER |
| | METAL LATH (VERTICAL) TO BE 7/8" THICK. |
| | SEE FBC 2504.2.1. |
| | |
| | 10) UPDATE THE STRAPS AND STUD PLATE |
| | TIES TO CONNECTORS LISTED IN CURRENT |
| | MANUFACTURERS' CATALOGS. SEE NOTES ON |
| | THE PLAN. |
| | |
| | 11) PLEASE REVIEW DETAILS ON D-1 AND |
| | CLARIFY THE SIZE OF THE FRAME WALLS. |
| | SPECIFY R-11 INSULATION FOR 2X4 WALLS |
| | AND R-19 FOR 2X6 WALLS. USP SPT 4 PLATE |
| | CONNECTORS ARE FOR 2X4 WALLS AND SPT 6 |
| | ARE FOR 2X6 WALLS. |
| | |
| | 12) THE PLANS SPECIFY R-30 INSULATION IN |
| | THE SINGLE ASSEMBLY ENCLOSED CEILING. |
| | THIS WILL INTERFERE WITH VENTILATION. |
| | THE CODE WILL ALLOW R-19 FOR THIS |
| | APPLICATION. INDICATE THE APPROPRIATE |
| | INSULATION ON THE PLAN AND ON THE ENERGY |
| | FORM AS REQUIRED BY FBC 11-604.1. |
| | |
| | 13) NOTE 4 ON T-1 STATES THAT THE |
| | EXISTING WALLS ARE CBC AND THE PLANS |
| | INDICATE WOOD FRAME WALLS. PLEASE |
| | CLARIFY. |
| | |
| | 14) PROVIDE DETAILS OF THE STRUCTURAL |
| | REPAIRS THAT WILL BE MADE TO THE EXIST- |
| | ING BEARING WALLS THAT WERE DAMAGED. |
| | REVISE NOTE ON T-1 TO SPECIFY THAT THE |
| | ENGINEER IS RESPONSIBLE FOR THE REPAIRS |
| | TO THE EXISTING STRUCTURE AND THE NEW |
| | ADDITION. |
| | |
| | 15) THE INFORMATION ON THE ENERGY FORM |
| | IS INCORRECT. PLEASE CORRECT AND SUBMIT |
| | TWO COPIES. |
| | |
| | 16) THE PRODUCT APPROVALS FOR THE |
| | SINGLE HUNG WINDOWS IS ILLEGIBLE. SUBMIT |
| | TWO CLEAR READABLE COPIES. |
| | |
| | 17) THE PRODUCT APPROVALS FOR THE FRENCH |
| | DOORS ARE NOT ACCEPTABLE. THE ACCEPTANCE |
| | NUMBER ON THE COVER SHEET DOES NOT MATCH |
| | THE ONE ON THE DRAWINGS AND PAGES ARE |
| | MISSING FROM THE NOA. SUBMIT TWO |
| | COMPLETE AND READABLE PRODUCT APPROVALS |
| | FOR THE DOUBLE OUTSWING FRENCH DOORS. |
| | |
| | 18) SUBMIT PRODUCT APPROVALS FOR THE |
| | ROOFING MATERIAL. |
| | |
| | 19) SUBMIT TWO COPIES OF A KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE MOUNTING TYPE, |
| | ANCHOR TYPE AND ANCHOR SPACING THAT WILL |
| | BE USED. |
| | |
| | IF YOU HAVE QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |