Plan Review Details - Permit 03081033
Plan Review Stops For Permit 03081033
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By rbrown Date 2003-09-24 Time 13:28 Rev Time 0.00
Received By rbrown Date 2003-09-24 Time 13:28 Sent To  
Notes
2003-09-24 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 2309.6PROVIDE MIN. 20"X 36" ACCESS
 OPENING INTO THE NEW ATTIC SPACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:13 Rev Time 0.00
Received By rbrown Date 2003-09-09 Time 16:29 Sent To  
Notes
2003-09-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED CEMENT TILE ROOFING.
  
 3) FBC TABLE 1606.2ASHEET 5, ROOF
 FRAMING. SUBMIT A DETAIL SHOWING HOW THE
 SIMPSON CS STRAPS WILL BE USED TO STRAP
 THE NEW TRUSSES TO THE EXISTING TRUSSES.
 THE DETAIL SHALL SHOW HOW MANY OF THE
 SPECIFIED 8-10D (TOTAL) NAILS IN EACH
 STRAP ARE FIXED INTO THE EXISTING TRUSS.
 WHAT ACTUAL SIMPSON CS REFERENCE/GAGE IS
 PROPOSED?NOTE THAT THE 2003 SIMPSON
 CATALOGUE DOES NOT PROVIDE TABULATED
 CAPACITIES FOR ANY OF THE CS STRAPS USED
 WITH JUST 8-10D NAILS.
  
 4) FBC TABLE 1606.2ASIMPSON H10 TRUSS
 ANCHORS.THE TRUSSES WILL BE SUBJECTED
 TO "WINDWARD OVERHANG' LOAD DUE TO THE
 POSITIVE PRESSURE FROM BELOW COINCIDENT
 WITH THE NEGATIVE PRESSURE ABOVE. ARE
 THE TRUSSES TO BE ANCHORED TO THE TWO
 INTERMEDIATE WOOD BEAMS (AND DESIGNED
 ACCORDINGLY BY THE TRUSS MANUFACTURER)?
 IF NOT, THE PROPOSED H10 ANCHORS HAVE
 INSUFFICIENT UPLIFT CAPACITY.AMEND THE
 PLANS TO CLARIFY THE PROPOSALS.
  
 5) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-25 Time 16:48 Rev Time 0.33
Received By dpalmer Date 2003-08-27 Time 13:05 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:13 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 12:13 Sent To B
Notes
2003-09-19 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 16:48 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 16:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-19 Cont ID  
Sent By mmclean Date 2003-08-25 Time 16:11 Rev Time 0.00
Received By alange Date 2003-08-19 Time 09:09 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-25 Cont ID  
Sent By alange Date 2003-08-19 Time 09:09 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***