Plan Review Details - Permit 03080986
Plan Review Stops For Permit 03080986
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-05-11 Cont ID  
Sent By lmartine Date 2004-05-11 Time 13:41 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-05-11 00:00:00BUILDING AND DOWNTOWN PLANNING IS APPROV
 ED PER LUIS MARTINEZ AND ANA MARIA

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:13 Rev Time 2.00
Received By lmartine Date   Time   Sent To M
Notes
2004-04-12 00:00:00 
 REVISION COMMENTS
 -----------------
  
 PLEASE SUBMIT PRODUCT APPROVALS FOR NEW
 DOORS AND WINDOWS MENTIONED.
  
  
  
 LUIS MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-24 Cont ID  
Sent By lmartine Date 2004-03-24 Time 13:26 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-03-24 00:00:00 
 REVISION COMMENTS
 -----------------
  
  
 1]
 SUBMIT STATE OF FLORIDA PRODUCT
 APPROVAL FOR ALL NEW EXTERIOR GLAZING,
 DOORS AND SHUTTERS.
  
 2]
 SEVERAL DETAILS FOR EXTERIOR WALL
 CONSTRUCTION NOTE COMBUSTIBLE MATERIAL
 (PLYWOOD), INSTALLATION OF SUCH
 MATERIAL IS NOT PERMITED WITHIN THE
 CITIES FIRE DISTRICT, SEE APPENDIX 'F'
 CITY AMENDMENTS.
  
 3]
 EXPLAIN FUTURE TENANT #2. POSSIBLE
 EXITING ISSUES.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:23 Rev Time 0.00
Received By rbrown Date 2003-10-02 Time 18:02 Sent To  
Notes
2003-10-09 00:00:00PASSED: ALTERNATE PRODUCT APPROVALS
 SUBMITTED 10/8/03.
  
 NOTE: THE UNSUITABLE SYSTEMS HAVE BEEN
 STRUCK FROM THE SUBMITTED JOHNS MANVILLE
 CORP. BUILT-UP ROOFING PRODUCT APPROVAL
 NOA# 01-0524.13
2003-10-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 9/19/03:
  
 3) THE SUBMITTED JOHNS MANVILLE CORP.
 BUILT-UP ROOFING PRODUCT APPROVAL
 NOA# 01-0524.13 HAS NOT BEEN MARKED TO
 IDENTIFY WHCH SYSTEM IS TO BE USED.OF
 THE AVAILABLE SYSTEMS, SOME HAVE A MAX.
 DESIGN PRESSURE RATING OF -45 PSF AND
 REFERENCE GENERAL LIMITATION #9 WHICH
 DOES NOT ALLOW RATIONAL ANALYSIS OR
 EXTRAPOLATION FOR ENHANCED FASTENING AT
 THE EDGE OR CORNER ZONES.PLAN SHEET #1
 STATES THAT THE DESIGN PRESSURE AT THE
 EDGE STRIP IS -59.2 PSF AND THAT AT THE
 CORNER ZONES IS -89.0 PSF, BOTH OF WHICH
 EXCEED THE ABOVE-MENTIONED DESIGN
 PRESSURE RATING.MARK THE PRODUCT
 APPROVAL TO SPECIFY A SYSTEM WHICH, WITH
 ENHANCED FASTENING IF APPROPRIATE, HAS
 A DESIGN PRESSURE RATING WHICH EXCEEDS
 THE DESIGN PRESSURES.ALTERNATIVELY, A
 SEPARATE ROOFING PERMIT APPLICATION WILL
 BE REQUIRED.
  
 4) HURRICANE MISSILE IMPACT PROTECTION.
 CONTRARY TO ROBERT BELL'S COMMENT
 RESPONSE LETTER, THE SUBMITTED PRODUCT
 APPROVALS FOR THE STOREFRONT SYSTEM AND
 THE NARROW STILE DOOR BOTH STATE THAT
 THESE PRODUCTS ARE NOT IMPACT RATED AND
 WILL REQUIRE THE PROVISION A HURRICANE
 MISSILE IMPACT PROTECTION SYSTEM.
 PROVIDE ALTERNATIVE PRODUCT APPROVALS
 OR SUBMIT A PRODUCT APPROVAL FOR STORM
 SHUTTERS.
  
 6) STOREFRONT PRODUCT APPROVAL.SEE
 COMMENT #4 ABOVE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-19 Cont ID  
Sent By rbrown Date 2003-09-19 Time 10:42 Rev Time 0.00
Received By rbrown Date 2003-09-19 Time 10:42 Sent To  
Notes
2003-09-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST STATE
 THE LICENSE NUMBER OF THE ARCHITECT.
 ADD THE LICENSE NUMBER.ALSO, NOTE THAT
 ONE SET THE PLANS HAS NOT BEEN SIGNED
 AND SEALED.
  
 3) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED BUILT-UP ROOFING SYSTEM.THE
 PRODUCT APPROVAL SHEETS SHALL BE MARKED,
 AS APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED.
  
 4) SUBMIT A PRODUCT APPROVAL FOR STORM
 SHUTTERS FOR ANY OF THE OPENINGS WHICH
 ARE NOT IMPACT RATED.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOORS, INCLUDING THE ROLL-UP
 DOOR.
  
 6) SUBMIT A PRODUCT APPROVAL FOR THE NEW
 STORE FRONT.
  
 7) FBC* 104.2.1THE PLANS SHALL STATE
 THE THE DIMENSIONS OF THE STOREFRONT
 OPENINGS.
  
 8) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.
  
 9) PROVISO:
 SHEET 1, FOOR PLAN.THE NOTE COVERING
 REPAIR OF THE STEEL BEAM AND COLOMNS
 ADJACENT THE EXISTING SHOWER STATES
 "(ALT. REMOVE COLUMNS/BEAM)".IF THE
 BEAM IS TO BE REMOVED, SUBMIT PLANS
 SHOWING WHAT IS SUPPORTED BY THE BEAM
 AND COLUMNS.
  
 10) SHEET 2, SECTION 4/2.NEW EXTERIOR
 WALL.AMEND THE PLANS TO SHOW/DESCRIBE
 WHAT THIS WALL IS REPLACING.
  
 11) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 18:00 Rev Time 0.75
Received By btrobaug Date 2004-04-06 Time 17:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-02-20 Cont ID  
Sent By dpalmer Date 2004-02-20 Time 15:41 Rev Time 1.50
Received By dpalmer Date 2004-02-20 Time 14:46 Sent To  
Notes
2004-02-20 00:00:00************* UNSAT ****************
  
 PLEASE SEE REVISED PLANS ARE COMING IN
 WITH ALL NEW ELECTRICAL SERVICE ETC.
 THE FOLLOWING ARE NEW NOTES AND NOTES
 FROM ORIGINAL REVIEWS THAT WERE REDLINED
 ON ORIG PLANS.
  
 1)NOTE: PLEASE SEE NOTE #5, MENTIONS
 AN EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN. PLEASE SEE 250.24 AN
 EQUIPMENT GRND IS ONLY INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE VERIFY AIC RATINGS AT
 THIS TIME. 110.9/ 215.5
  
 3)NOTE: PLEASE SIZE SEC'S, SERVICE IS
 SHOWN AS 250A'S. 3/0'S IS RATED FOR 200A
 'S PER 310.16. PLEASE SEE 230.42B
  
 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING FO EM/EXT LTS.
 REDLINED ON ORIG.
  
 5)NOTE: PLEASE SEE OCP FOR AHU'S 7.5KW
 TO BE SIZED PER 424.3B MIN 125%. SHOWN
 AS 40A. PLEASE VERIFY WITH NAMEPLATE
 ON UNITS.
  
 6)NOTE: PLEASE SEE NOTE #10, MENTIONS
 OPTIONAL 2" CONDUIT. THIS CONDUIT AND
 FEED FROMFIRST METER IS NOT OPTIONAL
 AT THIS TIME. TENANT SPACE WILL REQUIRE
 TENANT SEPARATION AT THIS TIME IF NOT
 INSTALLED.
  
 7)NOTE: PLEASE PROVIDE AMPERAGE FOR
 METERCANS SHOWN.
 RISER SHOWS BOTH125A MAINS COMING FROM
 ONE METER CAN.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 07:08 Rev Time 0.50
Received By dpalmer Date 2003-10-28 Time 07:08 Sent To  
Notes
2003-10-28 00:00:00PLANS REDLINED ****
  
 1)NOTE: PLEASE SEE THAT NO MEANS OF
 EGRESS LIGHTING IS SHOWN AS EXISTING OR
 NEW LEAVING SIDE DOOR. LS 101 5-8
 THIS WAS NOTE ON FIRST TWO REVIEWS.
  
 2)NOTE: PLEASE SEE EXT/EM LTS ARE BEING
 SHOWN ON PANEL SCHEDULE AND CAN NOT
 LOCATE EM LTS ON PLANS? ALSO MUST BE
 CIRCUITED PER 700.12E AS NOTED ON FIRST
 TWO REVIEWS.
  
  
  
 THESE ARE NOTES REDLINED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 16:30 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 16:30 Sent To  
Notes
2003-10-07 00:00:00************** UNSAT *******************
  
  
 1)NOTE: PLEASE SEE THAT IT APPEARS THE
 SAME PLAN CAME BACK IN W/OUT ANY CHANGES
 ?? MAYBE NOTES DID NOT GO TO ARCH FROM F
 ROM FIRST REVIEW.?
  
 2)NOTE: PLEASE SEE 424.3 FOR MIN SIZE
 OF OCP TO BE 125% FOR HEAT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-19 Cont ID  
Sent By dpalmer Date 2003-09-19 Time 13:49 Rev Time 0.33
Received By dpalmer Date 2003-09-19 Time 13:49 Sent To  
Notes
2003-09-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIDY NEW OR EXISTING
 REQ'D SIGN CIRCUIT PER 600.5
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR POSSIBLE NOTES FOR EMERGENCY LTS?
  
 3)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700.12E
  
 4)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING WHAT APPEARS TO BE SIDE EXIT?
 LS 101 5-8 EXISTING? OF SOME TYPE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By nmccray Date 2004-02-24 Time 11:11 Rev Time 0.00
Received By nmccray Date 2004-02-24 Time 11:11 Sent To  
Notes
2004-02-24 00:00:00REVISION DATED 2-12-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-17 Cont ID  
Sent By mcarsill Date 2003-10-17 Time 16:26 Rev Time 0.00
Received By mcarsill Date 2003-10-17 Time 16:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:13 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:13 Sent To B
Notes
2004-04-28 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 08:26 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 08:26 Sent To  
Notes
2004-03-26 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-16 Cont ID  
Sent By mmclean Date 2004-03-17 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 14:55 Sent To M
Notes
2004-03-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 12:33 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 12:33 Sent To P
Notes
2004-03-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 16:19 Sent To  
Notes
2004-02-13 00:00:00TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-10-27 Time 09:46 Rev Time 0.00
Received By csiegber Date 2003-10-27 Time 09:45 Sent To  
Notes
2003-10-27 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:22 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 15:22 Sent To B
Notes
2003-10-08 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:50 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 11:50 Sent To  
Notes
2003-09-29 00:00:00TO COMM BD #8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 15:04 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 15:04 Sent To  
Notes
2003-09-17 00:00:00ON COMM BD#
 ON COMM BD #51 FROM ZONING/DL 9/17/03 DS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-18 Cont ID  
Sent By mmclean Date 2003-09-17 Time 10:25 Rev Time 0.00
Received By alange Date 2003-08-18 Time 14:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2004-04-13 Cont ID  
Sent By pkrauss Date 2004-04-13 Time 06:46 Rev Time 0.45
Received By pkrauss Date 2004-04-13 Time 06:46 Sent To  
Notes
2004-04-13 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVISION.THE FLOOR PLAN DOES HOWEVER
 REFLECT THREE AHU'S WHEREAS THE APPROVED
 MECHANICAL PLANS INDICATE ONLY TWO.THE
 LOCATION OF THE AHU #2 HAS ALSO CHANGED.
 A MECHANICAL REVISION WILL BE NECESSARY.
  
 PLEASE INDICATE TONNAGE OF THE
 ADDITIONAL AHU.WHAT WILL BE THE TOTAL
 REQUIREMENT FOR AIR TO THIS SPACE?
 ARE THE ENGERGY CALCULATIONS CORRECT OR
 DO THEY NEED TO BE REVISED?PLEASE
 CLARIFY THE ABOVE INFORMATION AND SUBMIT
 REVISION FOR THE MECHANICAL CHANGES.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA FOR
 THE CONDENSING UNIT STANDS.PLANS DO
 NOT REFLECT HOW THE CONDENSING UNITS
 ARE TO BE MOUNTED.THE ARCHITECT OR
 ENGINEER IS REQUIRED TO PROVIDE A DETAIL
 REFLECTING HOW THE STANDS ARE TO BE
 ATTACHED TO THE EXISTING ROOF STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-31 Cont ID  
Sent By lmartine Date 2004-04-12 Time 17:44 Rev Time 0.45
Received By pkrauss Date 2003-10-31 Time 16:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By hmoser Date 2003-10-07 Time 18:56 Rev Time 0.50
Received By hmoser Date 2003-10-07 Time 18:56 Sent To  
Notes
2003-10-07 00:00:00NO PLANS
 HAROLD MOSER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-22 Cont ID  
Sent By hmoser Date 2003-09-22 Time 19:00 Rev Time 0.50
Received By hmoser Date 2003-09-22 Time 19:00 Sent To  
Notes
2003-09-22 00:00:00DENIED
 NO MECHANICAL PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-2936

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-03-16 Time 12:33 Rev Time 0.33
Received By kstevens Date 2004-02-24 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 12:06 Rev Time 0.33
Received By kstevens Date 2003-10-21 Time 12:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By kstevens Date 2003-09-23 Time 11:32 Rev Time 0.50
Received By kstevens Date 2003-09-23 Time 11:31 Sent To  
Notes
2003-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
  
 1) SHOW CLEAR FLOOR SPACE AND 5' TURNING
 SPACE FOR EACH TOILET ROOM. SECTION
 11-4.22.3
 2) 61G1-16.003 THE PERSONAL SEAL, SIGNA-
 TURE, AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS
 TO BE FILED FOR PUBLIC RECORD.
 61G1-16.004 THE FIRM LICENSE NUMBER IS
 REQUIRED ON TITLE BLOCK.
 3) WATER RISER DIAGRAM REQUIRED. SECTION
 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-17 Cont ID  
Sent By mmclean Date 2004-03-17 Time 10:23 Rev Time 0.00
Received By mmclean Date 2004-03-17 Time 10:23 Sent To I
Notes
2004-03-17 00:00:00APPROVED BY ANTHEA AGIANNIOTES 659-8031

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-17 Cont ID  
Sent By mmclean Date 2003-09-17 Time 10:25 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***