Plan Review Details - Permit 03080809
Plan Review Stops For Permit 03080809
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-11 Cont ID  
Sent By jwitmer Date 2003-12-11 Time 13:30 Rev Time 1.00
Received By jwitmer Date 2003-12-11 Time 13:30 Sent To  
Notes
2003-12-11 00:00:00PLAN REVIEW/ OK TO TURN FROM PLAN REVIEW
 TO PERMIT APP, OK TO ISSUE.J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By hpiskura Date 2003-11-05 Time 17:33 Rev Time 0.00
Received By hpiskura Date 2003-11-05 Time 17:33 Sent To  
Notes
2003-11-05 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 THE WIND LOAD CALCULATIONS, AND DESIGN
 PRESSURE ARE REQUIRED TO COMPLY WITH
 ASCE 7-98 FOR A 140 MPH ZONE.
  
 INCLUDE THE ANTENNA DISH/DEVICE AND ITS
 CONNECTION TO THE 2" PIPE.
  
 PROVIDE AN ENGINEERING INVESTIGATION AS
 ABOVE FOR THE PROPOSED EQUIPMENT CABINET
 AND ITS ATTACHMENT TO THE BUILDING.
  
 SHOW THE ROUTE OF ANY CABLING, CONDUIT
 OOR SIMILAR THAT WILL PENETRATE THE
 ROOF AND/OR FLOORS OF THE BUILDING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 14:51 Rev Time 0.50
Received By dpalmer Date 2003-12-04 Time 14:51 Sent To  
Notes
2003-12-04 00:00:00ELEC OK, HOWEVER, PLANS ARE NOT IN FOR
 PERMIT. ONLY PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 12:14 Rev Time 0.33
Received By dpalmer Date 2003-11-03 Time 12:14 Sent To  
Notes
2003-11-03 00:00:00**************** UNSAT **************
  
 1)NOTE: PLANS ARE COPIES OF SIGNED AND
 SEALED DRAWINGS. PLEASE ALSO SEE THAT
 PLANS ARE REQ'D TO BE ORIGINAL SIGNED,
 DATED AND RAISED SEALED. FS 471.025
 AND 61G15-23.002 FAC.
 PLEASE SUBMIT TWO SETS FOR REVIEW AND
 STAMPING.
  
  
 ***NOTE***
 PLEASE NOTE, PLANS ARE ONLY ON FOR PLAN
 REVIEW AND NOT FOR PERMIT APPLICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 12:37 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 12:37 Sent To  
Notes
2003-12-04 00:00:00TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 11:45 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 11:45 Sent To  
Notes
2003-11-03 00:00:00TO COMM BD#41/SENT TO PLANNING-JOSH
 LONG APPROVED AND SENT BACK TO FITZ
 TOWER-THEY CALLED AND RE-SENT 110/29/03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 14:55 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 14:55 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-26 Cont ID  
Sent By mmclean Date 2003-09-26 Time 15:42 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-09-26 00:00:009/8/03 APPROVED FOR THE LEVEL 1 MAILED
 TO APPLICANT PER THEIR REQUEST PER
 JOSH LONG ASSOCIATE PLANNER MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-18 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 14:55 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-08-18 00:00:008/18/03 NEED TO APPLY FOR A LEVEL 1 ON
 THE 5TH FLOOR MM