Plan Review Details - Permit 03080724
Plan Review Stops For Permit 03080724
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By rbrown Date 2003-08-25 Time 16:38 Rev Time 0.00
Received By rbrown Date 2003-08-25 Time 16:38 Sent To  
Notes
2003-08-25 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
  
 --PROVISO--
 FBC 11-7.2(1)THE SALES COUNTER SHALL
 HAVE A MIN. 36" LONG PORTION THAT IS A
 MAX. HEIGHT OF 36" ABOVE FINISHED FLOOR
 FOR ACCESSIBILITY.
  
 --PROVISO--
 A SEPARATE PERMIT APPLICATION IS
 REQUIRED FOR THE STOREFRONT REPLACEMENT.
 SHEET A2, DEMO PLAN, STATES THAT THE
 EXISTING STOREFRONT IS TO BE REMOVED
 AND IT IS NOTED THAT SHEET A3 REFERS TO
 'STOREFRONT BY OTHERS'.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-10-22 Time 11:37 Rev Time 0.33
Received By dpalmer Date 2003-10-22 Time 11:37 Sent To FIRE
Notes
2003-10-22 00:00:00REDLINED EQUIPMENT GRNDS AS EXISTING
 250.110/250.30

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:36 Rev Time 0.33
Received By dpalmer Date 2003-09-09 Time 18:40 Sent To  
Notes
2003-09-09 00:00:00*** REDLINED NOTES FOR EXISTING EQUIP-
 -MENT GROUNDING TO AND FROM TRANSFORMER?
 EXSITING? FIELD VERIFY. 250.110
 TRANSFORMER GROUNDING, EXISTING? 250.30

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-26 Cont ID  
Sent By dpalmer Date 2003-08-26 Time 19:43 Rev Time 0.75
Received By dpalmer Date 2003-08-26 Time 19:29 Sent To  
Notes
2003-08-26 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY NEW OR EXISTING
 EM/EXT LTSAND CIRCUITING PER 700.12E
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SHOW WINDOW RECEPTS. 210.62
  
 3)NOTE: PLEASE CLARIFY LOADS FOR TRACK
 LIGHTING 220.12B
  
 4)NOTE: PLEASE CLARFIY EQUIPMENT GROUND-
 ING TO AND FROM TRANSFORMER AND GROUND
 FOR TRANSFORMER 250.110, 250.30
 THIS CAN BE REDLINED IF NOT KNOWN AT
 THIS TIME DUE TO EXSITING INSTALLATION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By nmccray Date 2003-10-27 Time 10:11 Rev Time 0.00
Received By nmccray Date 2003-10-27 Time 10:11 Sent To  
Notes
2003-10-27 00:00:00REVISION DATED 10-16-03 APPROVED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-10-22 Time 11:37 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-02 Cont ID  
Sent By nmccray Date 2003-09-02 Time 11:05 Rev Time 0.00
Received By nmccray Date 2003-09-02 Time 11:05 Sent To  
Notes
2003-09-02 00:00:001) PLEASE CLARIFY EXISTING OR NEW EXIT
 SIGNS AND EMERGENCY LIGHTS.
  
 2) ADDITIONAL PLANS AND PERMITS ARE
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3) AN ADDITIONAL FIRE EXTINGUISHER MAYBE
 REQUIRED BY FIELD INSPECTOR.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:36 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 16:36 Sent To E
Notes
2003-10-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 16:38 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 16:38 Sent To  
Notes
2003-09-08 00:00:00ON COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 15:59 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 15:59 Sent To  
Notes
2003-08-13 00:00:00TO COMM BD #42