Plan Review Details - Permit 03080451
Plan Review Stops For Permit 03080451
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By btrobaug Date 2003-08-25 Time 09:07 Rev Time 0.50
Received By lsmith Date 2003-08-26 Time 07:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-03 Cont ID  
Sent By btrobaug Date 2003-09-03 Time 13:08 Rev Time 0.33
Received By btrobaug Date 2003-09-03 Time 11:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-29 Time 10:50 Rev Time 0.33
Received By btrobaug Date 2003-08-25 Time 09:05 Sent To B
Notes
2003-08-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 INDICATING EXISTING AND ALL LOADS BEING
 ADDED.ALSO INDICATE THE SIZE OF THE
 EXISTING SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-29 Cont ID  
Sent By csiegber Date 2003-08-29 Time 10:50 Rev Time 0.00
Received By csiegber Date 2003-08-29 Time 10:50 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-15 Cont ID  
Sent By alange Date 2003-08-15 Time 15:10 Rev Time 0.00
Received By alange Date 2003-08-15 Time 15:10 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:40 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:40 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-06 Cont ID  
Sent By kstevens Date 2003-09-06 Time 20:09 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 20:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-23 Cont ID  
Sent By btrobaug Date 2003-09-03 Time 13:08 Rev Time 0.50
Received By kstevens Date 2003-08-23 Time 10:01 Sent To E
Notes
2003-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL) NO LABEL
 SHOWN ON SPEC. SHEET.
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 NO RETENTION SHOWN ON SPECIFICATION
 SHEET SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By mmclean Date 2003-08-20 Time 10:26 Rev Time 0.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-12 Cont ID  
Sent By alange Date 2003-08-15 Time 15:10 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-08-12 00:00:008/12/03 DENIED, NEED TO BED 10FT FROM
 SIDE CALLED CONTR FILE E MM