Plan Review Details - Permit 03080444
Plan Review Stops For Permit 03080444
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-04 Cont ID  
Sent By hpiskura Date 2003-11-04 Time 13:36 Rev Time 0.00
Received By hpiskura Date 2003-11-04 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By hpiskura Date 2003-09-04 Time 07:31 Rev Time 0.00
Received By hpiskura Date 2003-08-21 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-07 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 18:37 Rev Time 0.33
Received By dpalmer Date 2003-10-07 Time 18:32 Sent To  
Notes
2003-10-07 00:00:00********* NOTE REDLINED *****
  
 EQUIPMENT GROUNDING TO BE VERIFIED FROM
 MAIN TO PANEL.
 250.110/250.122

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By alange Date 2003-08-08 Time 15:19 Rev Time 0.50
Received By dpalmer Date 2003-08-14 Time 07:28 Sent To  
Notes
2003-08-14 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF THE
 FAC 61G1-16.004 FOR ALL INFORMATION
 REQ'D ON TITLE BLOCK FOR ARCH'S.
  
 2)NOTE: PLEASE CLARIFY AND SHOW NEW OR
 EXIST, "SHOW WINDOW" RECEPTS REQ'D BY
 210.62.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT, PER 600.5
  
 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE
 REQ'MENTS INFRONT OF PANEL.
  
 5)NOTE: PLEASE CLARIFY LOAD FOR TRACK LT
 -S PER 220.12B
  
 6)NOTE: PLEASE PROVIDE AIC RATING FOR
 NEW PANEL. 110.9
  
 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING FROM MAIN AND PANEL.
 250.110, SIZE ANY EQUIPMENT GRND PER
 250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By mcarsill Date 2003-10-17 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2003-10-17 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-27 Cont ID  
Sent By mcarsill Date 2003-08-27 Time 07:42 Rev Time 0.00
Received By mcarsill Date 2003-08-27 Time 07:42 Sent To  
Notes
2003-08-27 00:00:001) PANIC BAR NOT REQUIRED ON REAR DOOR.
 IF SO DESIRED, THUMB-LATCH CANNOT
 BE INSTALLED WHEN PANIC HARDWARE IS
 PROVIDED.
  
 2) M-1 PLANS REFERENCE TO "EXISTING
 GAS TANKS. PLEASE PROVIDE MORE DETAILS
 WITH REGARDS TO SIZES, PROTECTION,
 AND ANY RELATIONSHIP TO ANY DOORS AND
 WINDOWS. COOKING EQUIPMENT HAS TO BE
 CHANGED TO ACCOMMODATE LPG INSTEAD
 OF NATURAL GAS.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM.
  
 4) DUCT SMOKE DETECTOR REQUIRED ON
 RTU'S 2000 CFM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-07 Time 13:36 Rev Time 0.00
Received By csiegber Date 2003-10-07 Time 13:36 Sent To  
Notes
2003-10-07 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 15:17 Rev Time 0.00
Received By alange Date 2003-08-08 Time 15:17 Sent To E
Notes
2003-08-08 00:00:00TO COMM BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-22 Cont ID  
Sent By pkrauss Date 2003-10-22 Time 12:32 Rev Time 0.45
Received By pkrauss Date 2003-10-22 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-29 Cont ID  
Sent By pkrauss Date 2003-08-29 Time 09:27 Rev Time 0.40
Received By pkrauss Date 2003-08-29 Time 09:27 Sent To  
Notes
2003-08-29 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW PLEASE PROVIDE PLANS WITH PERMIT
 MECHANICAL PERMIT APPLICATION.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD
 AND FIRE SUPPRESSION.PLEASE PROVIDE
 PLANS AND MANUFACTURER CUT SHEETS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-25 Cont ID  
Sent By pkrauss Date 2003-10-22 Time 12:57 Rev Time 0.50
Received By kstevens Date 2003-10-25 Time 14:43 Sent To  
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) THE FOLLOWING COMMENTS FROM THE FIRST
 REVIEW WERE NOT ADDRESSED. THE SAME
 COMMENT NUMBER FROM THE FIRST REVIEW
 WILL BE USED FOR CLAIRITY.
 1) SHT A-1 FOOD SERVICE APPROVAL COMMENT
 #3, SPECIFICATION WORKSHEETS SHALL BE
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SECTION 104..2.1
 3) SHT A-1 FOOD SERVICE EQUIPMENT SCHED.
 #29, GREASE INTERCEPTOR NOT APPROVED IN
 FOOD PREP, COOKING AREA. CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 SIZE OF THE GREASE INTERCEPTOR. WASTE
 ORDINANCE 2938-96. (561) 837-4074
 B) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2.
 C) GAS PLANS NOT APPROVED. SEPARATE
 PLANS TO BE SUBMITTED AT TIME OF GAS
 PERMIT APPLICATION. SEPARATE GAS PERMIT
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-08 Cont ID  
Sent By kstevens Date 2003-09-08 Time 14:10 Rev Time 2.00
Received By kstevens Date 2003-09-08 Time 14:10 Sent To  
Notes
2003-09-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT A-1 FOOD SERVICE APPROVAL COMMENT
 #3, SPECIFICATION WORKSHEETS SHALL BE
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SEC 104.2.1
 2) SHT A-1 FOOD SERVICE EQUIPMENT SCHED.
 #7 INDICATES "OPEN", BUT FLOOR PLAN
 SHOWS A RANGE. PLEASE CLAIRFY.
 3) SHT A-1 FOOD SERVICE EQUIPMENT SCHED.
 #29, GREASE INTECEPTOR NOT APPROVED IN
 FOOD PREP. COOKING AREA. CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 SIZE OF THE GREASE INTECEPTOR. WASTE
 ORDINANCE 2938-96. (561) 837-4074. ALT.
 CONTACT PERSON - MARIA ORTIZ (561) 837-
 4061.
 4) SHT M1 PLUMBING NOTES #1, ADOPTED
 CODE IS FBC-2001 PLUMBING. REVISE NOTES.
 5) SHT M1 GAS LOAD CALCULATIONS. ADOPTED
 CODE IS FBC-2001 FUEL GAS. REVISE NOTES.
 6) SHT M1 FLOOR PLAN/GREASE RISER, MOP
 SINK SHALL CONNECT TO GREASE SYSTEM.
 7) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1
 8) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 9) THE FOLLOWING COMMENTS ARE INFORMAT-
 ION FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 10) INFORMATIONAL: THE SHUT OFF VALVE &
 UNION "DOWNSTREAM OF SOLENOID VALVE ARE
 NOT REQUIRED.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]