| 2003-08-12 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03080423 |
| | ADD: 410 OLIVE DRIVE |
| | CONT: |
| | TEL: (954)650-0024 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) 3305.5 SEPERATION, A FENCE OR SOLID |
| | CONSTRUCTION AT LEAST 8 FT HIGH SHALL BE |
| | PROVIDED ON THE BUILDING SIDE OF THE |
| | WALKWAY. |
| | |
| | 2) 1803.2.1 HOW ARE YOU GOING TO RETAIN |
| | SOILS FROM THE RIGHT OF WAY FROM CAVING |
| | IN? THE ELEVATION ON THE WEST SIDE IS |
| | APPROX. 11.5', THE BOTTOM OF FOOTER"C" |
| | IS AT 3.75'? A DIFFERENCE OF 7.75'. |
| | THE BUILDING LINE IS ADJACENT TO THE |
| | PROPERTY LINE ON THE EAST, SOUTH & WEST |
| | SIDES OF THE PROPERTY,THE REPORT SUBMITT |
| | ED FROM ARDAMAN UNDER 7.1 SITE PREPARA- |
| | TION RECOMMENDATIONS, INDICATE THAT |
| | SHEET PILING MAY BE REQUIRED FOR THE |
| | (3) SIDES. THE CITY WILL REQUIRE THE |
| | SHEET PILING ON THE EAST, SOUTH & WEST |
| | SIDES. THE CITY WILL ALSO REQUIRE A SEAL |
| | ED COPY OF THE CANTILEVER SHEETPILE WALL |
| | ANALYSES, THERE WILL BE AT MOST A 2.25' |
| | TOE THAT THE CANTILEVERED SHEET PILE |
| | WILL BE WORKING WITH.THE SECOND ISSUE |
| | WILL BE THE VIBROFLOTATIONTAKING PLACE |
| | AT THE 3.75' ELEVATION LEVEL, THE CITY |
| | NEEDS INSURANCE THAT THE VIBROFLOTATION |
| | ADJACENT TO THE SHEET PILING WILL NOT EF |
| | FECT THE PERMITER WALL, NO INWARD MOVE- |
| | MENT OF THE SHEET PILING NOR DAMAGE TO |
| | THE ADJACENT SIDEWALKS, ROADWAY OR |
| | INTRASTRUCTURE. |
| | |
| | 4) PLEASE EXPLAIN YOUR PROCESS FOR |
| | DEWATERING, WELL POINT SYSTEM, WILL THIS |
| | BE ON THE INTERIOR SIDE OF THE SHEET |
| | PILING OR THE CITY SIDE? SEE7.1.3. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |