Plan Review Details - Permit 03080399
Plan Review Stops For Permit 03080399
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-08-17 Cont ID  
Sent By shill Date 2004-08-17 Time 09:04 Rev Time 0.50
Received By shill Date 2004-08-17 Time 09:04 Sent To PC
Notes
2004-08-17 00:00:00****CORRECTIONS****
 REVISION
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 TRACO S/H PRODUCT APPROVAL APPROVED
  
 1.)SEE ELECTRIC COMMENTS REGARDING
 WHITE OUT ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-08-17 Time 08:31 Rev Time 0.50
Received By shill Date 2004-05-04 Time 16:43 Sent To  
Notes
2004-05-04 00:00:00FRENCH DOOR PRODUCT APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-08 Time 07:39 Rev Time 1.00
Received By shill Date 2004-01-20 Time 14:35 Sent To E
Notes
2004-04-12 00:00:00PROVISO - SUBMIT PRODUCT APPROVALS
 FOR DOUBLE OUTSWING DOORS (NO SIDELITES)
 2868, +35.3/-38.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-12-17 Cont ID  
Sent By kstevens Date 2004-01-20 Time 09:35 Rev Time 0.50
Received By shill Date 2003-12-17 Time 19:28 Sent To  
Notes
2003-12-17 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST REGARDING
 SJE DESIGN & CONSTRUCTION INC.THE
 ENGINEERING AUTHORIZATION NUMBER
 PROVIDED IS DELINQUENT.YOU CANNOT
 PRACTICE ENGINEERING WITHOUT A CURRENT
 ENGINEERING LICENSE; DOING SO IS
 SUBJECT TO DISCIPLINARY ACTION BY THE
 FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-17 Time 11:53 Rev Time 1.00
Received By shill Date 2003-12-09 Time 16:40 Sent To  
Notes
2003-12-09 00:00:00****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 2.)SJE DESIGN & CONSTRUCTION IS
 REQUIRED TO HAVE THEIR ENGINEER
 AUTHORIZATION NUMBER AND GENERAL
 CONTRACTOR NUMBER ON THE TITLE BLOCK.
 HOWEVER, BOTH ARE DELINQUENT.ADDRESS.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)NO FEE FOR RESUBMITTAL - IMPACT
 FEES.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-08 Cont ID  
Sent By kstevens Date 2003-12-08 Time 07:29 Rev Time 1.00
Received By sthyng Date 2003-11-08 Time 11:50 Sent To  
Notes
2003-11-08 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 3.)SEE PREVIOUS CORRECTION LIST, ITEM
 #4, ENERGY CALCS REQUIRED FBC13-101.2.
 SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)THIS IS AN IMPROVEMENT OF OVER
 25% AND IS TO COMPLY WITH FBC3401.7.1.2.
 1, 2003 AMENDMENT (SMOKE DETECTORS AND
 GFIS WHERE REQUIRED).THIS MAY BE
 ADDRESSED BY A NOTE ON THE PLAN; CONFIRM
 WITH THE ELECTRIC PLAN REVIEWER.
  
 5.)NOTE THAT R4.2 WAS SPECIFIED IN THE
 WALL SECTION, NO ENERGY CALC SUBMITTED.
 IF A SHORT FORM IS SUBMITTED, R5 IS THE
 MINIMUM FOR AN EXTERIOR BLOCK WALL.
  
 6.)SEE PREVIOUS LIST IN REGARDS TO
 IMPACT FEES, 233-5025.
  
 7.)SEE PREVIOUS LIST, ITEM #13, SUBMIT
 A SECOND COPY OF THE HURRICANE SHUTTER
 PRODUCT APPROVAL.SUBMIT A HURRICANE
 SHUTTER INSTALLATION SCHEDULE, SEE
 ATTACHED.
  
 8.)ADDITIONAL FEES DUE, BZ231208 WITH
 THE PREVIOUS CORRECTION LIST.
  
 9.)THE ENGINEER'S TITLE BLOCK IS
 REQUIRED TO BE ON THE PLAN, FAC61G15-23.
 002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By btrobaug Date 2003-11-04 Time 12:44 Rev Time 2.50
Received By sthyng Date 2003-10-15 Time 12:59 Sent To  
Notes
2003-10-15 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 3.)PROVIDE AREA CALCULATIONS ON THE
 PLAN (EXISTING, PROPOSED, NEW TOTAL).
  
 4.)ENERGY CALCS REQUIRED FBC13-101.2.
 SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 5.)CHANGES DRAWN ON THE PLAN IN INK
 MUST BE INITIALED BY THE ENGINEER.
  
 6.)SPECIFY WALL INSULATION S1-A1.
  
 7.)NAILING FOR HETA20 CONFLICTS WITH
 THE CATALOG.
  
 8.)LOWEST FLOOR ELEVATION AT THE
 PERIMETER OF A MONOLITHIC FOUNDATION
 SHALL BE A MINIMUM OF 4" ABOVE FINISH
 GRADE, CITY OF WEST PALM BEACH AMEND. TO
 THE FBC1804.1.7.
  
 9.)WALL SECITON SHOWS A 16 X 12
 MONO.FOOTING, CONFLICTS W/FLOOR PLAN.
 REVISE WALL SECTION.
  
 10.) FLOOR PLAN GIVES A ROOM DESIGNATION
 OF "NEW MASTER BATHROOM".THIS ROOM IS
 20X19 WITH EGRESS WINDOWS.IF THIS IS
 A BEDROOM, CORRECTLY LABEL THIS ROOM.
  
 11.)WINDOW AT SHOWER AND TUB ARE
 REQUIRED TO BE SAFETY GLASS FBC2405.1.
  
 12.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 13.)SUBMIT A SECOND COPY OF THE
 HURRICANE SHUTTER PRODUCT APPROVAL.
  
 14.)ADDITIONAL FEES DUE, $249.52
 (VALUE ADJUSTMENT AND RADON).SEE
 ATTACHED BZ231208.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-10-29 Cont ID  
Sent By dpalmer Date 2004-10-29 Time 10:07 Rev Time 0.33
Received By dpalmer Date 2004-10-29 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-27 Time 10:59 Rev Time 0.50
Received By dpalmer Date 2004-09-21 Time 13:51 Sent To  
Notes
2004-09-21 00:00:00****** PROVISO/REVISION ************
  
 1)NOTE: PLEASE SEE EXSITING DWELLING
 MUST MEET FBC CHAPTER 34
 3401.7.1.2.1
  
 SD'S INSIDE AND OUTSIDE ALL SLEEPING RMS
 AND ALL RECEPTS REQUIREDTO BE GFI
 PROTECTD TO BE VERIFIED. 210.8

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-09-14 Time 11:46 Rev Time 0.33
Received By dpalmer Date 2004-08-17 Time 08:31 Sent To B
Notes
2004-08-17 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE ORIG PLANS HAVE NOW
 BEEN VOIDED DUE TO CHANGES MADE TO PLANS
 WITH WHITE-OUT AND PEN. PLANS ARE SIGNED
 AND SEALED BY AN ENGINEER.
 PLEASE HAVE THESE PLANS RE-DONE BY THE
 ENGINEER OF RECORD AS REQUIRED UNDER
 FS 471/471.025
 PLEASE SEE NEW ELECTRICAL SHEET SUBMIT-
 -TED MUST ALSO BE DONE BY THE ENGINEER
 OF RECORD.
  
 2)NOTE: PLEASE SEE NEW REVISED SHEET
 NOW SHOWS A NEW SUB PANEL.
 PLEASE INCLUDE REVISED RISER DIAGRM FOR
 NEW EQUIPMENT.
 PLEASE ALSO INCLUDE PANEL SCHEDULES FOR
 THIS TO SHOW MIN REQUIRED CIRCUITS PER
 2002 NEC.
 PLEASEALSO INCLUDE LOAD CALC FOR NEW
 A/C,SPA TUB,GEN LTS AND RECEPTS.
 215.5/ 220.31B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-08-10 Time 07:47 Rev Time 0.25
Received By dpalmer Date 2004-04-16 Time 19:30 Sent To P
Notes
2004-04-16 00:00:00REVISED BATH AREA BEFORE MAKING COLOR
 COPY OF ORIG PLAN.
 NOTEDON PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-13 Cont ID  
Sent By shill Date 2004-04-12 Time 16:30 Rev Time 0.50
Received By btrobaug Date 2004-01-13 Time 11:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-18 Cont ID  
Sent By shill Date 2004-01-12 Time 16:30 Rev Time 0.50
Received By btrobaug Date 2003-11-18 Time 15:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-18 Time 09:58 Rev Time 0.50
Received By btrobaug Date 2003-11-04 Time 12:28 Sent To B
Notes
2003-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE COMMENTS FROM THE LAST
 REVIEW WERE NOT ADDRESSED.PLEASE MAKE
 THE FOLLOWING ADDITIONS AND OR NOTES TO
 PLANS.
  
 1} SHOW RECEPTACLE SPACING PER 210.52.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IN ADDITION TO THESE COMMENTS PLEASE
 NOTE THAT ALL PLANS THAT ARE SIGNED AND
 SEALED BY AN ENGINEER ARE REQUIRED PER
 61G15-23.002 TO HAVE A TITLE BLOCK.
 THIS AND SIMILAR COMMENTS REGARDING NON
 COMPLIANCE WITH ART 471 FS.STATUTES
 HAVE COMPELLED US TO RETAIN ONE SET OF
 PLANS TO BE FILED AND TURNED INTO THE
 FPBE FOR SAID VIOLATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-28 Time 08:54 Rev Time 0.50
Received By btrobaug Date 2003-10-08 Time 16:17 Sent To P
Notes
2003-10-08 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 SHOW RECEPTACLES PER 2002 NEC.BEDROOMS
 PER 210.12,BATHS PER
 210.11(C)(3).RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 10:59 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 10:59 Sent To E
Notes
2004-10-27 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 11:46 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 11:46 Sent To E
Notes
2004-09-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-08-10 Time 07:47 Rev Time 0.00
Received By csiegber Date 2004-08-10 Time 07:47 Sent To E
Notes
2004-08-10 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:11 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 07:39 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 07:39 Sent To B
Notes
2004-04-08 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 16:28 Rev Time 0.00
Received By shill Date 2004-01-12 Time 16:28 Sent To E
Notes
2004-01-12 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 11:53 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 11:53 Sent To B
Notes
2003-12-17 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-18 Time 09:58 Rev Time 0.00
Received By csiegber Date 2003-11-18 Time 09:58 Sent To E
Notes
2003-11-18 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 08:54 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 08:53 Sent To E
Notes
2003-10-28 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 11:18 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 11:18 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-24 Cont ID  
Sent By mmclean Date 2003-10-01 Time 12:43 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 15:19 Sent To Z
Notes
2003-09-24 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 15:33 Rev Time 0.00
Received By alange Date 2003-08-08 Time 15:33 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 13:55 Rev Time 0.40
Received By pkrauss Date 2004-08-02 Time 13:55 Sent To  
Notes
2004-08-02 00:00:00PER MEETING WITH MARVIN (OWNER/BUILDER).
 NO MECHANICAL PERMIT REQUIRED.DUE TO
 THE CONSTRUCTION OF THE ROOF, DUCTWORK
 CANNOT BE RUN TO THE EXISTING A/C SYSTEM
 THEREFORE, A MAYTAG 8,000 BTU WALL UNIT
 WILL BE INSTALLED.ADDTION IS 360 SQ FT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-10 Cont ID  
Sent By kstevens Date 2003-10-09 Time 08:23 Rev Time 0.15
Received By pkrauss Date 2003-10-10 Time 11:10 Sent To B
Notes
2003-10-10 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH THE MECHANICAL PERMIT APPLICATION.
  
 1.A COMPLETED FORM 600C.
 2.INDICATE IF A/C EQUIPMENT IS NEW
 OR EXISTING.PROVIDE EQUIPMENT
 INFORMATION (MAKE, MODEL, SEER, ETC)
 3.INDICATE DUCT & GRILLE SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 09:17 Rev Time 0.50
Received By kstevens Date 2004-04-29 Time 09:17 Sent To  
Notes
2004-04-29 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-04-17 Cont ID  
Sent By alange Date 2004-04-22 Time 11:11 Rev Time 0.50
Received By kstevens Date 2004-04-17 Time 07:34 Sent To  
Notes
2004-04-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. SHOWER BATH IS
 SHOWN OUTSIDE OF THE HOUSE AND NOT TO
 THE RIGHT SIDE OF HOUSE AS SHOWN ON THE
 FLOOR PLAN. SUBMIT A SANITARY RISER DIA-
 GRAM THAT REFLECT THE FLOOR PLAN AND THE
 ACTUAL INSTALLATION OF THE SANITARY
 PIPING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-20 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 19:30 Rev Time 0.33
Received By kstevens Date 2004-01-20 Time 09:35 Sent To B
Notes
2004-01-20 00:00:00PASSED/PROVISO - REVISION REQUIRED SHOW-
 ING SHOWER BATHROOM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-08 Cont ID  
Sent By btrobaug Date 2004-01-13 Time 11:24 Rev Time 0.50
Received By kstevens Date 2003-12-08 Time 07:29 Sent To B
Notes
2003-12-08 00:00:00PASSED PROVISO - REVISION REQUIRED FOR
 SHOWER BATH

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-09 Cont ID  
Sent By btrobaug Date 2003-11-18 Time 16:10 Rev Time 0.33
Received By kstevens Date 2003-10-09 Time 08:23 Sent To M
Notes
2003-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN CODE
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. THE FLOOR PLAN
 SHOWS A TUB AND THE RISER DIAGRAM SHOWS
 A SHOWER. PLEASE CLAIRFY. (ALSO SEE RED
 LINE CORRECTION TO RISER SHOWING CORRECT
 ISOMETRIC). SECTION 104.2.1
 2) SEE ATTACHED SHEET CONCERNING INFOR-
 MATION REQUIRED PER 61G1-16.004. THIS
 INFORMATION IS REQUIRED AND SHALL BE ON
 EACH SHEET. PLEASE BE AWARE OF THIS FOR
 FUTURE PLANS SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2003-10-01 Cont ID  
Sent By mmclean Date 2003-10-01 Time 12:43 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-18 Cont ID  
Sent By csiegber Date 2003-09-24 Time 15:19 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-08-18 00:00:008/18/03 DENIED, NEED 2COPY OF SURVEY &
 2 COPY OF PLANS CALLED CONTRACTOR MOBIL
 PHONE NO LONGER IN SERVICE MM