Plan Review Details - Permit 03080392
Plan Review Stops For Permit 03080392
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By sthyng Date 2003-10-09 Time 16:13 Rev Time 1.00
Received By sthyng Date 2003-10-09 Time 15:18 Sent To  
Notes
2003-10-09 00:00:00PROVISO - SUBMIT MULLION PRODUCT
 APPROVAL BEFORE WINDOW/DOOR INSTALLATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-26 Cont ID  
Sent By jleech Date 2003-10-06 Time 17:32 Rev Time 2.00
Received By sthyng Date 2003-08-26 Time 14:17 Sent To  
Notes
2003-08-26 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED (ROOF,
 ELECTRIC, GAS, PLUMBING, MECHANICAL).
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 ISSUED BY THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)ADDITIONAL FEES DUE (RADON), $2.32.
 SEE ATTACHED BZ228777, PAY AT CASHIER.
  
 4.)REGARDING THE ENERGY CALCS, FAC
 61G1-16.003, SEAL THE ENERGY CALCS AND
 SIGNED PERSONALLY (NOT A PHOTOCOPY).
  
 5.)PRODUCT APPROVALS FOR THE
 IMPACT CASEMENT WINDOWS AND IMPACT
 GLAZED DOOR WERE SUBMITTED.ALSO
 REQUIRED ARE MULLIONS AND FIXED GLASS
 WINDOWS(SIDELITES FOR DOORS AND WINDOW).
 PRODUCT APPROVALS NOT SUBMITTED WILL
 REQUIRE A SEPARATE PERMIT APPLICATION
 LATER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 16:30 Rev Time 0.50
Received By btrobaug Date 2003-09-23 Time 15:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-15 Cont ID  
Sent By dbaxter Date 2003-09-22 Time 14:11 Rev Time 1.00
Received By btrobaug Date 2003-08-14 Time 14:19 Sent To P
Notes
2003-08-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1: THE EXISTING SERVICE IS INDICATED AS
 225 AMPS.THE 1/0 FEEDER CONDUCTORS ARE
 RATED FOR 175 AMPS,AND THE #4 GEC IS
 NOT LARGE ENOUGH FOR A 225 AMP
 SERVICE.PLEASE CORRELATE.
  
 2: PLEASE INDICATE WHERE THE OCP IS FOR
 THE "NEW PANEL".AGAIN PLEASE NOTE THE
 1/0 FEEDERS ARE RATED @ 175 AMPS,SEE
 RISER.THE SERVICE CALCULATION INDICATES
 A 200 AMP SERVICE.
  
 3: PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210.63.
  
 5: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 SEE REVIEWED SET.
  
 6: PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 7: THE PANEL LOCATION IN THE GARAGE MUST
 COMPLY WITH 110.26.SEE 110.26(E) RE:
 HEAD SPACE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
  
 NOTE: PLEASE BRING THE REVIEWED SET IN
 WITH THE CORRECTED SET TO EXPEDITE THE
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-22 Cont ID  
Sent By dbaxter Date 2003-09-22 Time 14:11 Rev Time 0.00
Received By dbaxter Date 2003-09-22 Time 14:11 Sent To E
Notes
2003-09-22 00:00:00TO BTROBAUGH DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 11:11 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 11:11 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By sgraham Date 2003-08-12 Time 14:49 Rev Time 0.00
Received By alange Date 2003-08-08 Time 15:44 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By kstevens Date 2003-08-16 Time 07:08 Rev Time 0.35
Received By pkrauss Date 2003-08-21 Time 12:45 Sent To B
Notes
2003-08-21 00:00:00PROVISO:
  
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-06 Cont ID  
Sent By jleech Date 2003-10-06 Time 17:32 Rev Time 0.33
Received By jleech Date 2003-10-06 Time 17:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-16 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 16:30 Rev Time 0.50
Received By kstevens Date 2003-08-16 Time 06:55 Sent To M
Notes
2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUPS SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SEC 909.1
 WASH MACHINE & VEG. SINK SHALL NOT DRAIN
 THRU BATHROOM PIPING.
 B) KITCHEN SINK NOT VENTED.
 C) NEW BAR SINK NOT SHOWN ON RISER.
 D) EXTRA SHOWER UPSTREAM OF KITCHEN
 SINK ON RISER. PLEASE CLAIRFY
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-12 Cont ID  
Sent By alange Date 2003-08-08 Time 15:44 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved