Plan Review Details - Permit 03080349
Plan Review Stops For Permit 03080349
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-11-06 Cont ID  
Sent By rbrown Date 2003-11-05 Time 14:24 Rev Time 0.00
Received By rbrown Date 2003-11-05 Time 14:24 Sent To P
Notes
2003-11-06 00:00:00COMMENTS NOW ADDRESSED.PASSED
2003-11-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/28/03:
  
 3) FBC 11-4.15SHEET A2 HAS BEEN RED-
 LINED TO SHOW A MAXIMUM SPOUT HEIGHT OF
 36" ABOVE FLOOR FOR THE WATER FOUNTAIN.
  
 6) FBC 1601ANNOTATE THE PLANS TO
 SPECIFY THE RAFTER AND BEAM FASTENERS,
 AS PER THE 2003 SIMPSON CATALOGUE, FOR
 THE H16 ANCHORS NOW SPECIFIED AT EACH
 ROOF TRUSS ABOVE 'RECEIVING'.
  
 7) FBC 1601ANNOTATE THE PLANS TO
 SPECIFY THE RAFTER AND LEDGER FASTENERS,
 AS PER THE 2003 SIMPSON CATALOGUE, FOR
 FOR THE LSU26 AND LSTA12 NOW SPECIFIED
 AT EACH CANOPY ROOF TRUSS.
  
 13) NOTE: IF THE SUBMITTED PLANS ARE
 REVISED MANUALLY, EACH REVISION SHALL BE
 INITIALLED AND DATED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-31 Time 10:44 Rev Time 0.00
Received By rbrown Date 2003-10-28 Time 18:59 Sent To  
Notes
2003-10-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/22/03:
  
 3) FBC 11-4.15SHEET A2 HAS BEEN RED-
 LINED TO SHOW A MAXIMUM SPOUT HEIGHT OF
 36" ABOVE FLOOR FOR THE WATER FOUNTAIN.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1606.2.4SPECIFY ANCHORS FOR THE
 SLOPED ROOF ABOVE 'RECEIVING'.THE WIND
 ENGINEERING / STRUCTURAL NOTES STILL DO
 NOT STATE THE DESIGN PRESSURES FOR THE
 ROOF STRUCTURE DESIGN.
  
 7) FBC 1601STRUCTURAL DETAILS FOR
 FASTENING OF THE NEW SLOPED CANOPIES.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.IT IS NOTED THAT SHEET A0,
 WIND ENGINEERING / STRUCTURAL NOTES,
 NOW INCLUDES A NOTE STATING THE UPLIFT
 (83 POUNDS) AT EACH TRUSS ANCHOR.THIS
 IS INSUFFICIENT FOR THE DESIGN WIND
 PRESSURES FOR THIS LOCATION.THE LSU24
 ANCHOR SPECIFIED ON SHEET S1
 (SECTION AA) IS NOT A VALID 2003 SIMPSON
 CATALOGUE REFERENCE.ALSO THE SPECIFIED
 RR RIDGE RAFTER CONNECTOR IS NOT
 SUITABLE FOR THIS APPLICATION.IT IS
 DESIGNED FOR RAFTER TO RIDGE CONNECTIONS
 (IN COMPRESSION) AND IS NOT APPROPRIATE
 FOR THE TENSILE LOADING THAT MUST BE
 RESISTED BE THE RAFTER IN MONOSLOPE
 CANOPY ROOF UNDER GRAVITY LOAD.SPECIFY
 VALID ANCHOR REFERENCES SUITABLE FOR THE
 APPLICABLE LOADING (TO INCLUDE THE
 DESIGN PRESSURES REFERENCED IN COMMENT 6
 ABOVE).
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-22 Cont ID  
Sent By rbrown Date 2003-08-22 Time 14:24 Rev Time 0.00
Received By rbrown Date 2003-08-22 Time 14:24 Sent To  
Notes
2003-08-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 308.2.1 DECLARE ANY HAZARDOUS
 MATERIALS OR PROCESSES TO BE EMPLOYED/
 STORED IN LABORATORY FACILITY.
  
 2) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS.THE DOORS BETWEEN 'RECEIVING'
 AND 'GROSSING' SHALL HAVE 18" CLEARANCE
 BETWEEN THE STRIKE EDGE OF THE DOORS
 AND THE ADJACENT WORK BENCH ON THE PULL
 SIDE OF THE DOORS FOR ACCESSIBILITY.
 REF. FIG. 27A
  
 3) FBC 11-4.15 AMEND THE PLANS TO SHOW
 THE REQUIRED ACCESSIBILITY HEIGHTS AND
 CLEARANCES AT THE WATER FOUNTAIN.
 REF. FIG. 27
  
 4) FBC* 104.2.1SUBMIT DETAILS FOR THE
 PROPOSAL TO RAISE THE FOOR LEVEL OF THE
 EXISTING BUILDING.
  
 5) FBC* 104.2.1.2SUBMIT MANUFACTURER'S
 DETAILS TO JUSTIFY THE STATED ONE-HOUR
 FIRE-RATING OF THE 'CHEM ROOM' POCKET
 DOOR.
  
 6) FBC 1606.2.4SPECIFY ANCHORS FOR THE
 SLOPED ROOF.THE WIND ENGINEERING AND
 STRUCTURAL NOTES DO NOT STATE THE DESIGN
 WIND PRESSURES FOR THE ROOF.
  
 7) FBC 1601SUBMIT STRUCTURAL DETAILS
 FOR FASTENING OF THE NEW SLOPED
 CANOPIES.IS THERE AN EXISTING CONCRETE
 CANOPY AT EACH LOCATION (THE AS-BUILT
 PLAN DOES NOT SHOW THEM)?
  
 8) FBC 1707.4SUBMIT PRODUCT APPROVALS
 FOR THE NEW WINDOWS AND EXTERIOR DOORS.
  
 9) FBC* F102.2.4ALL ROOF COVERINGS IN
 THE FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF CLASS A OR B ROOF
 COVERINGS AS DEFINED IN FBC 1505.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE FOR BOTH THE RE-ROOF AND THE
 NEW STANDING SEAM ROOF WHICH SHALL BE
 LISTED AS CLASS A OR B BY AN APPROVED
 TESTING AGENCY, OR SHALL MEET THE
 THICKNESS/GAUGE/WEIGHT CRITERIA
 SPECIFIED IN TABLE FBC 1507.3.9.2
  
 10) FBC* F102.2.7ARCHITECTURAL TRIM ON
 BUILDINGS IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS.THE SIDING SHOWN ON THE
 ELEVATIONS (SHEET A3) IS STATED AS BOTH
 "HADIE-PLANK" AND "HARDIE-PLANK".IN
 THE REVIEW IT HAS BEEN ASSUMED THAT THE
 PROPOSED SIDING IS 'HARDIPLANK' (KNOWN
 TO BE NON-COMBUSTIBLE) BY JAMES HARDIE
 SIDING PRODUCTS.PLEASE ADVISE IF THIS
 ASSUMPTION IS NOT CORRECT.ANNOTATE THE
 PLANS.
  
 11) FBC* F102.2.8IN THE FIRE DISTRICT,
 CANOPIES SHALL BE OF NON-COMBUSTIBLE
 MATERIAL OR FIRE-RETARDANT WOOD.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE
  
 12) FBC* F102.2.9ROOF MOUNTED
 MECHANICAL EQUIPMENT.SUPPORTS FOR
 EQUIPMENT PLACED ABOVE THE ROOF OF ANY
 BUILDING WITHIN THE FIRE DISTRICT SHALL
 BE OF NON-COMBUSTIBLE CONSTRUCTION.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 06:03 Rev Time 0.50
Received By dpalmer Date 2003-11-07 Time 05:59 Sent To  
Notes
2003-11-07 00:00:00RED LINEDGEC TO CWP. 250.50
 ARC FAULT SHOWN FOR BEDROOMS????

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 06:35 Rev Time 1.00
Received By dpalmer Date 2003-10-27 Time 06:35 Sent To  
Notes
2003-10-27 00:00:00ITEMS REDLINED AND NOTED ON PLANS.
 CWP FOR GRND ELEC SYSTEM. 250.50

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-25 Cont ID  
Sent By dpalmer Date 2003-08-25 Time 17:00 Rev Time 1.50
Received By dpalmer Date 2003-08-25 Time 16:59 Sent To  
Notes
2003-08-25 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE 422.13 FOR SIZING OF
 OCP FOR WATER HEATER. SHOWN AS 1P30A?
  
 2)NOTE: PLEASE CORRELATE OCP/KW/AWG FOR
 AHU'S AND COND UNITS. 424.3B
  
 3)NOTE: PLEASE SEE CONDUCTORS FROM MAINS
 TO PANELS. SHOWN AS #3'S. PLEASE SEE
 310.16
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3/230.42 ETC
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAINS. 110.9 IT IS NOTED FOR BRANCH
 BRKRS.
  
 6)NOTE: PLEASE SEE 600.5 FOR REQ'D SIGN
 CIRCUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By mcarsill Date 2003-10-23 Time 07:46 Rev Time 0.00
Received By mcarsill Date 2003-10-23 Time 07:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-27 Cont ID  
Sent By mcarsill Date 2003-08-27 Time 07:23 Rev Time 0.00
Received By mcarsill Date 2003-08-27 Time 07:23 Sent To  
Notes
2003-08-27 00:00:001) PLEASE INDICATE WHAT CHEMICALS WILL
 BE STORED IN THE CHEMICAL ROOM # 114.
 WILL THERE BE ANY FLAMMABLES,
 COMBUSTIBLES, CORROSIVES, TOXICS, ETC.
 PLEASE PROVIDE A COMPLETE LIST
 OF CHEMICALS AND STORAGE QUANTITIES.
 ALSO PLEASE INDICATE IF GASES, SOLIDS,
 OR LIQUIDS.
  
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR 3086 POCKET ONE HOUR FIRE DOOR.
 PLEASE BE ADVISED THAT ALL FIRE RATED
 DOORS ARE REQUIRED TO BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
  
 3) PLEASE DEFINE THE FOLLOWING TERMS
 GROSSING, EMBEDDING, H+E STAIN, SPECIAL
 STAIN.
  
 4) NO FIRE EXTINGUISHERS SHOWN ON THE
 PLANS.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 6) WHAT WILL BE STORED IN THE CLOSETS.
  
 7) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 8) WHAT WILL BE EXHAUSTED FROM THE HOOD
 LOCATED IN THE CHEM ROOM. A SEPARATE
 PLAN AND PERMIT WILL BE REQUIRED.
  
 9) WHAT IS THE PURPOSE 30" HIGH WORK
 BENCHES NEAR THE MAIN EXIT DOOR.
  
 10) PLEASE INDICATE OCCUPANT LOADS
 FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 14:47 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 14:47 Sent To M
Notes
2004-11-08 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 13:41 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 13:41 Sent To M
Notes
2004-08-03 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:08 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 15:08 Sent To P
Notes
2004-05-28 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 11:56 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 11:56 Sent To M
Notes
2004-05-07 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-17 Cont ID  
Sent By csiegber Date 2003-10-17 Time 13:55 Rev Time 0.00
Received By csiegber Date 2003-10-17 Time 15:33 Sent To  
Notes
2003-10-17 00:00:00TO COMM BD#34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-21 Cont ID  
Sent By btrobaug Date 2003-08-21 Time 11:41 Rev Time 0.00
Received By btrobaug Date 2003-08-21 Time 11:39 Sent To  
Notes
2003-08-21 00:00:00COMM BOARD #6./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 14:17 Rev Time 0.00
Received By alange Date 2003-08-08 Time 14:17 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-11-29 Cont ID  
Sent By pkrauss Date 2004-11-29 Time 07:04 Rev Time 0.55
Received By pkrauss Date 2004-11-29 Time 07:04 Sent To  
Notes
2004-11-29 00:00:00ORIGINAL PLANS COULD NOT BE LOCATED FOR
 COMPARISION.SHOULD THE APPROVED PLANS
 (ORIGINAL SET) BE DRAWN BY A MECHANICAL
 ENGINEER, ALL REVISIONS SUBSEQUENT
 SHALL
 BE BY THE ENGINEER OF RECORD.
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS ON
 THE
 JOBSITE AT THE TIME OF INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-08-10 Cont ID  
Sent By pkrauss Date 2004-08-09 Time 10:39 Rev Time 0.35
Received By pkrauss Date 2004-08-09 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-11-07 Cont ID  
Sent By csiegber Date 2004-08-03 Time 13:41 Rev Time 0.40
Received By pkrauss Date 2003-11-07 Time 09:02 Sent To  
Notes
2003-11-07 00:00:00PROVISO:2ND REQUEST
 1.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE ROOF CURBS TO THE RTU'S.SEE
 ATTACHED REQUIREMENTS.
  
 PLEASE PROVIDE SUBMITTAL PRIOR TO
 ROUGH INSPECTION.
  
 2.CONDENSATE DRAIN SHALL COMPLY WITH
 2001 FBC(M) 307.2.1 #2 AND #3.
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION TO ALARM
 STROBE IN NORMALLY OCCUPIED AREAS PER
 2001 FBC(M) 606.2.2 & NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-31 Cont ID  
Sent By pkrauss Date 2003-10-31 Time 10:09 Rev Time 0.50
Received By pkrauss Date 2003-10-31 Time 10:02 Sent To B
Notes
2003-10-31 00:00:00PROVISO:
 1.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE ROOF CURBS TO THE RTU'S.
 (SEE ATTACHED)
  
 2.CONDENSATE DRAIN SHALL COMPLY WITH
 2001 FBC(M) 307.2.1 #2 AND #3.
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED WITH NOTIFICATION TO ALARM
 STROBE IN NORMALLY OCCUPIED ARES AS PER
 2001 FBC(M) 606.2.2 & NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By pkrauss Date 2003-08-28 Time 14:02 Rev Time 0.40
Received By pkrauss Date 2003-08-28 Time 14:02 Sent To  
Notes
2003-08-28 00:00:00DENIED:
  
 1. PROVIDE OUTSIDE AIR CALUCALTIONS AS
 PER 2001 FBC(M) TABLE 403.3
  
 2. PROVIDE MSDS SHEETS FOR THE CHEMICALS
 TO BE USED IN THE "CHEM ROOM".
  
 3. INDICATE HOW CHEMICALS ARE TO BE
 STORED.
  
 4. PROVIDE INFORMATION ON THE EXHAUST
 FAN. (MAKE, MODEL, CFM, ETC)
  
 5. BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-06-11 Cont ID  
Sent By kstevens Date 2004-06-11 Time 15:03 Rev Time 1.00
Received By kstevens Date 2004-06-11 Time 15:03 Sent To  
Notes
2004-06-11 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) REVISIONS AS SUBMITTED NOT APPROVED.
 NO HAND DRAWN REVISIONS. NEW SHEETS REQD
 SUBMIT NEW SHEETS WITH ALL CHANGES. SHOW
 REVISION NUMBER AND CLOUD CHANGES.
 SECTION 104.2.1
  
 2) ALL REVISIONS ON FLOOR PLANS SHALL BE
 REFLECTED ON THE RISER DIAGRAMS. SEE
 PROVISOS AND RED LINE CORRECTIONS TO
 BE MADE ON REVISION FROM STAMPED SET OF
 PLANS. ALL PROVISO AND RED LINE CORRECT-
 IONS SHALL BE REVISED AND SHOWN ON THE
 REVISION SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-11-20 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:08 Rev Time 2.00
Received By kstevens Date 2003-11-20 Time 17:55 Sent To  
Notes
2003-11-20 00:00:00 
  
  
  
 PASSED/PROVISO
  
 PASSED SUBJECT TO RESPONSE FROM RODNEY
 COMPO CONCERNING REQUIREMENT FOR A
 DILUTION TANK FOR CHEMICAL LAB.
 NO PLUMBING SHALL BE INSTALLED UNTILL A
 RESPONSE HAS BEEN ISSUED. IF A DILUTION
 TANK IS REQUIRED THAN A REVISION WILL BE
 REQUIRED WITH THE TANK INCLUDED.
  
 THE SERVICE SINK SHALL CONNECT DOWN-
 STREAM OF THE BATHROOM GROUP. SECTION
 909.1 - A REVISION WILL BE REQUIRED FOR
 THE RED LINE CORRECTION SHOWN ON THE
 SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-29 Cont ID  
Sent By rbrown Date 2003-11-06 Time 17:29 Rev Time 1.00
Received By kstevens Date 2003-10-29 Time 17:35 Sent To  
Notes
2003-10-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE, (561)
 837-4074. A DILUTION TANK MAY BE REQUIR-
 ED FOR THE CHEMICALS.
  
 2) SHT A2 THE SANITARY RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 THE LAV PAST THE EYEWASH IS NOT SHOWN
 ON THE FLOOR PLAN. EYE WASH SHALL BE
 DOWNSTREAM OF THE FLOOR DRAIN. NO LUNCH
 ROOM SINK SHOWN ON THE RISER DIAGRAM.
 THIS SHALL TIE INTO THE LINE FOR THE
 DRINKING FOUNTAINS.
 3) SEPARATE GAS PERMIT REQUIRED FOR GAS
 WORK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-02 Cont ID  
Sent By kstevens Date 2003-09-02 Time 10:36 Rev Time 1.50
Received By kstevens Date 2003-09-02 Time 10:35 Sent To  
Notes
2003-09-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 NEC-99
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMINSTRATION
 CODE.
  
 1) SHT A2 INDICATE NATURE OF WORK BEING
 PERFORMED. LIST ALL CHEMICALS & HAZARD-
 OUS MATERIALS BEING USED. SUBMIT MSDS
 SHEETS FOR ALL CHEMICALS AND HAZARDOUS
 MATERIALS. AN EMERGENCY EYE WASH/SHOWER
 MAY BE REQUIRED AS A RESULT OF INFORMAT-
 ION RECIEVED FROM MSDS SHEETS. SECTION
 104.2.1.
 2) CONTACT RODNEY COMPO (561) 837-4074
 OR MARIA ORTIZ (561) 837-4061. A DILUT-
 ION TANK MAY BE REQUIRED FOR THE CHEM-
 ICALS.
 3) DETAIL REQUIRED FOR DRINKING FOUNTAIN
 PER 11-4.15, SPOUT HEIGHT 11-4.15.2,
 CLEARANCES/CLEAR FLOOR SPACE 11-4.15.5.
 ALSO PROVISIONS FOR THOSE WHO HAVE DIFF-
 ICULTY BENDING OR STOOPING PER SECTION
 11-4.1.3(10)(A)
 4) SHT A2 PLUMBING RISER, BREAK ROOM
 SINK SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. (SEE RED LINE
 CORRECTIONS) SECTION 909.1
 5) SHT A2 PLUMBING RISER DOES NOT RE-
 FLECT THE FLOOR PLAN. ONE SINK SHALL BE
 CONNECTED TO THE RIGHT SIDE OF THE BLDG.
 DRAIN. (SEE RED LINE CORRECTION)
 6) A SERVICE SINK IS REQUIRED PER SECT-
 ION 403.1
 7) SECTION 422-17 NEC, PROTECTION OF
 COMBUSTABLE MATERIAL. EACH ELECTRICALLY
 HEATED APPLIANCE THAT IS INTENDED BY
 SIZE, WEIGHT, AND SERVICE TO BE LOCATED
 IN A FIXED POSITION SHALL BE PLACED SO
 AS TO PROVIDE AMPLE PROTECTION BETWEEN
 THE APPLIANCE AND ADJACENT COMBUSTIBLE
 MATERIAL. - THE ELECT. WATER HEATER
 SHALL BE IN A SEPARATE CLOSET OR A WALL
 6" FROM W/H SHALL BE INSTALLED TO PRE-
 VENT STORAGE OF COMBUSTABLE MATERIAL
 FROM BEING PLACED NEXT TO THE HEATER.
 8) SUBMIT DETAIL FOR BREAK ROOM SINK.
 SHOW COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS. - CLEAR FLOOR SPACE -
 HEIGHT - KNEE CLEARANCE - DEPTH - EX-
 POSED PIPES & SURFACES - FAUCETS.
 9) SHT S2 SUBMIT CALCULATIONS FOR ROOF
 DRAINS. SHOW SQUARE FOOTAGE OF ROOF AND
 ADD 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPET WALLS. IF GUTTER AND
 DOWNSPOUTS INDICATE SIZE OF DOWNSPOUTS
 & LOCATION. INDICATE SIZE OF GUTTER AND
 SLOPE PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 10) APPLICATION INDICATES IRRIGATION
 WORK TO BE DONE. SEPARATE PERMIT/PLANS
 REQUIRED FOR IRRIGATION.
 11) SHT A1, ALL REMOVED AND CAPPED
 PLUMBING LINES SHALL BE INSPECTED PRIOR
 TO COVERING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2003-11-20 Cont ID  
Sent By kstevens Date 2003-11-20 Time 18:30 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-18 Cont ID  
Sent By sgraham Date 2003-08-18 Time 14:16 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***