Plan Review Details - Permit 03080314
Plan Review Stops For Permit 03080314
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-07 Cont ID  
Sent By rbrown Date 2003-10-07 Time 15:34 Rev Time 0.00
Received By rbrown Date 2003-10-07 Time 15:33 Sent To  
Notes
2003-10-07 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 DESIGN PRESSURE RATING OF THE SUBMITTED
 MULLION PRODUCT APPROVAL NOA# 02-0423.01
 LIMITS WINDOW HEIGHT TO 7 FEET MAX FOR
 THE NEW 9 FEET WIDE WINDOW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-10-01 Time 10:31 Rev Time 0.00
Received By rbrown Date 2003-09-19 Time 14:19 Sent To FIRE
Notes
2003-09-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/20/03:
  
 6) PRODUCT APPROVALS:
  
 A) THE SUBMITTED ARCH ALUMINUM
 STOREFRONT SYSTEM PRODUCT APPROVAL NOA#
 00-1220.05 IS MISSING TWO OF THE EIGHT
 DRAWING SHEETS.ALSO, THE DRAWING
 SHEETS PROVIDED ARE POOR COPIES AND
 CANNOT BE READ.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT SIZES/MATERIALS ARE TO BE USED
  
 B) THE SUBMITTED FLORIDA STORM PANELS
 PRODUCT EVALUATION REPORT #2009 DOES NOT
 INCLUDE THE FOUR DRAWING SHEETS
 REFERENCED ON SHEET 2, SECTION 5.1
 UNDER 'SUBSTANTIATING DATA'.SUBMIT
 COMPLETE AND LEGIBLE COPIES.
 COPIES OF SBCCI AND ICC EVALUATION SVCS
 REPORTS CAN BE PRINTED FROM THE WEBSITE
 WWW.SBCCIES.ORG/EVALUATION/INDEX.HTM
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT SIZES/MATERIALS ARE TO BE USED
  
 C) THE SUBMITTED FENESTRATION TESTING
 LABORATORY INC. REPORT L-1427 FOR THE
 ARCH ALUMINUM OUTSWING DOOR CAN ONLY BE
 ACCEPTED IF SUPPORTED BY SITE SPECIFIC
 ENGINEERING IN FORM OF A PRODUCT
 APPROVAL SUBMITTAL FORM (BLANK COPY
 ATTACHED).ALTERNATIVELY, SUBMIT TWO
 COPIES OF A MIAMI-DADE PRODUCT APPROVAL
 OR A SBCCI/ICC EVALUATION REPORT FOR A
 SUITABLE DOOR.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT SIZES/MATERIALS ARE TO BE USED
  
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-09-19 Time 11:22 Rev Time 0.00
Received By rbrown Date 2003-08-20 Time 13:25 Sent To  
Notes
2003-08-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) SHEET A-1.GENERAL NOTES REFER TO
 STANDARD BUILDING CODE SECTION 1604.
 AMEND THE REFERENCE TO FLORIDA BUILDING
 CODE 1604.5.
  
 2) SHEET S-2, STRUCTURAL DESIGN CRITERIA
 NOTE 1 REFERS TO "STANDARD BUILDING
 CODE (2001)".AMEND THE REFERENCE TO
 FLORIDA BUILDING CODE (2001).
  
 3) SHEET S-2.THE DETAIL REFERS TO THE
 ARCHITECTURAL PLANS FOR THE STUCCO BAND
 OVER THE NEW STEEL PLATES.NO STUCCO
 BAND DETAILS HAVE BEEN PROVIDED ON THE
 ARCHITECTURAL PLANS.AMEND/ANNOTATE
 THE PLANS.
  
 4) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING. THE
 ENGINEER'S LICENSE NUMBER SHALL BE ADDED
 TO SHEETS S-1 AND S-2.
  
 5) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 - THE TWO NEW INTERIOR 56"X 30"
 "WINDOW" GLAZED PANELS ADJACENT
 STEVE'S AND STEVE & SUSAN'S DOORS.
 - THE 3' FIXED GLASS PANELS EACH SIDE
 OF THE NEW 6' EXTERIOR DOUBLE DOOR.
 - ANY GLAZING IN THE NEW DOORS
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 6) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOORS WITH SIDELITES, THE NEW
 12' WIDE WINDOW, AND HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS IF APPLICABLE
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-18 Cont ID  
Sent By dpalmer Date 2003-08-18 Time 08:01 Rev Time 0.50
Received By dpalmer Date 2003-08-18 Time 08:01 Sent To  
Notes
2003-08-18 00:00:00NOTED 700.12E

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By nmccray Date 2003-09-24 Time 13:44 Rev Time 0.00
Received By nmccray Date 2003-09-24 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-26 Cont ID  
Sent By rbrown Date 2003-09-19 Time 15:14 Rev Time 0.00
Received By nmccray Date 2003-08-26 Time 14:47 Sent To  
Notes
2003-08-26 00:00:00*************DENIED*********************
 UNDER GENERAL NOTES ALL FINISHES SHALL
 MEET THE REQUIREMENTS OF NFPA 101
 CURRENT EDITION SECTION 27.3.3.1. IT
 SHOULD READ NFPA 101 LIFE SAFETY CODE
 2000 EDITION CHAPTER 39.3.3 INTERIOR
 FINISH.
  
 SEPARATE PLANS AND PERMIT APPLICATIONS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-01 Cont ID  
Sent By csiegber Date 2003-10-01 Time 10:31 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 10:31 Sent To B
Notes
2003-10-01 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 11:22 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 11:21 Sent To B
Notes
2003-09-19 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 13:32 Rev Time 0.00
Received By alange Date 2003-08-07 Time 13:32 Sent To  
Notes
2003-08-07 00:00:00TO COMM BD. #10