| Plan Review Stops For Permit 03080291 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-10-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-21 |
Time |
11:53 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2003-10-21 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2003-10-21 00:00:00 | OK PER HHP 10-21-03 LS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-08-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-08-21 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-08-21 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2003-08-21 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. | | | | | | THE PROPOSED RAMPS AT THE REAR EXIT | | | SHOWN ON SHEET A2.1 MUST MEET HC | | | ACCESSIBILTY.SEE FBC 11-4.8. | | | | | | SHEET A3 SHOWS A DROPPED CEILING / | | | SOFFIT DETAIL.SPECIFIC CONNECTION | | | DETAILS FOR THE FRAMING TO THE EXISTING | | | STRUCTURE WILL BE REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-07 |
Time |
09:27 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-10-07 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2003-10-07 00:00:00 | REDLINED 2002 NEC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-25 |
Time |
11:20 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2003-08-25 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2003-08-25 00:00:00 | PASSED FOR ELECTRICAL SHEETS ONLY. | | | SEE ARCH'S COVER SHEET, NOTES OLD CODES | | | NO LONGER IN AFFECT. PLEASE NOTE, 2002 | | | NEC. THERE WAS NO 1997 NEC. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2003-10-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-21 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-09-30 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-09-30 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-08-21 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-08-21 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2003-08-21 00:00:00 | 1) FIRE ALARM NOTES # 17 AND # 19 ARE | | | INCORRECT. DUCT SMOKE DETECTORS ARE | | | REQUIRED TO ACTIVATE THE FIRE ALARM | | | SYSTEM AND THE CIRCUITS AND DEVICES | | | SHALL BE CLASS A, STYLE D. SEPARATE | | | PLANS AND PERMITS REQUIRED FOR FIRE | | | ALARM EQUIPMENT REMODEL. | | | | | | 2) PLEASE INDICATE HOW THE ELECTRIC | | | STRIKE MECHANISMS EFFECT EXITING. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER REMODEL. | | | | | | 4) DOORS 105B AND 106B OPEN INTO THE | | | CORRIDOR AND REDUCES IT DOWN TO MORE | | | THAN 50 PERCENT. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-22 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-22 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2003-09-22 00:00:00 | TO COMM BD #21/9/24/03 DEE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-08-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-07 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-08-07 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2003-08-07 00:00:00 | TO COMM BD # | | | TO COMM BD #33 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-02 |
Time |
06:43 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-10-02 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2003-10-02 00:00:00 | PLAN CHECK APPROVED BY HAROLD MOSER | | | (9-9-03).PLAN SHEETS M-2 & M-3 | | | CHANGED/APPROVED BY PATTY KRAUSS 10-1-03 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-09-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-09-09 |
Time |
14:03 |
Rev Time |
1.00 |
| Received By |
hmoser |
Date |
2003-09-09 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-10-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-18 |
Time |
13:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-18 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-09-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-13 |
Time |
11:15 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-09-13 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2003-09-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMIN. CODE | | | | | | 1) SHT A2.1 PER TABLE 403.1 A DRINKING | | | FOUNTAIN IS REQUIRED. (ALSO SEE SECTION | | | 410.1) | | | 2) SHT P-1 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED PER SECT- | | | ION 607.3.2 | | | 3) SHT P-2 PLUMBING FIXTURE SCHEDULE, | | | ITEMS P-10, P-11, P-12, P-13, & P-17 NOT | | | FOUND ON FLOOR PLAN. PLEASE CLAIRFY. | | | SECTION 104.2.1 | | | 4) SHT P-2 FLOOR DRAINS NOT APPROVED FOR | | | INDIRECT WASTE. FLOOR SINKS ARE REQUIRED | | | PER SECTION 802.3 | | | 5) SHT P-3 AN RPZ BACKFLOW IS REQUIRED | | | ON WATER SERVICE FOR THIS SPACE. UTILITY | | | ORD. & SECTION 608.13.2 | | | 6) SHT P-3 FILTER FOR REFERIGERATOR ICE | | | MAKER SHALL BE NSF APPROVED. PLEASE SUB- | | | MIT MANUFACTURE SPECIFICATIONS. SECTION | | | 611.1. (SEE ATTACHED SHEET) | | | 7) SHT P-4 ITEM #10 BOOSTER PUMP, MANUF. | | | SPEC. SHEETS REQUIRED. PUMP SHALL BE | | | LISTED. SECTION 303.4 | | | 8) SHT P-4 ITEM #8 BACKFLOWS, MAXIMUM | | | HEIGHT 4' ABOVE THE FLOOR FOR SERVICING | | | AND CERTIFYING. | | | 9) SHT P-5 DOMESTIC WATER ISOMETRIC. THE | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE | | | NOT AT THE TOP OF THE DROPS IN THE CEIL- | | | ING AS SHOWN. MANUF. INSTALLATION INSTR- | | | UCTIONS AND PDI-WH 201. | | | 10) ALL DEVICES, APPURTENANCES. APPLIAN- | | | CES AND APPARATUS INTENDED TO SERVE SOME | | | SPACIAL FUNCTION, SUCH AS STERILIZATION, | | | DISTILLATION, PROCESSING, COOLING, OR | | | STORAGE OF ICE OR FOODS, AND THAT CONN- | | | ECT TO EIGHER THE WATER SUPPLY OR DRAIN- | | | AGE SYSTEM, SHALL BE PROVIDED WITH PRO- | | | TECTION AGAINST BACKFLOW, FLOODING, | | | FOWLING, CONTAMINATION OF THE WATER SUP- | | | PLY SYSTEM AND STOPPAGE OF THE DRAIN. | | | SECTION 422.3 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-21 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|