Plan Review Details - Permit 03080291
Plan Review Stops For Permit 03080291
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-21 Cont ID  
Sent By lsmith Date 2003-10-21 Time 11:53 Rev Time 1.00
Received By lsmith Date 2003-10-21 Time 11:53 Sent To  
Notes
2003-10-21 00:00:00OK PER HHP 10-21-03 LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By hpiskura Date 2003-08-21 Time 08:05 Rev Time 0.00
Received By hpiskura Date 2003-08-21 Time 08:05 Sent To  
Notes
2003-08-21 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 THE PROPOSED RAMPS AT THE REAR EXIT
 SHOWN ON SHEET A2.1 MUST MEET HC
 ACCESSIBILTY.SEE FBC 11-4.8.
  
 SHEET A3 SHOWS A DROPPED CEILING /
 SOFFIT DETAIL.SPECIFIC CONNECTION
 DETAILS FOR THE FRAMING TO THE EXISTING
 STRUCTURE WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-07 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 09:27 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 09:13 Sent To  
Notes
2003-10-07 00:00:00REDLINED 2002 NEC

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-25 Cont ID  
Sent By dpalmer Date 2003-08-25 Time 11:20 Rev Time 1.50
Received By dpalmer Date 2003-08-25 Time 11:20 Sent To  
Notes
2003-08-25 00:00:00PASSED FOR ELECTRICAL SHEETS ONLY.
 SEE ARCH'S COVER SHEET, NOTES OLD CODES
 NO LONGER IN AFFECT. PLEASE NOTE, 2002
 NEC. THERE WAS NO 1997 NEC.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By lsmith Date 2003-10-21 Time 11:48 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By nmccray Date 2003-09-30 Time 15:31 Rev Time 0.00
Received By nmccray Date 2003-09-30 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By mcarsill Date 2003-08-21 Time 17:26 Rev Time 0.00
Received By mcarsill Date 2003-08-21 Time 17:25 Sent To  
Notes
2003-08-21 00:00:001) FIRE ALARM NOTES # 17 AND # 19 ARE
 INCORRECT. DUCT SMOKE DETECTORS ARE
 REQUIRED TO ACTIVATE THE FIRE ALARM
 SYSTEM AND THE CIRCUITS AND DEVICES
 SHALL BE CLASS A, STYLE D. SEPARATE
 PLANS AND PERMITS REQUIRED FOR FIRE
 ALARM EQUIPMENT REMODEL.
  
 2) PLEASE INDICATE HOW THE ELECTRIC
 STRIKE MECHANISMS EFFECT EXITING.
  
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 4) DOORS 105B AND 106B OPEN INTO THE
 CORRIDOR AND REDUCES IT DOWN TO MORE
 THAN 50 PERCENT.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-22 Time 13:59 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 13:59 Sent To  
Notes
2003-09-22 00:00:00TO COMM BD #21/9/24/03 DEE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 08:08 Rev Time 0.00
Received By alange Date 2003-08-07 Time 08:05 Sent To  
Notes
2003-08-07 00:00:00TO COMM BD #
 TO COMM BD #33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-02 Cont ID  
Sent By pkrauss Date 2003-10-02 Time 06:43 Rev Time 0.40
Received By pkrauss Date 2003-10-02 Time 06:43 Sent To  
Notes
2003-10-02 00:00:00PLAN CHECK APPROVED BY HAROLD MOSER
 (9-9-03).PLAN SHEETS M-2 & M-3
 CHANGED/APPROVED BY PATTY KRAUSS 10-1-03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-09 Cont ID  
Sent By hmoser Date 2003-09-09 Time 14:03 Rev Time 1.00
Received By hmoser Date 2003-09-09 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-18 Cont ID  
Sent By kstevens Date 2003-10-18 Time 13:59 Rev Time 0.50
Received By kstevens Date 2003-10-18 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-13 Cont ID  
Sent By kstevens Date 2003-09-13 Time 11:15 Rev Time 1.50
Received By kstevens Date 2003-09-13 Time 11:15 Sent To  
Notes
2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT A2.1 PER TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED. (ALSO SEE SECTION
 410.1)
 2) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER SECT-
 ION 607.3.2
 3) SHT P-2 PLUMBING FIXTURE SCHEDULE,
 ITEMS P-10, P-11, P-12, P-13, & P-17 NOT
 FOUND ON FLOOR PLAN. PLEASE CLAIRFY.
 SECTION 104.2.1
 4) SHT P-2 FLOOR DRAINS NOT APPROVED FOR
 INDIRECT WASTE. FLOOR SINKS ARE REQUIRED
 PER SECTION 802.3
 5) SHT P-3 AN RPZ BACKFLOW IS REQUIRED
 ON WATER SERVICE FOR THIS SPACE. UTILITY
 ORD. & SECTION 608.13.2
 6) SHT P-3 FILTER FOR REFERIGERATOR ICE
 MAKER SHALL BE NSF APPROVED. PLEASE SUB-
 MIT MANUFACTURE SPECIFICATIONS. SECTION
 611.1. (SEE ATTACHED SHEET)
 7) SHT P-4 ITEM #10 BOOSTER PUMP, MANUF.
 SPEC. SHEETS REQUIRED. PUMP SHALL BE
 LISTED. SECTION 303.4
 8) SHT P-4 ITEM #8 BACKFLOWS, MAXIMUM
 HEIGHT 4' ABOVE THE FLOOR FOR SERVICING
 AND CERTIFYING.
 9) SHT P-5 DOMESTIC WATER ISOMETRIC. THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF THE DROPS IN THE CEIL-
 ING AS SHOWN. MANUF. INSTALLATION INSTR-
 UCTIONS AND PDI-WH 201.
 10) ALL DEVICES, APPURTENANCES. APPLIAN-
 CES AND APPARATUS INTENDED TO SERVE SOME
 SPACIAL FUNCTION, SUCH AS STERILIZATION,
 DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONN-
 ECT TO EIGHER THE WATER SUPPLY OR DRAIN-
 AGE SYSTEM, SHALL BE PROVIDED WITH PRO-
 TECTION AGAINST BACKFLOW, FLOODING,
 FOWLING, CONTAMINATION OF THE WATER SUP-
 PLY SYSTEM AND STOPPAGE OF THE DRAIN.
 SECTION 422.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By lsmith Date 2003-10-21 Time 11:48 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***