Plan Review Details - Permit 03080273
Plan Review Stops For Permit 03080273
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-05-03 Cont ID  
Sent By shill Date 2006-05-03 Time 14:37 Rev Time 0.00
Received By shill Date 2006-05-03 Time 14:37 Sent To  
Notes
2006-05-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.
 WWW.FLORIDABUILDING.ORG.SUBMIT A LOCAL
 PRODUCT APPROVAL APPLICATION WITH ALL
 REQUIRED DOCUMENTATION.
  
 2.)PROVIDE THE FORM BOARD SURVEYS TO
 THE INSPECTOR AT TIME OF INSPECTION.
 THEY TYPICALLY DO NOT GO THROUGH PLAN
 REVIEW FOR RESIDENTIAL PROJECTS.
  
 3.)THIS PERMIT HAS BEEN CLOSED DUE TO
 INACTIVITY FBC2004*105.4, FBC2001*104.5.
 SUBMIT NEW PLANS AND PERMIT APPLICATION.
 THERE IS A NEW GOVERNING CODE FBC2004
 EFFECTIVE OCTOBER 1, 2005.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-06-23 Cont ID  
Sent By shill Date 2005-06-23 Time 07:52 Rev Time 0.00
Received By shill Date 2005-06-23 Time 07:52 Sent To  
Notes
2005-06-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ZONING APPROVAL REQUIRED.
  
 2.)PLEASE SUBMIT TWO COPIES OF THE
 MULLION PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 11:31 Rev Time 0.50
Received By shill Date 2005-06-09 Time 11:31 Sent To PC
Notes
2005-06-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE SUBMIT REVISED A1 PREPARED
 BY MR. LIMA (ARCHITECT) SHOWING THE
 PROPOSED CHANGE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-12-17 Cont ID  
Sent By shill Date 2003-12-17 Time 14:03 Rev Time 1.00
Received By shill Date 2003-12-17 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-16 Cont ID  
Sent By shill Date 2003-12-16 Time 13:56 Rev Time 1.50
Received By shill Date 2003-12-16 Time 13:56 Sent To  
Notes
2003-12-16 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.PLEASE
 HAVE THE PERSON WHO PREPARED THE ENERGY
 CALC CALL ME AS I DO NOT UNDERSTAND
 WHY THE SQUARE FOOTAGE IS THAT OF THE
 PORCH RATHER THAN THE ADDITION (UNDER
 ATTIC, ITEM #10).
  
 2.)ADDITIONAL FEES DUE (RADON), $4.50,
 BZ231393.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)HAVE THE ARCHITECT READ THE SOILS
 REPORT.A STEM WALL IS RECOMMENDED DUE
 TO SOIL CONDITIONS, A MONOLITHIC SLAB
 IS SHOWN ON THE PLAN.
  
 5.)THE ORIGINAL APPLICATION AND
 OWNER/BUILDER AFFIDAVIT IS MISSING FROM
 THE PACKAGE.
  
 6.)WHEN RESUBMITTING, ASSEMBLE TWO
 COMPLETE, MOST CURRENT SETS OF PLANS.
 OLD SHEETS ARE TO BE MARKED AND
 SUBMITTED SEPARATELY.
  
 7.)HAVE THE FINAL SET OF DRAWINGS
 STAMPED BY THE HISTORIC PRESERVATION
 DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-21 Cont ID  
Sent By sthyng Date 2003-10-21 Time 11:13 Rev Time 2.00
Received By sthyng Date 2003-10-21 Time 11:13 Sent To  
Notes
2003-10-21 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ENERGY CALCS INCORRECT; SHOWS AN
 UNDER ATTIC SPACE OF 186 SQUARE FEET.
 PLEASE SEE THE PLAN AND REVISE THE
 ENERGY CALCS TO MATCH.
  
 2.)ADDITIONAL FEES DUE (RADON), $4.50,
 BZ231393.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)SEE PREVIOUS LIST, ITEM #12. STAIRS
 SHALL HAVE FLOOR OR LANDINGS AT DOOR
 OPENINGS, FBC1007.4.2.
  
 5.)PREVIOUS LIST ITEM #13 WAS
 ADDRESSED ON THE FOUNDATION PLAN BUT
 THE TREAD IS SHOWN AS 10" (RATHER THAN
 16") ON SHEETS AS1 AND A1.REVISE SO
 THAT ALL DETAILS ARE CONSISTENT AND
 COMPLY WITH FBC1007.3.
  
 6.)SEE PREVIOUS LIST ITEM #14.A NOTE
 WAS MADE ON THE PLAN IN REGARDS TO
 IMPACT PROTECTION BUT THE PRODUCT
 APPROVALS FOR IMPACT PROTECTION FOR THE
 GLAZED DOOR (AND ANY WINDOWS NOT IMPACT
 RESISTANT) WERE NOT SUBMITTED.SUBMIT
 TWO COPIES AND THE ATTACHED SHEDULE,
 OR A SEPARATE PERMIT FOR IMPACT
 PROTECTION WILL BE REQUIRED.
  
 7.)SEE PREVIOUS LIST, ITEM #17, NOT
 ADDRESSED.A SOILS INVESTIGATION
 REPORT IS REQUIRED.
  
 8.)SEE ATTACHED IN REGARDS TO
 FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-10-16 Time 09:19 Rev Time 2.00
Received By sthyng Date 2003-08-18 Time 17:41 Sent To  
Notes
2003-08-18 00:00:00*****CORRECTIONS*****
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)ADDITIONAL FEES DUE (RADON), $4.50.
  
 3.)THE SITE PLAN (AS1) SHOWS 450
 SF OF ADDITION; AREA CALCULATIONS SHOW
 256 (A1).REVISE; SHOW EXISTING,
 PROPOSED, NEW TOTAL.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY BEFORE A PERMIT CAN BE
 ISSUED.THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 6.)ENERGY CALCS REQUIRED FBC13-101.5.5
  
 7.)PROVIDE THE ARCHITECT FIRM LICENSE
 NUMBER ON THE TITLE BLOCK, FAC61G1-
 16.004(2).
  
 8.)FOR ALL ATTACHMENTS, SPECIFY THE
 ATTACHMENT WITH UPLIFT.
  
 9.)FIRESTOP REQUIRED IN ALL WALLS
 AND PARTITION WALLS, FBC705.3.
  
 10.) CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC1804.1.7, LOWEST FLOOR
 ELEVATION SHALL BE A MINIMUM OF 4"
 ABOVE FINISH GRADE AT THE BUILDING
 PERIMETER.
  
 11.) BOTTOM OF FOOTER TO BE MINIMUM OF
 12" BELOW FINISH GRADE, FBC1804.1.3.
  
 12.) STAIRS SHALL HAVE FLOORS OR
 LANDINGS AT DOOR OPENINGS, FBC1007.4.2.
  
 13.) THE SUM OF TWO RISERS AND A TREAD
 IS REQUIRED TO BE NOT LESS THAN 24",
 FBC1007.3.
  
 14.)IMPACT PROTECTION REQUIRED FOR
 GLAZING (GLAZED DOOR), FBC1606.1.4.
 PROVIDE TWO COPIES OF PRODUCT APPROVALS
 FOR SHUTTERS.
  
 15.) PROVIDE TWO COPIES OF MULLION
 PRODUCT APPROVALS.
  
 16.) PROVIDE WIND DESIGN INFORMATION,
 FBC1606.1.7.
  
 17.) PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 13:46 Rev Time 0.25
Received By dpalmer Date 2005-03-28 Time 13:46 Sent To  
Notes
2005-03-28 00:00:00REVISED KITCHEN LAYOUT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-12 Cont ID  
Sent By btrobaug Date 2004-03-12 Time 15:12 Rev Time 0.50
Received By btrobaug Date 2004-03-12 Time 15:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-14 Cont ID  
Sent By btrobaug Date 2003-10-14 Time 13:46 Rev Time 0.50
Received By btrobaug Date 2003-10-14 Time 13:08 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-18 Cont ID  
Sent By csiegber Date 2003-10-03 Time 14:22 Rev Time 1.00
Received By btrobaug Date 2003-08-12 Time 14:36 Sent To P
Notes
2003-08-12 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PROVIDE A SCHEDULE FOR "MB" PANEL.
  
 3} PANEL "E" HAS AN OCP AND FEED FOR
 PANEL"C",THE RISER SHOWS IT BEING FED
 FROM "MB",PLEASE CORRELATE.
  
 4} PANEL "A" DOES NOT SHOW 2 SMALL
 APPLIANCE CIRCUITS TO COMPLY WITH
 210.52(B)(3),AND 220.16(A).
  
 5} THE LOCATION OF PANEL "E" DOES NOT
 APPEAR TO COMPLY WITH 110.26.THE A/C
 COMPRESSER WOULD BE IN THE WAY.
  
 6} IF THE EXISTING "GUEST HOUSE" IS
 DETACHED,PANEL "B" MUST COMPLY WITH
 225.31 & 250.32.PLEASE SHOW SAME ON
 RISER.
  
 NOTE: OUR CURRENTLY ADOPTED EDITION OF
 THE NEC IS 2002.(SEE NOTE #2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 10:38 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 10:38 Sent To B
Notes
2006-04-26 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-22 Cont ID  
Sent By adarroug Date 2005-06-22 Time 11:11 Rev Time 0.00
Received By adarroug Date 2005-06-22 Time 11:11 Sent To B
Notes
2005-06-22 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 14:50 Rev Time 0.00
Received By shill Date 2005-06-14 Time 14:50 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 14:24 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 14:23 Sent To B
Notes
2005-06-07 00:00:00TO 'SH' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 14:22 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 14:22 Sent To E
Notes
2003-10-03 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 14:05 Rev Time 0.00
Received By alange Date 2003-08-08 Time 14:05 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-06 Cont ID  
Sent By mmclean Date 2003-08-07 Time 16:45 Rev Time 0.00
Received By alange Date 2003-08-06 Time 15:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-16 Cont ID  
Sent By pkrauss Date 2003-10-16 Time 09:17 Rev Time 0.20
Received By pkrauss Date 2003-10-16 Time 09:17 Sent To B
Notes
2003-10-16 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.ENERGY & MANUAL J ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-19 Cont ID  
Sent By btrobaug Date 2003-10-14 Time 13:46 Rev Time 0.25
Received By pkrauss Date 2003-08-15 Time 12:57 Sent To B
Notes
2003-08-15 00:00:00NO MECHANICAL PLANS OR INFORMATION
 SUBMITTED FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-13 Cont ID  
Sent By btrobaug Date 2003-08-18 Time 18:14 Rev Time 0.50
Received By kstevens Date 2003-08-13 Time 13:09 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-21 Cont ID  
Sent By mmclean Date 2005-06-21 Time 17:49 Rev Time 0.00
Received By mmclean Date 2005-06-21 Time 17:49 Sent To I
Notes
2005-06-21 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF SURVEY
 SHOWING THE LOCATION OF THE SCREEN
 ENCLOSURE WTIH SETBACK FROM SIDE & REAR
 OF PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-06 Time 15:20 Rev Time 0.00
Received By mmclean Date 2003-08-06 Time 17:50 Sent To I
Notes
***NONE***