Plan Review Details - Permit 03080138
| Plan Review Stops For Permit 03080138 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-08-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-08-19 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-08-19 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2003-08-19 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. | | | | | | SAME COMMENTS AS OTHER PHASES, A COPY | | | IS ATTACHED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-08-25 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-05 |
Time |
13:51 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-08-25 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2003-08-25 00:00:00 | PLEASE SEE COMMENTS UNDER ALL OTHER | | | PHASES FOR WORK. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-08-21 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-08-21 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2003-08-21 00:00:00 | PLEASE SEE PLAN REVIEW COMMENTS FOR | | | PHASE I, PERMIT # 03080048. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-08-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-05 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
dbaxter |
Date |
2003-08-05 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2003-08-05 00:00:00 | TO COMM BD.#45 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-08-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-08-21 |
Time |
07:59 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-08-21 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2003-08-21 00:00:00 | PLAN CHECK - PLANS DATED 7/28/03 | | | | | | PLEASE PROVIDE A NARRATIVE AS TO THE | | | EXISTING SMOKE CONTROL OR SMOKE EVAC | | | SYSTEM AND HOW THE NEW SYSTEM WILL BE | | | INCORPORATED INTO THE EXISTING SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-08 |
Time |
11:59 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-09-08 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2003-09-08 00:00:00 | DENIED | | | | | | SEE COMMENTS FORM REVIEW ON PERMIT NUMB- | | | ER 03080048.- 11-4.1.6(2) SHOW 20% | | | REQUIRED TO BE SPENT ON ACCESSIBLILITY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|