Plan Review Details - Permit 03080097
Plan Review Stops For Permit 03080097
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-02 Cont ID  
Sent By sthyng Date 2003-10-02 Time 07:32 Rev Time 1.00
Received By sthyng Date 2003-10-02 Time 07:32 Sent To  
Notes
2003-10-02 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PERMIT WAS ISSUED WITH A
 PROVISO TO SUBMIT A DETAIL FOR THE
 RAILING AND GUARDRAIL TO COMPLY WITH
 FBC1608.2, 1007.5, 1015.3.REVISE
 PLAN.
  
 2.)SPECIFY ATTACHMENTS (SECTION B,
 SIMPSON JOIST HANGER, SECTION A, TS).
 SIMPSON HDSA IS NOT IN THE 2003 CATALOG,
 SPECIFY ATTACHMENT (SECTION B).
  
 3.)IMPACT PROTECTION REQUIRED, FBC
 1606.1.4.
  
 4.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FRENCH DOORS, NEW
 WINDOW, AND IMPACT PROTECTION.
  
 5.)ENERGY CALCS REQUIRED, FBC13-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 7.)AREA CALCULATIONS REQUIRED ON THE
 PLAN; EXISTING AND PROPOSED, NEW TOTAL.
  
 8.)TO EXPEDITE PLAN REVIEW, CLOUD OR
 OTHERWISE INDICATE ALL CHANGES.FOR
 EXAMPLE, THE NEW WINDOW AND THE STEEL
 IN SECTION B ARE NOT MARKED BUT ARE
 CHANGES FROM THE PERMITTED SET.
  
 10.)AS DISCUSSED WITH THE OWNER,
 REVISE THE PLAN TO REFLECT THE ACTUAL
 REPAIR TO THE CONCRETE POSTS.PER OUR
 CONVERSATION, THE STEEL WAS REPLACED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 11:04 Rev Time 1.50
Received By sthyng Date 2003-08-22 Time 11:52 Sent To  
Notes
2003-08-22 00:00:00******PROVISO******
 1.)SUBMIT STEEL DETAIL AS A REVISION.
 2.)RAILING AND GUARDRAIL TO COMPLY WITH
 FBC1007.5.1, 1007.5.3,1608.2,1015.3.
 SUBMIT A REVISED STAIR DETAIL BEFORE
 CONSTRUCTION.
 3.)CALL FOR PREINSPECT, 805-6651

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 11:04 Rev Time 0.50
Received By dpalmer Date 2003-09-29 Time 11:04 Sent To B
Notes
2003-09-29 00:00:00************ UNSAT ******************
  
 1NOTE: PLEASE SUBMIT PLANS UNDER PERMIT
 # IN WHICH ELECTRICAL REVIEW AND PERMIT
 WAS ISSUED.
 NO REVIEW WAS DONE UNDER THIS # FOR
 PERMIT.
  
 2)NOTE: PLEASE NOTE, BEFORE SUBMITTING
 SAME ELECTRICAL SHEETS, PLEASE SEE THE
 2002 NEC AND THE 1999 NFPA-72 8-1
 FOR MANY ITEMS MISSING ON PLANS AND
 INCOMPLETE PLANS ALSO.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 UNDER ELEC #. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-08-22 Cont ID  
Sent By kstevens Date 2003-09-26 Time 09:45 Rev Time 0.00
Received By sthyng Date 2003-08-22 Time 11:51 Sent To  
Notes
2003-08-22 00:00:00REMOVED ELECTRIC PLAN FROM PACKAGE;
 OWNER TO APPLY FOR ELECTRIC PERMIT
 SEPARATELY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By mmclean Date 2003-08-19 Time 16:57 Rev Time 0.50
Received By btrobaug Date 2003-08-21 Time 13:08 Sent To B
Notes
2003-08-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE COMPLIANCE WITH 250-50 FOR
 THE GEC SYSTEM AND SIZE OF CONDUCTOR.
  
 3} THE ELECTRICAL FLOOR PLANS DO NOT
 MATCH THE ARCHITECTURAL FLOOR
 PLAN,PLEASE CORRELATE.
  
 5} PROVIDE A LOAD CALCULATION AND PANEL
 SCHEDULE PER 215.5 NEC.INDICATE REQUIRED
 CIRCUITS ON SAME.
  
 6} PLEASE SEE THE 2002 NEC FOR
 ELECTRICAL REQUIREMENTS AND
 NFPA-72,1999,FOR SMOKE DETECTION
 DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-19 Cont ID  
Sent By sthyng Date 2003-09-19 Time 12:14 Rev Time 0.00
Received By sthyng Date 2003-09-19 Time 12:14 Sent To Z
Notes
2003-09-19 00:00:00SENT TO ZONING 9/16, APPARENTLY NOT
 REVIEWED, SENT BACK TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-16 Cont ID  
Sent By sthyng Date 2003-09-16 Time 16:21 Rev Time 0.00
Received By sthyng Date 2003-09-16 Time 16:21 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-09 Time 10:14 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 10:14 Sent To B
Notes
2003-09-09 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 15:26 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 15:26 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:11 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:11 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-26 Cont ID  
Sent By kstevens Date 2003-09-26 Time 09:36 Rev Time 0.50
Received By kstevens Date 2003-09-26 Time 09:36 Sent To E
Notes
2003-09-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
  
 1) SEPARATE PLUMBING PERMIT REQUIRED
 2) SHT A-1 WASH MACHINE REQUIRES A TRAP,
 AND STANDPIPE. SECTIONS 1002.1 & 802.4
 3) CLEANOUT REQUIRED ON W/M STACK 4 FEET
 ABOVE THE FLOOR. 708.10.
 4) THE PERSONAL SEAL, SIGNATURE, AND
 DATE SHALL APPEAR ON SHEETS. NO DATE
 WHERE SIGNED AND SEALED. 61G1-16.003
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2003-09-19 Cont ID  
Sent By mmclean Date 2003-09-19 Time 12:20 Rev Time 0.00
Received By mmclean Date   Time   Sent To P
Notes
2003-09-19 00:00:009/19/03 OK PER SHIRLEY GRAHAM ASSOC
 PLANNER MM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-08-19 Cont ID  
Sent By sthyng Date 2003-09-19 Time 12:14 Rev Time 0.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-04 Time 16:11 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-08-06 00:00:008/6/03 DENIED, NEED SITE PLAN TO SHOW
 LOCATION OF STAIRS IN REAR/CANNOT PULL
 PERMIT AS OWNER BUILDER MM


Account Summary | Usage Policy | Privacy Policy