Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-18 Cont ID  
Sent By hpiskura Date 2003-08-18 Time 15:54 Rev Time 0.00
Received By hpiskura Date 2003-08-18 Time 15:54 Sent To  
Notes
2003-08-18 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 THE COMMENTS ARE THE SAME AS THAT FOR
 PHASE I A COPY IS ATTACHED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 07:29 Rev Time 0.50
Received By dpalmer Date 2003-08-20 Time 07:29 Sent To  
Notes
2003-08-20 00:00:00************* UNSAT *****************
  
 1)NOTE: PLANS DO NOT SHOW ANY ELECTRICAL
 FOR AREAS BEING EXTENDED.?
  
 2)NOTE: PLEASE SEE 210.60 FOR NEW ELEC-
 -TRICAL BEING ADDED TO THESE AREAS.
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G15-23.002 FOR ENGINEERS AND FAC
 61G1-16.004 FOR ARCH'S. PLEASE SEE MISS-
 -ING INFORMATION REQ'D ON TITLE BLOCKS
 AS REQ'D UNDER FS 471 & 481
  
 PLEASE NOTE; PLANS HAVE ONLY COME IN
 FOR PLAN REVIEW AND NOT FOR PERMIT.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 07:33 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 07:33 Sent To  
Notes
2003-10-03 00:00:001) OPEN DOOR ON PAGE MFP 252, SUITE
 TYPE 1, FIRE SPRINKLER HEAD APPEARS
 BLOCKED WHEN DOOR IS OPEN.
  
 2) EIFS STILL SHOWN ON ENLARGED
 ELEVATION PAGES. PLEASE SEE APPENDIX
 F, LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By mcarsill Date 2003-08-21 Time 16:29 Rev Time 0.00
Received By mcarsill Date 2003-08-21 Time 16:29 Sent To  
Notes
2003-08-21 00:00:00THESE COMMENTS ARE ALSO FOR PHASE 2,3,
 AND 4 FOR THE PROJECT.
  
 1) TEMPORARY WALLS AND DUST PROTECTION
 SHALL BE CONSTRUCTED OF NON-COMBUSTIBLE
 MATERIALS. NON FIRE RETARDANT VISQUEEN
 SHALL NOT BE PERMITTED.
  
 2) TEMPORARY EGRESS AND EXIT CORRIDORS
 SHALL MEET ALL APPLICABLE CODES.
  
 3) ALL RENOVATIONS SHALL COMPLY WITH
 NFPA 241.
  
 4) ALL TEMPORARY CONSTRUCTION
 MATERIALS SHALL NOT INTERFERE WITH
 ANY EXISTING FIRE PROTECTION FEATURES.
  
 5) PLEASE INDICATE IN WRITING HOW THE
 HOTEL WILL REMAIN OPEN DURING
 CONSTRUCTION. ALSO PLEASE INDICATE
 IN WRITING WHAT SAFEGAURDS WILL BE
 TAKEN TO SEPARATE CONSTRUCTION FROM
 NON-CONSTRUCTION AREAS. ALSO HOW WILL
 EXITS, EXIT ACCESS AND EXIT DISCHARGE
 BE MAINTAINED DURING RENOVATION
 PERIODS.
  
 6) DOOR SCHEDULE NOTES INDICATE
 UNDERCUTTING OF GUESTROOM ENTRY DOORS
 WHICH ARE 20 MINUTE FIRE RATED. PLEASE
 EXPLAIN NOTE RATIONALE.
  
 7) COMBUSTIBLE DEBRIS IS TO BE REMOVED
 DAILY DURING DEMOLITION ACTIVITIES.
  
 8) A NEW FIRE ALARM SYSTEM WAS
 RECENTLY INSTALLED WITHIN THE HOTEL
 EXCEPT FOR THE FIRST FLOOR. THE FIRE
 ALARM SYSTEM IS TO BE UPGRADED ON THE
 ENTIRE FIRST FLOOR.
  
 9) THE RAMP ON SERVICE CORRIDOR # 4
 SHALL BE EQUIPPED WITH HANDRAILS ON
 BOTH SIDES.
  
 10) FABRIC CANOPIES SHALL BE FIRE RATED
 SINCE THE HOTEL IS LOCATED IN THE
 CITY FIRE LIMITS.
  
 11) ALL ARCHITECTURAL TRIM SHALL BE
 NON-COMBUSTIBLE AS REQUIRED IN
 APPENDIX F, LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE.
  
 12) BUILDING ADDRESS REQUIRED.
  
 13) THE FURNITURE PLAN APPEARS THAT
 SEATING WITHIN THE RESTAURANT 001,
 AND LOUNGE 041 APPEAR TO BE TOO
 CLOSE TOGETHER.
  
 14) ALL NEW STAIRS AND RAMPS SHALL
 BE EQUIPPED WITH HANDRAILS.
  
 15) SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE NEW HOOD PLANNED
 FOR KITCHEN 002.
  
 16) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER REMODEL.
  
 17) ANY FIRE WALLS DISCOVERED TO HAVE
 DAMAGE ARE TO BE REPAIRED.
  
 18) ALL WOOD IS REQUIRED TO BE FRT.
 EXTERIOR GRADE PLYWOOD IS NOT
 ACCEPTABLE SINCE THE BUILDING IS LOCATED
 IN THE FIRE LIMITS.
  
 19) ALL AREAS USED FOR EXITING SHALL
 BE A MINIMUM OF AT LEAST SEVEN FEET
 HIGH.
  
 20) ENSURE THAT ALL EXISTING SMOKE
 DETECTORS IN EACH GUEST ROOM IS IN
 WORKING ORDER.
  
 21) PLEASE INDICATE IN WRITING HOW THE
 NEW FIRE SPRINKLER SYSTEM HEADS WILL
 BE INSTALLED AND PROTECTION STILL BE
 PROVIDED WITHIN THE HOTEL.
  
 22) PLEASE NOTE ON THE PLANS THE
 SIZES OF THE BATRHROOMS AND CLOSETS
 THAT WILL NOT BE RECEIVING FIRE
 SPRINKLER PROTECTION.
  
 23) PLEASE NOTE ON THE PLANS THE
 LOCATIONS OF ALL EXISTING SYSTEM
 SMOKE AND NON SYSTEM SMOKE DETETECTORS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 08:10 Rev Time 0.00
Received By alange Date 2003-08-04 Time 08:10 Sent To  
Notes
2003-08-04 00:00:00TO COMM BD #63

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-11 Cont ID  
Sent By pkrauss Date 2003-08-21 Time 09:45 Rev Time 0.40
Received By hmoser Date 2003-08-21 Time 09:45 Sent To  
Notes
2003-08-21 00:00:00PLAN CHECK - PLANS DATED 7/28/03
  
 PLEASE PROVIDE A NARRATIVE AS TO THE
 EXISTING SMOKE CONTROL OR SMOKE EVAC
 SYSTEM AND HOW THE NEW SYSTEM WILL
 INCORPORATED INTO THE EXISTING SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-02 Cont ID  
Sent By kstevens Date 2003-09-02 Time 17:52 Rev Time 2.50
Received By kstevens Date 2003-09-02 Time 17:52 Sent To  
Notes
2003-09-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ACCESSIBLE SLEEPING ROOMS OR SUITES
 THAT COMPLY WITH THE REQUIREMENTS OF
 11-9.2.1 TO 11-9.2.2 (REQUIREMENTS FOR
 ACCESSIBLE UNITS, SLEEPING ROOMS, AND
 SUITES) SHALL BE PROVIDED IN CONFORMANCE
 WITH THE TABLE BELOW. (PAGE 11.43). IN
 ADDITION, IN HOTELS, OF 50 OR MORE
 SLEEPING ROOMS OR SUITES, ADDITIONAL
 ACCESSIBLE SLEEPING ROOMS OR SUITES THAT
 INCLUDE A ROLL-IN SHOWER SHALL ALSO BE
 PROVIDED IN CONFORMANCE WITH THE SAME
 TABLE. SUCH ACCOMMODATIONS SHALL COMPLY
 WITH THE REQUIREMENTS OF 11-9.2, 11-4.21
 AND FIGURE AA-57(A) OR (B). - PLEASE
 INDICATE HOW THIS WILL BE DONE.
 2) IN ALL BUILDINGS, STURCTURES AND FAC-
 ILITIES LICENSED AS A HOTEL, MOTEL OR
 RESORT CONDOMINIUM PURSUANT TO CHAPTER
 509 FLORIDA STATUTES, A NUMBER OF ROOMS
 EQUALING AT LEAST 5 PERCENT OF THE GUEST
 ROOMS MINUS THE NUMBER OF ACCESSIBLE
 ROOMS REQUIRED BY THE TABLE SHALL PROV-
 IDE THE ADDITIONAL SPECIAL ACCESSIBILITY
 FEATURES OF 11-9.2.3 - PROVIDE DETAILS.
 3) SLEEPING ACCOMMODATIONS FOR PERSONS
 WITH HEARING IMPAIRMENTS. SECTION 11-9.1
 .3. IN ADDITION TO THOSE ACCESSIBLE
 SLEEPING ROOMS AND SUITES REQUIRED BY
 11-9.2.1, SLEEPING ROOMS AND SUITES THAT
 COMPLY WITH 11-9.3 (VISUAL ALARMS, NOTI-
 FICATION DEVISCES, AND TELEPHONES) SHALL
 BE PROVIDED IN CONFORMANCE WITH THE TAB-
 LE ON PAGE 11.44
 4) 11-9.1.4 CLASSES OF SLEEPING ACCOMMO-
 DATIONS. (1) IN ORDER TO PROVIDE PERSONS
 WITH DISABILITIES A RANGE OF OPTIONS
 EQUIVALENT TO THOSE AVAILABLE TO OTHER
 PERSONS SERVED BY THE FACILITY, SLEEPING
 ROOMS AND SUITES REQUIRED TO BE ACCESSI-
 BLE BY 11-9.1.2 SHALL BE DISPERSED
 AMONG THE VARIOUS CLASSES OF SLEEPING
 ACCOMMODATIONS AVAILABLE TO PATRONS OF
 THE PLACE OF TRANSIENT LODGING. FACTORS
 TO BE CONSIDERED INCLUDE ROOM SIZE, COST
 AMENITIES PROVIDED AND THE NUMBER OF
 BEDS PROVIDED. - INDICATE HOW THIS WILL
 BE ACCOMPLISHED.
 5) SEE SECTION 11-9.1.4 (2) EQUIVALENT
 FACILITATION.
 6) 11-9.2.3 HOTEL, MOTEL AND CONDOMINI-
 MUM SPECIAL ACCESSIBILITY FEATURE. SHOW
 COMPLIANCE WITH THIS SECTION.
 7) SHOW COMPLIANCE WITH SECTION 11-4.23
 AND ALL SUBSECTIONS
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***