Plan Review Details - Permit 03080042
Plan Review Stops For Permit 03080042
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-18 Cont ID  
Sent By hpiskura Date 2003-08-18 Time 15:06 Rev Time 0.00
Received By hpiskura Date 2003-08-18 Time 15:06 Sent To  
Notes
2003-08-18 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 IF NOTICE OF ACCEPTANCE AND/OR TEST
 REPORTS FOR THE ROOF COVERING, DOORS
 AND WINDOWS ARE NOT INCLUDED AT TIME OF
 PERMIT APPLICATION, WITH AN
 INSTALLATION SCHEDULE, A SEPARATE
 PERMIT AND FEES WILL BE REQUIRED FOR
 THAT WORK.
  
 THE EIFS MUST BE INSTALLED IN ACCORDANCE
 WITH ITS LISTING, FBC 2603.6.
  
 THE EIFS SHOWN AS ARCHITECTURAL TRIM
 MUST COMPLY WITH FBC 1404.1 AND FBC
 F102.2.7 AS AMENDED BY THE CITY OF WEST
 PALM BEACH. A COPY IS ATTACHED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By dpalmer Date 2003-08-20 Time 06:40 Rev Time 2.00
Received By dpalmer Date 2003-08-20 Time 06:16 Sent To  
Notes
2003-08-20 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 EM.EXT LTS PER 700.12E.
  
 2)NOTE: PLEASE SUBMIT FIXTURE SCHEDULES
 CONTAINING WATTAGES/VOLTAGES FOR FIXTURE
 -S.
  
 3)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH SUBMITTED PANEL SCHEDULES/
 MAX LOAD PER CIRCUIT.
 A COMPLETE AND ACCURATE PANEL SCHEDULES
 WILL BE REQ'D BEFORE FINAL ALSO.
  
 4)NOTE: PLEASE INCLUDE LOADS ON PANELS
 215.5
  
  
 5)NOTE: PLEASE SEE ATTACHED COPIES OF
 FAC 61G15-23.002 FOR ENGINEERS AND
 61G1-16.004 FOR ARCH'S. PLEASE SEE ALL
 INFORMATION REQ'D ON TITLE BLOCKS FOR
 PLANS. REQ'D ALSO UNDER FS 471/481
  
 PLEASE NOTE; PLANS HAVE ONLY COME IN FOR
 PLAN REVIEW AND NOT FOR PERMIT.
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By mcarsill Date 2003-08-21 Time 17:20 Rev Time 0.00
Received By mcarsill Date 2003-08-21 Time 17:20 Sent To  
Notes
2003-08-21 00:00:00PLEASE SEE PLAN REVIEW COMMENTS FOR
 PHASE I, PERMIT # 03080048.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 08:06 Rev Time 0.00
Received By alange Date 2003-08-04 Time 08:06 Sent To  
Notes
2003-08-04 00:00:00COMM BD# 62

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By pkrauss Date 2003-08-21 Time 09:32 Rev Time 0.45
Received By pkrauss Date 2003-08-21 Time 09:32 Sent To  
Notes
2003-08-21 00:00:00PLAN CHECK - PLANS DATED 7/28/03
  
 PLEASE PROVIDE A NARRATIVE AS TO THE
 EXISTING SMOKE CONTROL OR SMOKE EVAC
 SYSTEM AND HOW THE NEW SYSTEM WILL BE
 INCORPORATED INTO THE EXISTING SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-02 Cont ID  
Sent By kstevens Date 2003-09-02 Time 15:17 Rev Time 1.50
Received By kstevens Date 2003-09-02 Time 15:17 Sent To  
Notes
2003-09-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHTS MP060 & MP061 ALL TERMINATED OR
 CAPPED PLUMBING LINES TO BE INSPECTED
 PRIOR TO COVERING.
 2) SHT MP060 CLAIRFICATION REQUIRED FOR
 G.W. LINE CAP OFF. (PASSES THROUGH KEY
 CAFE RESTURANT.
 3) SHT MP201 DETAIL 1/MP202 ON SHEET
 MP201? PLEASE CLAIRFY.
 4) SHT MP-201 DETAIL 3/MP201 FOR SECOND
 FLOOR. 2ND FLOOR NOT IN PHASE 2 AS IN-
 DICATED ON APPLICATION. NO 2ND FLOOR
 FLOOR PLANS SHOWN.
 5) SHT MP201 DETAIL 4/201 NOT FOUND ON
 FLOOR PLAN. PLEASE CLAIRFY.
 6) SANITARY RISER DIAGRAMS AND WATER
 RISER DIAGRAMS REQUIRED PER SECTION
 104.2.1
 7) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK FOR EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***