Plan Review Details - Permit 03080040
Plan Review Stops For Permit 03080040
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-06-01 Cont ID  
Sent By shill Date 2005-06-01 Time 16:11 Rev Time 1.00
Received By shill Date 2005-06-01 Time 16:11 Sent To  
Notes
2005-06-01 00:00:00****CORRECTIONS****
 RAILING SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE RAILING DETAILS ARE GENERIC AND
 ILLEGIBLE.THEY ARE PREPARED BY AN
 ENGINEER OTHER THAN EOR AND NOT SEALED.
  
  
 2.)PLEASE SUBMIT LEGIBLE DRAWINGS JOB
 SPECIFIC.DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 3.)IF THE RAILING DETAIL (WITH DESIGN
 CRITERIA FBC1608.2.2) IS PREPARED BY AN
 ENGINEER OTHER THAN EOR, HAVE THE
 DOCUMENT REVIEWED BY EOR.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-03-24 Cont ID  
Sent By shill Date 2004-03-24 Time 13:21 Rev Time 0.50
Received By shill Date 2004-03-24 Time 13:21 Sent To  
Notes
2004-03-24 00:00:00REVISION FOR CONNECTORS DATED 3/24/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 14:00 Rev Time 2.00
Received By shill Date 2004-03-05 Time 14:00 Sent To  
Notes
2004-03-05 00:00:00PROVISO
 1.) SUBMIT DETAIL (REVISION) FOR
 RAILINGS BEFORE INSTALLATION.
 2.) SUBMIT REVISED CONNECTORS OR
 SUBMIT CALCULATIONS OR TECHNICAL
 BULLETIN FROM MFGR.
 3.) SUBMIT REVISED EN CALC FOR WHOLE
 HOUSE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-23 Cont ID  
Sent By btrobaug Date 2004-03-04 Time 11:04 Rev Time 2.00
Received By shill Date 2004-02-23 Time 10:56 Sent To  
Notes
2004-02-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.) TWO COPIES OF ALL PERMIT DOCUMENTS
 MUST BE SUBMITTED.ONLY ONE COPY OF THE
 HVAC CALCS, RAILING DETAIL, AND SURVEY
 WAS SUBMITTED.
  
 2.)SEPARATE PERMIT REQUIRED FOR
 FENCING; PRODUCT APPROVALS NOT
 REQUIRED.
  
 3.)STUCCO OVER WIRE LATH IN A VERTICAL
 APPLICATION IS TO BE 7/8", FBC2504.2.2,
 ASTM C926.
  
 4.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 5.)GUARDRAILS ARE TO COMPLY WITH
 FBC1608.2.2 AND FBC1007.SUBMIT A
 DETAIL SHOWING COMPLIANCE BEFORE
 INSTALLATION.
  
 6.)THE PRINTED LICENSE NUMBER OF
 THE PERSON SEALING THE PLAN IS TO BE
 ON EACH SHEET, FAC61G15-23.002.
  
 7.)CONNECTOR CS185 (SHEET A5) IS NOT
 IN THE SIMPSON CATALOG.CS18 FASTENING
 CONFLICTS WITH THE CATALOG.ALL
 CONNECTORS SPECIFIED SHOULD BE FROM
 THE HIGH WIND CATALOG.FASTENING WHICH
 IS NOT CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS ARE TO
 EITHER HAVE A TECHNICAL BULLETIN
 SUPPLIED BY THE MANUFACTURER OR
 SEALED ENGINEER'S CALCULATIONS.CHECK
 ALL CONNECTORS.
  
 8.)PROVIDE THE APPROVED SITE PLAN
 STAMPED BY ZONING.
  
 9.)TRUSS BOTTOM CHORD LIVE LOAD IS TO
 BE A MINIMUM OF 10, FBC TABLE 16014.1.
 THE ENGINEER'S TITLE BLOCK IS TO BE ON
 EVERY SHEET.A PHOTOCOPY OF A SIGNATURE
 IS NOT ACCEPTABLE.CORRECTED TRUSS
 DRAWINGS MUST BE AVAILABLE AT TIME OF
 INSPECTION.
  
 10.)SUBMIT THE ORIGINAL APPROVED
 MECH/ELEC/PLUMBING SHEETS.THE SHEETS
 SUBMITTED WERE PHOTOCOPIES; MUST BE
 SIGNED/SEALED WHEN AN ENGINEER'S TITLE
 BLOCK IS ON THE PAGE.
  
 11.)WHEN RESUBMITTING, REMOVE OLD
 SHEETS AND REPLACE WITH REVISED SHEETS.
 SUBMIT OLD SHEETS SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-03 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:05 Rev Time 0.00
Received By hpiskura Date 2003-11-03 Time 13:03 Sent To  
Notes
2003-11-03 00:00:00THE SURVEY DOES NOT AGREE WITH THE SITE
 PLAN ON THE SOUTH ELEVATION.
  
 SHEET A2 DOES NOT HAVE INFORMATION FOR
 THE 2-2X6 TO SUPPORT THE H-7 TRUSS LIKE
 GRADE, SPECIES, LAP LENGHT OR FASTENING
 METHODS.
  
 THE NEW 24"X24" FOOTING DOES NOT A
 LENGTH MEASUREMENT, MINIMUM SOIL
 BEARING VALUE OR DEPTH BELOW GRADE.
  
 WHAT WILL BE DOWELED TO THE EXISTING
 FOOTER BETWEEN THE DINING ROOM AND
 KITCHEN.
  
 THE ROOM DIMENSIONS DO NOT DEFINE THE
 NEW CONSTRUCTION TO THE EXISTING.
  
 THE 18'X5' PORCH DOES NOT HAVE
 DIMENSIONS TO LOCATE THE FOOTING PIERS.
  
 THERE ARE NO DETAILS FOR THE
 CONSTRUCTION OF THE BREAKFAST ROOM WALL
 @ THE 45 DEEGREE ANGLE.
  
 THE TYPICAL HEADER DETAIL DOES NOT SHOW
 A CONTINUOUS LOAD PATH TO THE
 FOUNDATION.
  
 THERE ARE NO FRAMING PLANS FOR THE
 SECOND FLOOR.
  
 THE DELEGATION OF TRUSS DESIGN IS NOT
 SHOWN OR LOADS SPECIFIED.
  
 THERE IS STILLNO INFORMATION FOR THE
 CONNECTION OF THE TRUSSES TO THE
 EXISTING ROOF OR THE REQUESTED
 COMPUTATIONS TO DEMONSTRATE THE
 CAPABILITY OF THE EXITING CONSTRUCTION.
 TAX RECORDS INDICATE THIS HOUSE WAS
 CONSTRUCTED PRIOR TO 1940.
  
 IN SECTION CC, WHAT WILL THE HEAD ROOM
 BE ON THE SECOND FLOOR BALCONY?

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-09 Cont ID  
Sent By btrobaug Date 2003-10-27 Time 11:33 Rev Time 0.00
Received By hpiskura Date 2003-09-09 Time 14:56 Sent To  
Notes
2003-09-09 00:00:00PLEASE PROVIDE A RECENT SIGNED, SEALED
 AND DATED PROPERTY SURVEY.
  
 THE SITE PLAN ON SHEET A1 IS NOT CLEAR
 AS TO THE SIZE AND LOCATION OF THE
 ADDITION AND PORCHES.THE OTHER SHEETS
 ARE LACKING DIMENSIONS AS WELL FOR THE
 NEW WORK.PLEASE REVISE AS NECESSARY.
  
 THE DRIVE APPROACH SHOWN ON SHEET A1 IS
 NOT ACCEPTABLE IN WEST PALM BEACH.
 CONTACT M. AMINI AT 805-6723 FOR
 SPECIFIC INFORMATION.
  
 THE ROOF TRUSSES DATED 7/29/03 DO NOT
 SHOW THE MINIMUM 10# LIVE LOAD FOR THE
 BOTTOM CHORD IN ACCORDANCE WITH FBC
 TABLE 1604.1 FOR ATTICS WITHOUT STORAGE.
 PLEASE REVISE AS NECESSARY.
  
 THE TRUSS ENGINEERING SHOWS A 15# DEAD
 LOAD FOR THE TOP CHORD.SINCE A
 CONCRETETILE ROOF COVERING IS PROPOSED,
 WHAT IS THE ASSUMED WEIGHT OF
 MATERIALS?IE; PLYWOOD SHEATHING, FELT
 MATERIALS, ETC.HAS THE ENGINEER OF
 RECORD REVIEWED THE TRUSS DRAWINGS?
  
 SEVERAL OF THE TRUSSES ARE SHOWN AS
 SUPERIMPOSING POINT LOADS > 1000 LBS ON
 THE EXISTING ROOF STRUCTURE AS WELL AS
 INTERIOR BEARING WALLS NOT INDICATED ON
 THE PLANS.
 PLEASE PROVIDE COMPUTATIONS
 DEMONSTRATING THE ABILITLY OF THE
 EXISTING STRUCTURE
 TO SUPPORT THE NEW CONSTRUCTION.
  
 SHEET A3.PROVIDE A FRAMING DETAIL FOR
 THE TWO NEW DOOR OPENINGS ON THE FRONT
 PORCH SECOND FLOOR BALCONY.FBC 104.2.
  
 WHAT IS THE DESIGN LOAD FOR THE BALCONY?
  
 PLEASE SHOW A CONSTRUCTION DETAIL AND
 DESIGN LOADS FOR THE BALCONY GUARD
 RAILS. SEE FBC 104.2.
  
 WHAT IS THE SPACING OF THE FRONT PORCH
 COLUMNS?
  
 SHEET A3, SECTION C-C. THE NOTE "2X6
 STRAPPED TO EXISTING WALL STUDS" IS
 POOR ENGINEERING DESIGN FOR A BALCONY.
 PLEASE PROVIDE A CONSTRUCTION DETAIL
 WITH SPECIFIC INFORMATION.
  
 SECTION A-A CALLS OUT J BOLTS FOR
 ANCHORING THE BOTTOM PLATE.WILL THERE
 BE ANY WASHERS?
  
 THE FRONT AND REAR PORCHES INDICATE
 STEPS.PLEASE PROVIDE DIMENSIONS AND
 CONSTRUCTION DETAILS.
  
 A3 SECTION C-C.THE ROOF CONNECTION FOR
 THE PORCH TO THE EXISTING.WILL THERE
 BE ANY MODIFICATION TO THE EXISTING FOR
 UPLIFT?
  
 SHEET A2. WHAT IS THE SPACING OF THE
 RAFTERS, SHEATHING AND DESIGN LOAD FOR
 THE SHED ROOF?SEE FBC 104.2.
  
 WHAT IS THE FOOTING SIZE FOR THE SHED?
  
 SHOW THE TERMITE TREATMENT FOR THE SOIL
 AS PROVIDED FOR IN FBC 1816.
  
 SHEET A2.WHAT IS THE NOTE IN THE
 DINING ROOM AREA "DOWEL INTO EXISTING
 FOOTING" INDICATIVE OF?
  
 SHOW THE ATTIC ACCESS AND VENTILATION AS
 REQUIRED BY FBC 2309.6 AND 2309.7.
  
 THE ADDITION MAY BE SUBJECT TO IMPACT
 FEES COLLECTED BY COUNTY.THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION BEFORE A
 PERMIT MAY BE ISSUED.CALL
 561-233-5025 FOR MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 07:37 Rev Time 0.30
Received By dpalmer Date 2004-12-03 Time 07:37 Sent To  
Notes
2004-12-03 00:00:00REVISED PLANS, OK.
  
 LTR FROM ENGINEER OF RECORD(GORDON BUCK)
 HE IS NO LONGER ENGINEER OF RECORD FOR
 ELECTRICAL PLANS/WORK ON THIS PROJECT.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-09-23 Cont ID  
Sent By dpalmer Date 2004-09-23 Time 07:28 Rev Time 0.75
Received By dpalmer Date 2004-09-23 Time 07:12 Sent To  
Notes
2004-09-23 00:00:00********* UNSAT ******************
  
 1)NOTE: PLEASE SEE ORIGIANL PLANS ARE
 SIGNED AND SEALED BY AN ENGINEER.
 ANY REVISIONS TO PLANS ON FILE MUST BE
 REVISED ORIG ENG.
 FS 471
 PLEASE CALL FOR OTHER OPTIONS.
  
 2)NOTE: PLEASE SEE THERE ARE NUMEROUS
 CIRCUITS SHOWN ON PANEL SCHEDULES WHICH
 SHOW 20A BRKR AND #14 AWG.
 PLEASE SEE MANY OF THESE CIRCUITS ARE
 REQUIRED TO BE 20A CIRCUITS.
  
 3)NOTE: PLEASE SEE ALL EQUIPMENT LISTED
 ON PANEL "D" ARE NOT SHOWN ON PLAN?
 PLEASE ALSO SEE WATER HEATER INDICATED
 IN SHED BUT NOT ON PANLE SCHEDULE?
  
 4)NOTE: PLEASE SEE A WATER HEATER IS
 SHOWN ON PANEL "B" BUT NOT SHOWN ON MAIN
 HOUSE PLANS?
  
 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210.8A6
  
 6)NOTE: PLEASE SEE 210.52C1-5 FOR REQ'D
 RECEPT SPACING ALONG KITCHEN COUNTER-
 -SPACE. THERE ARE SOME MISSING.
  
 7)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL "A" FOR SUB-FEED CONDCUTOR
 SIZES.
  
 8)NOTE: PLEASE SEE OCP AND AWG FOR BOTH
 AHU'S. SHOWS 50A OCP AND #6 FOR 5KW
 HEAT INDICATED ON LOAD CALCULATIONS??
 424.3B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-09-16 Time 11:08 Rev Time 0.50
Received By btrobaug Date 2004-03-04 Time 10:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-27 Cont ID  
Sent By btrobaug Date 2003-10-27 Time 11:33 Rev Time 0.50
Received By btrobaug Date 2003-10-27 Time 11:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By kstevens Date 2003-10-25 Time 05:14 Rev Time 1.00
Received By btrobaug Date 2003-08-14 Time 14:03 Sent To P
Notes
2003-08-18 00:00:00PROVISO
 FAILED
 ~~~~~~
 PLEASE MAKE NECESSARY CHANGES TO PLANS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PANEL "B" MUST BE GROUNDED PER
 250-32,PLEASE SHOW SAME ON PLANS.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210.12
  
 6} THE DINING ROOM RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(A)(1).
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PROTECTED PER 210.8(A)(6).
 AND THE SPACING PER210.52(C)(1).
  
 8} THE BEDROOMS NEED RECEPTACLES ADDED
 TO COMPLY WITH 210.52(A)(1)&(2).
  
 9} THE BEDROOMS MUST COMPLY WITH 210.70.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 11:44 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 11:44 Sent To B
Notes
2005-05-27 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-11-30 Cont ID  
Sent By mjacobs Date 2004-11-30 Time 17:28 Rev Time 0.00
Received By mjacobs Date 2004-11-30 Time 17:28 Sent To E
Notes
2004-11-30 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-16 Time 11:08 Rev Time 0.00
Received By csiegber Date 2004-09-16 Time 11:08 Sent To E
Notes
2004-09-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-02 Cont ID  
Sent By shill Date 2004-03-02 Time 13:51 Rev Time 0.00
Received By shill Date 2004-03-02 Time 13:51 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 11:29 Sent To B
Notes
2004-03-01 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:05 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:05 Sent To B
Notes
2004-02-11 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 11:16 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 11:16 Sent To M
Notes
2003-10-16 00:00:00TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 11:09 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 11:09 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 13:10 Rev Time 0.00
Received By alange Date 2003-08-04 Time 13:10 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 08:02 Rev Time 0.00
Received By alange Date 2003-08-04 Time 08:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By pkrauss Date 2004-09-21 Time 13:23 Rev Time 0.45
Received By pkrauss Date 2004-09-21 Time 13:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By pkrauss Date 2003-10-17 Time 13:08 Rev Time 0.35
Received By pkrauss Date 2003-10-17 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-10-16 Time 11:16 Rev Time 0.25
Received By pkrauss Date 2003-08-26 Time 13:19 Sent To B
Notes
2003-08-26 00:00:00DENIED:
 PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS AS PER 2001 FBC CHAPTER 13
 SUB-SECTION 600.
  
 RETURN AIR REQUIRED AS PER 2001 FBC(M)
 601.4
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-25 Cont ID  
Sent By kstevens Date 2003-10-25 Time 05:14 Rev Time 0.50
Received By kstevens Date 2003-10-25 Time 05:14 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-22 Cont ID  
Sent By btrobaug Date 2003-10-24 Time 12:37 Rev Time 0.50
Received By kstevens Date 2003-08-22 Time 12:24 Sent To M
Notes
2003-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUPS SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SEC 909.1
 WASH MACHINE ON 2ND FLOOR.
 B) STANDPIPES ARE REQUIRED AT WASH
 MACHINES.
 C) SHOWER BATHROOM 2ND FLOOR SHOWS TWO
 LAVS ON FLOOR PLAN, BUT ONLY ONE ON SANT
 RISER DIAGRAM.
 2) SHOW DIMENSIONS FOR SHOWERS. MINIMUM
 SIZE 900 SQ INCHES. SHOWER COMPARTMENTS
 SHALL NOT BE LESS THAN 30" INSIDE FIN-
 ISHED SIDE TO SIDE. SECTION 417.4.
 3) SHOW SIZE OF OPENINGS FOR ALL WATER
 CLOSETS. PER SECTION 504.3.1
 4) SHOW MEASUREMENTS FOR TOILET ROOMS
 5) PROVIDE DETAILS FOR FLOOR DRAINS. IN-
 DICATE HOW THESE WILL BE MADE WATERPROOF
 OR WATER TIGHT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-04 Time 10:17 Rev Time 0.00
Received By mmclean Date 2004-03-04 Time 10:17 Sent To B
Notes
2004-03-04 00:00:00APPROVED BY ANA MARIE

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-12 Cont ID  
Sent By shill Date 2004-03-02 Time 13:51 Rev Time 0.25
Received By ajones Date   Time   Sent To  
Notes
***NONE***