| 2003-08-21 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. |
| | |
| | 3) PROVIDE A FINAL SOIL BORING TEST AS |
| | REQUIRED BY THE PRELIMINARY SOIL REPORT |
| | AND FBC 1804.2.2. |
| | |
| | 4) REVISE NOTE #11 ON C1. FBC 1606.1.4 |
| | REQUIRES PROTECTION OF GALZED OPENINGS |
| | IN WINDBORNE DEBRIS REGIONS AS WELL AS |
| | THE HVHZ. |
| | |
| | 5) REVISE NOTE #15 UNDER FRAMING NOTES |
| | ON C1. HIGH RIB METAL LATH IS REQUIRED |
| | TO BE FASTENED AT EVERY RIB (4"O.C.) PER |
| | ASTM C 1063. |
| | |
| | 6) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 1/2" DIA. ANCHOR BOLTS FOR THE GARAGE |
| | DOOR BUCKS ON THE DETAIL ON A4. |
| | |
| | 7) CLARIFY ON THE S.G.D. BUCK DETAIL ON |
| | A4 THAT THE FRAME IS FASTENED THROUGH |
| | THE 1X BUCK. |
| | |
| | 8) SUBMIT A TRUSS ANCHOR SCHEDULE. FBC |
| | 1609.4.3 NO LONGER ALLOWS THE ONE-THIRD |
| | INCREASE IN THE STEEL CALCULATIONS FOR |
| | COMBINATION LOADS. SEE THE 2003 USP OR |
| | 2002 SIMPSON HIGH WIND CONSTRUCTION |
| | CATALOGS FOR CONNECTOR VALUES WITHOUT |
| | THE INCREASE. |
| | |
| | 9) REVISE CONNECTION DETAIL 2 ON A5. THE |
| | MAXIMUM UPLIFT VALUE IS 1125# WITH (7) |
| | 16D NAILS IN EACH MEMBER. SEE 2003 USP |
| | CATALOG. |
| | |
| | 10) DETAIL 11 ON A5 SPECIFIES A HANGER |
| | ON A MASONRY WALL FASTENED WITH (2) 5/8" |
| | THROUGH BOLTS ON EACH SIDE. PLEASE |
| | CLARIFY. |
| | |
| | 11) AN ID. TAG FOR A DETAIL 1 ON A6 IS |
| | GIVEN ON THE FRAMING PLAN ON A5, HOWEVER |
| | THERE IS NO SUCH DETAIL. PLEASE CORRECT. |
| | |
| | 12) AN ID. TAG FOR DETAIL 1 ON A8 IS ON |
| | THE FRAMING PLAN ON A5 AND THERE IS NOT |
| | A SHEET A8. PLEASE CORRECT. |
| | |
| | 13) A SEPARATE PERMIT FOR ROOFING WILL |
| | BE REQUIRED. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE |
| | SINGLE HUNG WINDOWS. |
| | |
| | 15) THE SITE SPECIFIC PRODUCT APPROVALS |
| | DO NOT LIST THE 3'X 8' F.G. WINDOWS. |
| | THE SITE SPECIFIC PRODUCT APPROVAL FORM |
| | IS REQUIRED TO BE SIGNED BY THE DESIGNER |
| | RECORD OR A SIGNED AND SEALED LETTER OF |
| | APPROVAL FROM THE D.O.R. MUST ACCOMPANY |
| | THE FORM. |
| | |
| | 16)THE STORM PANEL KEY PLAN AND SCHEDULE |
| | DO NOT CORRESPOND TO THE PLANS. THE |
| | PRODUCT APPROVAL THAT WAS SUBMITTED HAS |
| | EXPIRED. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |