Plan Review Details - Permit 03072358
Plan Review Stops For Permit 03072358
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By jwitmer Date 2003-09-23 Time 17:37 Rev Time 0.45
Received By jwitmer Date 2003-09-23 Time 17:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-12 Cont ID  
Sent By jwitmer Date 2003-08-12 Time 10:49 Rev Time 1.25
Received By jwitmer Date 2003-08-12 Time 10:49 Sent To  
Notes
2003-08-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03072358
 ADD: 531 SOUTHERN BLVD
 CONT: MALT CONSTRUCTION
 TEL: (561)799-2961
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) INFORMATION ON THE (2) 2X10 ATTACH-
 MENT TO THE CMU WALL.
 B) WHAT TYPE OF SIMPSON DEVICE IS THE
 DESIGN SPECING FOR THE CEILING JOIST?
  
 2) THE CEILING JOIST SIZE ARE NOT SPECED
 OUT, NOR THE SPACING?
  
 3) DETAIL# 1 DOESN'T SHOW A BEARING SUR-
 FACE ONTHE FRAME WALL, WILL THIS ALSO BE
 A BUCKET OR HANGER?
  
 4) WILL THE SURFACE ABOVE BE USED FOR
 STORAGE?
 A)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 B)106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 13:14 Rev Time 1.50
Received By dpalmer Date 2003-10-03 Time 13:14 Sent To  
Notes
2003-10-03 00:00:00************ PROVISO/REVISION ********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 PLEASE SEE THAT A SEPARATE ELECTRICAL
 PERMIT IS REQ'D. THIS WORK WAS NOT UNDER
 PREVIOUS ELECTRICAL PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -ION
 PLEASE ALSO SUBMIT ANY OTHER REVISIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-01 Cont ID  
Sent By dpalmer Date 2003-08-01 Time 06:37 Rev Time 0.33
Received By dpalmer Date 2003-08-01 Time 06:37 Sent To  
Notes
2003-08-01 00:00:00******************* UNSAT ***********
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G1-16.004 FOR REQ'D MISSING
 INFORMATION FOR ARCH'S TITLE BLOCK.
 FS 481
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
 PLEASEPROVIDE LOAD CALC ON PANEL FOR
 ADDING OF NEW CIRCUITS AND A/C SYSTEM
  
 3)NOTE: PLEASE SHOW LOCATION OF NEW
 A/C SYSTEM AND REQ'D DISC'S 440.11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-29 Cont ID  
Sent By nmccray Date 2003-09-29 Time 10:36 Rev Time 0.00
Received By nmccray Date 2003-09-29 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By nmccray Date 2003-08-20 Time 14:58 Rev Time 0.00
Received By nmccray Date 2003-08-20 Time 14:58 Sent To  
Notes
2003-08-20 00:00:001) WHAT WILL BE OCCUPANCY OR USE
 CATEGORY.
  
 2) PLAN DOESN'T SHOW EXIT SIGNS OR
 EMERGENCY LIGHTS.
  
 3) WHAT ARE THE INTERIOR FINISH
 CLASSIFICATION FOR THE WALLS AND
 CEILINGS, CLASS "A" OR CLASS "B".
  
 4) WILL THERE BE ANY COOKING IN THIS
 BUSINESS.
  
 5) PORTABLE FIRE EXTINGUISHER IS
 REQUIRED.
  
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 11:54 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 11:54 Sent To  
Notes
2003-09-15 00:00:00ON COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 09:46 Rev Time 0.00
Received By alange Date 2003-07-31 Time 09:46 Sent To  
Notes
2003-07-31 00:00:00TO COMM BD #26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-29 Cont ID  
Sent By pkrauss Date 2003-09-29 Time 09:33 Rev Time 0.40
Received By pkrauss Date 2003-09-29 Time 09:33 Sent To  
Notes
2003-09-29 00:00:00PROVISO:
 FRESH AIR INTAKE SHALL BE A MINIMUM OF
 10 FT FROM EXHAUST.2001 FBC(M) 401.5.1
  
 CONDENSING UNIT STAND SHALL COMPLY WITH
 2001 FBC 1511.7:

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-08-20 Time 10:43 Rev Time 0.25
Received By pkrauss Date 2003-08-20 Time 10:43 Sent To  
Notes
2003-08-20 00:00:00MECHANICAL CONTRACTOR LISTED ON PERMIT
 APPLICATION WILL NOT BE DOING THE JOB
 PER OWNERS REQUEST.MECHANICAL PERMIT
 TO BE FILED FOR SEPARATELY AND PLANS
 SUBMITTED WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-29 Cont ID  
Sent By pkrauss Date 2003-09-29 Time 09:38 Rev Time 0.05
Received By pkrauss Date 2003-09-29 Time 09:38 Sent To  
Notes
2003-09-29 00:00:00NO PLUMBING PLANS SUBMITTED FOR
 REVIEW.