Plan Review Details - Permit 03072203
Plan Review Stops For Permit 03072203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-14 Cont ID  
Sent By kstevens Date 2003-08-11 Time 18:16 Rev Time 0.00
Received By rbrown Date 2003-08-14 Time 09:55 Sent To  
Notes
2003-08-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 3401.7.2.4HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS WILL BE
 REQUIRED ON THE NEW WINDOWS IF THE AREA
 OF GLASS IN THE NEW WINDOWS EXCEEDS 25%
 OF THE TOTAL GLAZED AREA OF THE WHOLE
 RESIDENCE.PROVIDE A PRODUCT APPROVAL
 FOR SHUTTERS FOR THE NEW WINDOWS OR
 SUBMIT DETAILS TO VERIFY THAT THE NEW
 WINDOW GLASS AREA IS LESS THAN 25% OF
 THE GLAZED AREA OF THE WHOLE RESIDENCE.
  
 4) FBC 1707.4.2MIAMI-DADE PRODUCT
 APPROVAL, ICC-ES EVALUATION REPORT OR
 SITE-SPECIFIC ENGINEER'S CERTIFICATION
 IS REQUIRED FOR THE PROPOSED WINDOWS.
 THE NOTICE OF EVALUATION SUBMITTED FOR
 THE AMERICAN CRAFTSMAN SINGLE HUNG
 WINDOW IS NOT SUFFICIENT.BLANK COPIES
 OF THE PRODUCT APPROVAL SUBMITTAL FORM
 ARE ATTACHED, FOR USE IF THE SITE-
 SPECIFIC ENGINEERING OPTION IS TO BE
 PURSUED.
  
 5) FBC* 104.2.1THE DRAWING TITLE BLOCK
 IS NOT PRINTED CLEARLY.ALL DRAWINGS
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 6) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ALSO, THE PLANS
 SHALL CITE FLORIDA BUILDING CODE 2001
 (WITH REVISIONS AS OF JUNE 2003) AS THE
 BASIS OF THE DESIGN.
  
 7) FBC 1606.2.2 WALL SECTION - ANCHORING
 OF 2X6 BASE PLATE.ANNOTATE THE PLANS
 TO STATE WHAT THE PROPOSED RED HEAD
 ANCHORS WILL BE BOLTED INTO AT 24" O.C.
  
 8) FBC 1606.2.2WALL SECTION.THE
 STRAPS SPECIFIED ARE SIMPSON HETAL 16
 (ANNOTATION IS NOT PRINTED CLEARLY ON
 THE PLANS).THIS TYPE OF ANCHOR IS
 DESIGNED FOR EMBEDMENT IN THE TIE BEAM
 AND IS NOT SUITABLE FOR THE PROPOSED
 USE.SPECIFY AN ALTERNATIVE ANCHOR
 CAPABLE OF RESISTING THE LALETRAL LOADS
 DUE TO WIND PRESSURES IN THE WALL. ALSO,
 ADD DIMENSIONS TO THE WALL SECTION TO
 SHOW THE HEIGHT OF THE EXISTING CMU WALL
 AND THE OVERALL WALL HEIGHT.
  
 9) FBC 2308.3WOOD FRAMING AROUND DOOR
 AND WINDOW OPENINGS.AMEND THE PLANS TO
 SHOW THE WOOD FRAMING AROUND THE NEW
 WINDOWS AND THE DOOR.THE STRAPS AND
 ANCHORS SHALL RESIST THE LATERAL LOADS
 DUE TO WIND PRESSURES ON THE WINDOW/DOOR
 AND ADJACENT FRAMED WALL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-07 Time 15:23 Rev Time 0.50
Received By dpalmer Date 2003-08-08 Time 07:45 Sent To P
Notes
2003-08-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ADDING ADDITIONAL LOADS OF NEW
 WASHER AND DRYER.PLEASE SHOW SIZE OF
 EXISTING PANEL. 215-5
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210-52
  
 3)NOTE: PLEASE SHOW THE REQ'D ARC-FAULT
 PROTECTED CIRCUITS PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 15:17 Rev Time 0.00
Received By alange Date 2003-08-07 Time 15:17 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 08:19 Rev Time 0.00
Received By alange Date 2003-08-04 Time 08:19 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 09:49 Rev Time 0.00
Received By alange Date 2003-07-30 Time 09:49 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-11 Cont ID  
Sent By dpalmer Date 2003-08-08 Time 08:54 Rev Time 0.33
Received By kstevens Date 2003-08-11 Time 18:16 Sent To B
Notes
2003-08-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUP SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 15:22 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-04 Time 08:19 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-08-01 00:00:008/1/03 DENIED, NEED COPY OF 2 SURVEY
 CALLED OWNER FILE M MM