Plan Review Details - Permit 03072146
Plan Review Stops For Permit 03072146
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-28 Cont ID  
Sent By rbrown Date 2003-08-28 Time 10:21 Rev Time 0.00
Received By rbrown Date 2003-08-28 Time 10:20 Sent To  
Notes
2003-08-28 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 11-4.13.6THE 3070 S.C. DOOR TO THE
 EXISTING LUNCH ROOM DOES NOT HAVE THE
 REQUIRED 18" CLEARANCE BETWEEN THE
 STRIKE EDGE OF THE DOOR AND THE ADJACENT
 WALL ON THE PULL SIDE .IT MUST BE
 RECONFIGURED DOOR SHALL BE EITHER:
 (A) OMITTED, OR
 (B) MOVED TO ALIGN WITH THE REAR WALL
 OF THE CLOSET PROVIDED THERE IS 12"
 CLEARANCE ON THE PUSH SIDE OF THE
 DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-15 Cont ID  
Sent By rbrown Date 2003-08-15 Time 09:34 Rev Time 0.00
Received By rbrown Date 2003-08-15 Time 09:33 Sent To  
Notes
2003-08-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) 61G1-16.004 FL. ADMIN. CODE.THE
 TITLE ON THE DRAWING SHALL INCLUDE THE
 FIRM LICENSE NUMBER (SEE FAC EXTRACT
 ATTACHED TO THE ELECTRICAL REVIEW
 COMMENT SHEET)
  
 3) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT THE NEW DOOR TO THE EXISTING LUNCH
 ROOM.18" CLEARANCE IS REQUIRED BETWEEN
 THE LEADING EDGE OF THE DOOR AND THE
 ADJACENT PERPENDICULAR WALL ON THE PULL
 SIDE OF THE DOOR.AMEND/ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.THE
 STATEMENT IN NOTE 4 (SHEET A-1) HAS
 BEEN NOTED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-08-27 Time 19:45 Rev Time 0.33
Received By dpalmer Date 2003-08-27 Time 19:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-01 Cont ID  
Sent By dpalmer Date 2003-08-01 Time 11:33 Rev Time 0.33
Received By dpalmer Date 2003-08-01 Time 11:33 Sent To  
Notes
2003-08-01 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW MIN CIRCUITING NOTE
 OR CIRCUITS ON PLANS AND CORRELATE WITH
 SUBMITTED PANEL SCHEDULES.
  
 2)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G1-16.004 FOR MISSING INFORMATION
 REQ'D ON TITLE BLOCK. FS 471
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS, THAT MAY HAVE AN AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By mcarsill Date 2003-08-21 Time 09:24 Rev Time 0.00
Received By mcarsill Date 2003-08-21 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 16:40 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 16:40 Sent To  
Notes
2003-08-27 00:00:00TO COMM BD #49

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 09:03 Rev Time 0.00
Received By alange Date 2003-07-29 Time 09:03 Sent To  
Notes
2003-07-29 00:00:00TO BLDG COMM BOX #41

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-04 Cont ID  
Sent By pkrauss Date 2003-08-04 Time 09:41 Rev Time 0.25
Received By pkrauss Date 2003-08-04 Time 09:38 Sent To  
Notes
2003-08-04 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-28 Cont ID  
Sent By kstevens Date 2003-08-28 Time 10:17 Rev Time 0.25
Received By kstevens Date 2003-08-28 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-12 Cont ID  
Sent By kstevens Date 2003-08-12 Time 11:09 Rev Time 0.50
Received By kstevens Date 2003-08-12 Time 11:09 Sent To  
Notes
2003-08-12 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) 61G1-16.004 TITLE BLOCK - SEE ATTACH-
 ED SHEET FOR INFORMATION REQUIRED ON
 TITLE BLOCK. (ATTACHED TO ELECT. COMMENT
 SHEET)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]