Plan Review Details - Permit 03072014
Plan Review Stops For Permit 03072014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-09-26 Time 15:34 Rev Time 0.00
Received By lsmith Date 2003-09-29 Time 10:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-11 Cont ID  
Sent By jwitmer Date 2003-08-11 Time 14:53 Rev Time 0.75
Received By jwitmer Date 2003-08-11 Time 14:53 Sent To  
Notes
2003-08-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03072014
 ADD: 4055 N HAVERHILL RD
 CONT:WAYNE DEVELOPMENT CORP
 TEL: (954)650-5810
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 1025.2 LOCKS(1) A SIGN IS READILY VIS
 IBLE DUABLE SIGN ON OR ADJACENT TO THE
 DOOR STATING: THIS DOOR TO REMAIN UNLOCK
 ED WHEN THIS BUILDING IS OCCUPIED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLAN INDICATES A NEW ROOM, SINCE
 THE OCCUPANCY IS MERCANTILE, IF USED AS
 A FITTING OR DRESSING ROOM MUST COMPLY
 WITH 11-4.35(1-5).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-26 Cont ID  
Sent By dpalmer Date 2003-09-26 Time 15:34 Rev Time 0.75
Received By dpalmer Date 2003-09-26 Time 15:34 Sent To B
Notes
2003-09-26 00:00:00PLANS SENT TO LEA SMITH TO PROCESS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-23 Time 16:11 Rev Time 0.50
Received By dpalmer Date 2003-09-08 Time 10:49 Sent To  
Notes
2003-09-08 00:00:00*************UNSAT ****************
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
 IT APPEARS THAT ONLY NOTE#1 WAS ADDRESS-
 ED?
  
 PLEASE SEE ORIG NOTES ATTACHED.
  
 PLEASE SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-01 Cont ID  
Sent By dpalmer Date 2003-08-01 Time 06:16 Rev Time 0.33
Received By dpalmer Date 2003-08-01 Time 06:16 Sent To  
Notes
2003-08-01 00:00:00********** UNSAT ********************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK AS REQ'D
 UNDER FS-471, 61G15-23.004.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 SERVICE TO BE NEW? NO NOTES IF ALL
 EXISTING?
  
 3)NOTE: PLEASE SEE ALL SERVICE CONDUCTOR
 -S.??350MCM FOR 600A'S, #1'S FOR 200A
 MAIN DISC'S? PLEASE SIZE AND SHOW PER
 310.16
 350MCM MENTIONS IN ONE 3' CONDCUIT? IS
 THIS MEANT TO BE 2-3" CONDUITS?
  
 IT APPEARS THESE MUST BE MISPRINTS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-29 Cont ID  
Sent By mcarsill Date 2003-07-29 Time 17:24 Rev Time 0.00
Received By mcarsill Date 2003-07-29 Time 17:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 16:11 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 16:11 Sent To E
Notes
2003-09-23 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 09:34 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 09:33 Sent To  
Notes
2003-08-27 00:00:00TO COMM BD #9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 07:57 Rev Time 0.00
Received By alange Date 2003-07-28 Time 10:03 Sent To  
Notes
2003-07-28 00:00:00TO COMM BD # 24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-12 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 07:14 Rev Time 0.10
Received By pkrauss Date 2003-08-12 Time 07:13 Sent To  
Notes
2003-08-12 00:00:00HVAC EXISTING AS PER NOTE ON A-1.
 SEPARATE PERMIT REQUIRED SHOULD ANY
 HVAC WORK BE DONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-08-12 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 07:14 Rev Time 0.10
Received By pkrauss Date 2003-08-12 Time 07:14 Sent To  
Notes
2003-08-12 00:00:00PLUMBING EXISTING - NO CHANGE PER NOTE
 ON PLAN SHEET A-1