Plan Review Details - Permit 03071836
Plan Review Stops For Permit 03071836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By jwitmer Date 2003-09-23 Time 08:02 Rev Time 0.80
Received By jwitmer Date 2003-09-23 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-11 Cont ID  
Sent By jwitmer Date 2003-08-11 Time 07:15 Rev Time 1.75
Received By jwitmer Date 2003-08-11 Time 07:14 Sent To  
Notes
2003-08-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03071836
 ADD: 326 ACACIA RD
 CONT: BRICE BUILDING
 TEL: (954)420-0110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) WHAT TYPE BUILDING IS THIS?
  
 2) PLANS INDICATE THAT THIS SPACE WILL
 BE USED FOR DANCE STUDIO BUT THE OCCUPAN
 CY INDICATED IS BUSINESS? EDUCATION.
  
 3) TOTAL OCCUPANT LOAD IS INDICATED AS
 75, THIS REQUIRES 2 MEANS OF EGRESS SEE
 1004.1.2.
 THE 2 MEANS OF EGRESS SHALL BE AT LEAST
 1/3RD THE DISTANCE APART FOR FULLY SPRIN
 KLERED BUILDINGS.
  
 4) RAMPS @ ENTRY DOOR # 418,
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.ALSO SEE 1012.3 MOST
 RESTRICTIVE SHALL APPLY.
  
 5)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 THE NEW EGRESS DOORWAY TO COMPLY WITH
 1021.4.
  
 6) DEPENDING ON THE TYPE BUILDING THIS
 BUILDING IS THIS COMMENT MAY OR MAY NOT
 APPLY, SEE 803.7 FLOOR FINISHES.
  
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-08 Cont ID  
Sent By dpalmer Date 2003-09-08 Time 07:10 Rev Time 0.25
Received By dpalmer Date 2003-09-08 Time 07:10 Sent To  
Notes
2003-09-08 00:00:00REVISED ELEC SHEET FOR EXT/ EM LTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-01 Cont ID  
Sent By dpalmer Date 2003-08-01 Time 11:18 Rev Time 0.33
Received By dpalmer Date 2003-08-01 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-08 Cont ID  
Sent By nmccray Date 2003-09-08 Time 15:38 Rev Time 0.00
Received By nmccray Date 2003-09-08 Time 15:38 Sent To  
Notes
2003-09-08 00:00:00***********PROVISO**********************
 ADDITIONAL SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-08-20 Cont ID  
Sent By mcarsill Date 2003-08-20 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2003-08-20 Time 11:23 Sent To  
Notes
2003-08-20 00:00:001) PLEASE INDICATE PROPOSED OCCUPANT
 LOAD.
  
 2) A SINGLE MEANS OF EGRESS FROM THE
 ROOM IS SHOWN. AT LEAST TWO MEANS OF
 EGRESS IS REQUIRED.
  
 3) WHEN CEILING IS PAINTED FLAT BLACK,
 CARE IS TO BE TAKEN NOT TO PAINT
 THE FIRE SPRINKLER HEADS.
  
 4) ANY EMERGENCY LIGHTS OR EXIT SIGNS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 16:32 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 16:32 Sent To  
Notes
2003-09-03 00:00:00ON COMM BD #25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:46 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:46 Sent To  
Notes
2003-07-30 00:00:00TO BLDG COMM BD #6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-25 Cont ID  
Sent By mmclean Date 2003-07-30 Time 12:45 Rev Time 0.00
Received By alange Date 2003-07-25 Time 10:47 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-12 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 07:24 Rev Time 0.10
Received By pkrauss Date 2003-08-12 Time 07:23 Sent To  
Notes
2003-08-12 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-30 Cont ID  
Sent By mmclean Date 2003-07-30 Time 12:45 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***