Plan Review Details - Permit 03071511
Plan Review Stops For Permit 03071511
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By rmcdouga Date 2003-10-27 Time 16:27 Rev Time 2.00
Received By rmcdouga Date 2003-10-27 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-10 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 08:39 Rev Time 2.00
Received By rmcdouga Date 2003-10-10 Time 09:41 Sent To  
Notes
2003-10-10 00:00:00DENIED
  
 1) SHEET RF-1 IS THE REVERSE OF THE REST
 OF THE PLANS. SUBMIT RF-1 SHEET WITH THE
 CORRECT ORIENTATION.
  
 2) SHEETS 1, SD1, SD2, AND RF 1 FOR THE
 ROYALL WALL SYSTEM DOES NOT HAVE THE
 ORIGINAL WET SIGNATURE OF THE ENGINEER
 AS REQUIRED BY FAC 61G15-23.002.
  
 3) IF USING ALLOWABLE STRESS DESIGN,
 INCREASES IN THE ALLOWABLE STRESS OF THE
 STEEL FOR THE TRUSS CONNECTORS IS NOT
 ALLOWED BY FBC 1609.4.3 (2). DESIGN
 CALCULATIONS WILL BE REQUIRED TO BE
 SUBMITTED IF CONNECTOR VALUES WITH THE
 ONE-THIRD INCREASE IS USED.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 IMPACT RESISTANT WINDOW IN THE DEN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-15 Cont ID  
Sent By kstevens Date 2003-10-08 Time 10:13 Rev Time 3.00
Received By rmcdouga Date 2003-08-15 Time 10:27 Sent To  
Notes
2003-08-15 00:00:00DENIED
  
 1) THE ENGINEER'S TITLE BLOCK DOES NOT
 HAVE HIS LICENSE NUMBER LISTED. THE
 TITLE BLOCK ON THE PLANS AND THE ROYAL
 WALL DRAWINGS ARE DIFFERENT FOR THE SAME
 ENGINEER. PLEASE CLARIFY. THE REGISTRAT-
 ION NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED IN THE TITLE BLOCK. SEE FAC
 61G15-23002.
  
 2) THE TITLE BLOCK FOR THE ARCHITECT IS
 MISSING THE ADDRESS AND LICENSE NUMBER.
 SEE FAC 61G1-16.004.
  
 3) AFFINITY ARCHITECTS SHOULD REMOVE
 THEIR TITLE BLOCK IF THEY ARE NOT THE
 DESIGNERS OF RECORD.
  
 4) SHEET 2 REFERENCES THE 1997 STANDARD
 GAS CODE. PLEASE UPDATE TO THE 2001 FBC
 FUEL GAS CODE.
  
 5) THE TOTAL SQFT LISTED ON SHEET 2 IS
 INCORRECT. PLEASE RETOTAL AREAS LISTED.
  
 6) FBC 11-4.23.2 REQUIRES AT LEAST ONE
 BATH ROOM WITH A DOOR THAT HAS A 29"
 CLEAR OPENING. BECAUSE FULL BATHS ARE
 PROVIDED ON HABITABLE GRADE, ONE OF THEM
 MUST COMPLY.
  
 7) SHEET 6 SPECIFIES HUGHES CONNECTORS
 ON THE KNEE WALL AND INTERIOR BEARING
 PARTITION DETAILS. HUGHES IS NO LONGER
 IN BUSINESS. PLEASE UPDATE.
  
 8) HUGHES ANS SEMCO CONNECTORS ARE
 SPECIFIED ON RF-1. THEY ARE NO LONGER IN
 BUSINESS. PLEASE UPDATE.
  
 9) THE ROOF SHEATHING NAILING ON THE
 TYPICAL WALL SECTION ON SHEET 6 DOES NOT
 CORRESPOND WITH THE NAILING SCHEDULE ON
 SHEET 4. PLEASE CORRECT.
  
 10) FBC 1609.4 DOES NOT ALLOW A ONE-
 THIRD INCREASE IN STEEL STRESS CALCS.
 PLEASE REVIEW THE ANCHOR SCHEDULES ON
 RF-1 AND SD2 AND REVISE VALUES.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
  
 12) THE DOOR FROM THE GARAGE TO THE
 CONDITIONED AREA IS REQUIRED TO BE
 SOLID CORE OR INSULATED. SEE FBC CHAPTER
 13-603.1.ABC.1.
  
 13)STORM PANELS:THE SAFEGUARD COMPANY IS
 NO LONGER IN BUSINESS AND WEATHERGUARD
 HAS NOT COMPLETED THE PROCESS OF
 ASSUMING THE PRODUCT APPROVAL FROM SBCCI
 THE BUILDING OFFICIAL HAS DETERMINED
 THAT WE CAN NOT ACCEPT THIS PRODUCT FOR
 USE IN THE CITY OF WPB AT THIS TIME.
 THE SBCCI REPORT NO. 9808 THAT WAS
 SUBMITTED IS NO LONGER CURRENT.
  
 14)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 PLEASE INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 15) THE TRUSS DRAWINGS FOR SINGLE FAMILY
 DWELLINGS ARE NO LONGER REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. THEY ARE TO
 BE GIVEN TO THE INSPECTOR AT THE ROOF
 FRAMING INSPECTION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 07:58 Rev Time 0.25
Received By dpalmer Date 2003-10-27 Time 07:58 Sent To B
Notes
2003-10-27 00:00:00ALL REVISIONS AND OPTIONS TO BE
 REVISED BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-24 Time 12:48 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 12:17 Sent To P
Notes
2003-10-07 00:00:00********** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES.
 A/C SUB PANEL IS SHOWN AS AN 80A FEED
 AND AWG IS ONLY RATED FOR 60A'S. A/C
 PANEL IS SHOWN AS 60A ON RISER?
  
 2)NOTE: PLEASE SEE THE ONLY PANEL
 SCHEDULE SUBMITTED FOR A SUB PANEL IS
 FOR A 125A GEN LT AND RECEPTS.
 PLEASE SUBMIT OTHER PANEL SCHEDULES AS
 REQ'D. 215.5
  
 3)NOTE: PLEASE SEE THAT A NEW RISER IS
 NOW SUBMITTED. PLEASE SEE MISSING FOOTER
 STEEL AND COLD WATER PIPE REQD FOR
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 4)NOTE: PLEASE SEE 210.12 ARC FAULT IS
 NOT FOR ONLY RECEPTS UNDER THE 2002 NEC
 WHICH WENT INTO EFFECT 7/1/2003
  
 5)NOTE: PLEASE SEE THAT LOAD FOR A/C
 SUB PANEL IS SHOWN AT 75A'S.
  
 6)NOTE: RANGE IS SHOWN AS OPT (GAS) A
 MIN LOAD FOR ELECTRICAL MUST BE SHOWN
 PER TABLES IN NEC 220
  
 7)NOTE: PLEASE SEE MIN LOAD FOR ELEC
 DRYER TO BE 5KW 220.18
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:25 Rev Time 0.50
Received By dpalmer Date 2003-07-31 Time 05:50 Sent To M
Notes
2003-07-31 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN AT MCB PANEL. NOTES MENTION USE OF
 FUSES AND FUSIBLE DISC HAS BEEN REMOVED?
 110.9
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM. MAIN PANEL SHOWS
 3-SUB PANELS AND ONLY ONE SHOWN ON
 RISER.
  
 4)NOTE: PLEASE SHOW WHERE A/C UNITS ARE
 BEING FED FROM. SHOWS A A/C SUB PANEL
 BUT ONLY SUB PANEL SHOWN IS FEEDING ALL
 GENERAL PURPOSE LT/RECEPTS?
  
 5)NOTE; PLEASE SHOW PANEL LOCATIONS ON
 PLANS.
  
 6)NOTE: PLEASE SEE FAC/ FS 481 AND
 61G1-16.004 FOR MISSING INFORMATION
 RE'D ON TITLE BLOCK FOR ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 12:48 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 12:48 Sent To E
Notes
2003-10-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:25 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 09:25 Sent To E
Notes
2003-10-06 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-24 Cont ID  
Sent By alange Date 2003-07-24 Time 13:33 Rev Time 0.00
Received By alange Date 2003-07-24 Time 13:33 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-21 Cont ID  
Sent By mmclean Date 2003-07-24 Time 10:38 Rev Time 0.00
Received By shernand Date 2003-07-21 Time 10:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-10 Cont ID  
Sent By dpalmer Date 2003-07-31 Time 07:25 Rev Time 0.25
Received By pkrauss Date 2003-08-10 Time 18:42 Sent To P
Notes
2003-10-10 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By kstevens Date 2003-10-08 Time 10:13 Rev Time 0.33
Received By kstevens Date 2003-10-08 Time 10:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-11 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 13:40 Rev Time 0.33
Received By jleech Date 2003-08-11 Time 18:17 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-24 Cont ID  
Sent By shernand Date 2003-07-21 Time 10:56 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***