Plan Review Details - Permit 03071487
Plan Review Stops For Permit 03071487
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-26 Cont ID  
Sent By hpiskura Date 2003-08-26 Time 06:45 Rev Time 0.00
Received By hpiskura Date 2003-08-25 Time 12:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-07 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 12:17 Rev Time 0.00
Received By hpiskura Date 2003-08-07 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-16 Cont ID  
Sent By dpalmer Date 2003-09-16 Time 06:53 Rev Time 0.50
Received By dpalmer Date 2003-09-16 Time 06:31 Sent To  
Notes
2003-09-16 00:00:00********** NOTES REDLINED *****
  
 PLEASE SEE THAT AN EQUIPMENT GROUNDING
 CONDUCTOR IS NOT INSTALLED FROM METER
 TO MAIN DISCONNECT. 250.24
  
 GFI CODE REFERENCE ON PLAN, SHOWS 210.88
 SHOULD BE 210.8

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-26 Cont ID  
Sent By dpalmer Date 2003-08-26 Time 06:49 Rev Time 1.00
Received By dpalmer Date 2003-08-25 Time 18:00 Sent To  
Notes
2003-08-26 00:00:00**************UNSAT ***************
  
 PLEASE SEE NOTES FROM FIRST REVIEW, SOME
 NOT COMPLETED.SOME NEW NOTES FROM PLANS
 BEING CHANGED AND FROM RISER DIAGRAM
 BEING SUBMITTED.
  
 1)NOTE: PLEASE CLARIFY SIZING OF SERVICE
 ENT CONDUCTORS FOR 200A SERVICE. SHOWN
 AS 1/0`S PLEASE SEE 310.16.
  
 2)NOTE: PLEASE CLARIFY HOW SUB PANEL IS
 BEING FED? RISER SHOWS COMING FROM PANEL
 'A', YET PANEL "A" SCHEDULE DOES NOT
 SHOW SUB PANEL/OCP FEEDING PANEL "B"??
  
 3)NOTE: PLEASE CLARIFY TWO ITEMS SHOWN
 ON PANEL SCHEDULE "A" ,220A CIRCUIT?
 ONE SHOWN WITH #10 AWG? PLEASE CLARIFY
 WHAT THESE ARE?
  
 4)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLAN W/ PANEL SCHEDULE. PLEASE SEE
 WATER HEATER?WH, SHOWN AS #6, YET
 PANEL SCHEDULE SHOWS GEN LTS?
  
 5)NOTE: PLEASE SEE 250.110 AND 250.122
 FOR MISSING EQUIPMENT GROUNDING CONDUCT-
 OR FROM MAIN PANEL TO SUB-PANEL?
  
 6)NOTE: PLEASE SEE 424.3B FOR SIZING
 OF OCP FOR AHU. PLEASE ALSO SEE 310.16
 FOR AWG.
  
 7)NOTE: PLEASE SEE 210.8B, 1,2,3 FOR
 GFI PROTECTION REQ'D IN KITCHENS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 13:57 Rev Time 0.50
Received By dpalmer Date 2003-07-23 Time 07:33 Sent To  
Notes
2003-07-23 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY CONFLICTING NOTES
 ON PLANS. NOTE 6 MENTIONS TO CONNECT
 NEW ELEC TO EXISITNG PANELS, HOWEVER
 OTHER NOTES MENTION THAT BOTH PANELS
 ARE BEING REPLACED?
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE.
 PLEASE CIRCUIT EM/EXT LTS PER 700.12E
  
 3)NOTE: PLEASE CLARIFY NEW/OR EXISTING
 EGRESS LIGHTING OUTSIDE DOORWAYS.
 LIFE SAFETY 101 5-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By mcarsill Date 2003-09-02 Time 16:26 Rev Time 0.00
Received By mcarsill Date 2003-09-02 Time 16:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:43 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:43 Sent To  
Notes
2003-07-25 00:00:001) BUILDING ADDRESS AT LEAST 6" HIGH
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-11-21 Time 14:35 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 14:35 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 14:14 Sent To  
Notes
2003-09-08 00:00:00ON COMM BD#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 09:27 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 09:27 Sent To  
Notes
2003-08-22 00:00:00TO COMM BD #5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 13:57 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 13:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 12:17 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 12:17 Sent To B
Notes
2003-08-14 00:00:00TO HPISCURA DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 16:36 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 16:36 Sent To  
Notes
2003-07-18 00:00:00COMM BOARD #7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 10:58 Rev Time 0.33
Received By pkrauss Date 2003-12-02 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-11-21 Time 14:36 Rev Time 0.40
Received By pkrauss Date 2003-08-28 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-11 Cont ID  
Sent By pkrauss Date 2003-08-11 Time 13:13 Rev Time 0.30
Received By pkrauss Date 2003-08-11 Time 13:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-16 Cont ID  
Sent By kstevens Date 2003-09-16 Time 09:12 Rev Time 0.50
Received By kstevens Date 2003-09-16 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-06 Cont ID  
Sent By kstevens Date 2003-09-06 Time 20:19 Rev Time 0.25
Received By kstevens Date 2003-09-06 Time 20:19 Sent To  
Notes
2003-09-06 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 FROM PREVIOUS REVIEW, SEE ATTACHED SHEET
 CONCERNING 61G1-16.003. WHEN SEAL MAY BE
 AFFIXED. NO DATE SHOWN WHEN PLANS WERE
 SEALED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-08-07 Time 14:58 Rev Time 1.00
Received By kstevens Date 2003-08-07 Time 14:57 Sent To  
Notes
2003-08-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY AND WATER RISERS REQUIRED.
 (ONLY FIXTURES FROM THE BATHROOM GROUP
 TO DRAIN INTO THE HORIZONTAL BRANCH OF
 THE WET VENT. OTHER SINKS SHALL TIE IN
 DOWNSTREAM OF BATHROOM GROUP. 909.1)
 2) 61G1-16.003 DATE SHALL APPEAR ON ALL
 SHEETE WITH SEAL AND SIGNATURE. (SEE
 ATTACHED SHEET)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]