Plan Review Details - Permit 03071467
Plan Review Stops For Permit 03071467
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:47 Sent To  
Notes
2003-07-25 00:00:001) PROVIDE PRODUCT APPROVALS FOR TWO
 HOUR DUCT WRAP.
  
 2) PROVIDE SEPARATE PLAN AND PERMIT
 FOR FIRE SUPPRESSION SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:50 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 16:50 Sent To M
Notes
2003-12-17 00:00:00TO PK BOX/SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-22 Cont ID  
Sent By pkrauss Date 2003-12-22 Time 15:49 Rev Time 0.40
Received By pkrauss Date 2003-12-22 Time 15:49 Sent To  
Notes
2003-12-22 00:00:00DENIED:
 PLANS SHOULD REFLECT CHANGE TO DUCT AS
 REQUIRED PER COMMENT #1 FROM PLAN REVIEW
 DATED 8/9/03 (SEE ATTACHED).DUCT
 SHALL TERMINATE A MINUMIM OF 2 FT FROM
 PARAPET SO LONG AS THE PARAPET IS NOT
 HIGHER THAN THE TOP OF THE FAN
 DISCHARGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-09 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:50 Rev Time 0.45
Received By pkrauss Date 2003-08-09 Time 10:34 Sent To  
Notes
2003-08-09 00:00:00PROVISO:
  
 1.PLAN SHEET 2 SECTION VIEW OF THE
 HOOD, EXHAUST FAN TERMINATION SHALL
 COMPLY WITH 2001 FBC(M) 506.3.14.3
 EXCEPTION #2, THE MINIMUM HORIZONTAL
 DISTANCE BETWEEN VERTICAL DISCHARGE FANS
 AND PARAPET-TYPE BUILDING STRUCTURES
 SHALL BE TWO FEET PROVIDED THAT SUCH
 STRUCTURES ARE NOT HIGHER THAN THE TOP
 OF THE FAN DISCHARGE OPENING.
  
 2.PROVIDE INSTALLATION INSTRCTIONS FOR
 THE 2 HR FIRE WRAP ON THE JOBSITE AT THE
 TIME OF INSPECTION.
  
 3.ADDITIONAL PLANS AND PERMIT REQUIRED
 FOR THE FIRE SUPPRESSION.
  
 4.ADDITIONAL PERMIT REQUIRED SHOULD
 THE WALK-IN COOLER BE NEW.PLEASE
 PROVIDE MANUFACTURER CUT SHEETS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.