Plan Review Details - Permit 03071461
Plan Review Stops For Permit 03071461
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-03 Cont ID  
Sent By hpiskura Date 2003-09-03 Time 07:15 Rev Time 0.00
Received By hpiskura Date 2003-09-03 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By hpiskura Date 2003-08-07 Time 10:30 Rev Time 0.00
Received By hpiskura Date 2003-08-07 Time 10:30 Sent To  
Notes
2003-08-07 00:00:00TWO INDEPENDENT MEANS OF EGRESS ARE
 REQUIRED BY FBC 1004.2 AND EGRESS
 THROUGH KITCHENS IS PROHIBITTED BY FBC
 1001.1.3.SEE ALSO FBC 1012.
  
 PLEASE REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By dpalmer Date 2003-09-02 Time 20:00 Rev Time 0.33
Received By dpalmer Date 2003-09-02 Time 20:00 Sent To  
Notes
2003-09-02 00:00:00OK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 07:52 Rev Time 0.50
Received By dpalmer Date 2003-07-22 Time 07:52 Sent To  
Notes
2003-07-22 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G15-23.002 FOR REQ'D INFORMATION
 ON TITLE BLOCK FOR METRO DESIGN GROUP.
  
 2)NOTE: PLEASE SEE ANY OTHER COMMENTS
 FROM OTHER REVIEWERS THAT MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 16:38 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:44 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:44 Sent To  
Notes
2003-07-25 00:00:001) PLAN INDICATES IA SEATING CAPACITY
 OF 50 PERSONS. FRONT DOOR SWINGS
 INWARD. EXIT DOORS SUBJECT TO 50 OR
 MORE PERSONS SHALL SWING IN THE
 DIRECTION OF EXIT TRAVEL. RE: NFPA 101,
 SECTION 7.2.1.4.2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 16:08 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 16:08 Sent To P
Notes
2003-09-15 00:00:00TO KS DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 10:15 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 10:15 Sent To  
Notes
2003-08-27 00:00:00TO COMM BD#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-21 Time 10:14 Rev Time 0.00
Received By shernand Date 2003-07-21 Time 10:10 Sent To  
Notes
2003-07-21 00:00:00COMM BD# 1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-08-09 Cont ID  
Sent By pkrauss Date 2003-08-09 Time 11:49 Rev Time 0.10
Received By pkrauss Date 2003-08-09 Time 11:49 Sent To  
Notes
2003-08-09 00:00:00NO HVAC PLANS SUBMITTED FOR REVIEW.
 SEE PROVISO FOR HOOD ON PERMIT 03071467

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-22 Cont ID  
Sent By kstevens Date 2003-09-22 Time 14:23 Rev Time 1.25
Received By kstevens Date 2003-09-22 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-13 Cont ID  
Sent By csiegber Date 2003-09-15 Time 16:08 Rev Time 1.00
Received By kstevens Date 2003-09-13 Time 13:18 Sent To  
Notes
2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA STATUTES
  
 1) SHT 3 FLOOR SINK UNDER 6-BURNER WITH
 OVEN. INDICATE WHAT DRAINS INTO THIS
 FLOOR SINK. IF IT IS A FLOOR DRAIN IT
 SHALL BE LOCATED WHERE IT CAN BE SERV-
 ICED. 412.2
 2) COVER SHEET STILL SHOWS A DEMO PLAN
 D-1. THIS SHEET STILL NOT FOUND. PLEASE
 CLAIRFY. 104.2.1
 3) SHOW ALL PIPE SIZES FOR GAS LINES.
 NOT ADDRESSED FROM PREVIOUS REVIEW.
 4) ALL GAS APPLIANCE MANUFACTURE SHEETS
 NOT SUBMITTED. RICE COOKERS NOT SUBMITT-
 ED. FRYERS MANUF. SHEETS INDICATE 105K
 BTU, BUT RISER SHOWS 90K. PLEASE CLAIRFY
 CHARBROILER - RISER SHOWS 120K BTU, GAS
 CALCULATION CHART SHOWS 90K BTU, AND
 MANUF. INFORMATION INDIACATES 60K BTU'S
 PLEASE CLAIRFY. 6 BURNER W/OVEN ON RISER
 SHOWS 270K BTU, GAS CALCULATION CHART
 SHOWS 203K BTU, MANUF. INFORMATION DOES
 NOT CALL OUT WHICH MODEL IS BEING USED.
 PLEASE CLAIRFY.
 5) PLUMBING PERMIT REQUIRED.
 6) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-08-07 Time 12:26 Rev Time 1.50
Received By kstevens Date 2003-08-07 Time 12:26 Sent To  
Notes
2003-08-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT 3 FLOOR SINKS AT 6-BURNER W/OVEN
 SHALL DRAIN TO GREASE LINE.
 2) COVER SHEET SHOWS DEMO PLAN D-1 BUT
 THIS SHEET NOT FOUND. PLEASE CLAIRFY.
 3) ALL CAPPED AND DEMO'ED PIPING SHALL
 BE INSPECTED PRIOR TO COVERING.
 4) SEPARATE GAS PERMIT REQUIRED.
 5) SHOW ALL PIPE SIZES FOR GAS LINES.
 6) TYPE OF GAS, (LP OR NATURAL)
 7) INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 9) GAS RISER DIAGRAM SHOWS 76,000 BTU'S
 FOR WATER HEATER, BUT GAS CALCULATION
 CHART SHOW 160,000. PLEASE CLAIRFY.
 10) 61G15-23.002(2) CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]