| Plan Review Stops For Permit 03071461 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-09-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-09-03 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-09-03 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-08-07 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-08-07 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-08-07 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2003-08-07 00:00:00 | TWO INDEPENDENT MEANS OF EGRESS ARE | | | REQUIRED BY FBC 1004.2 AND EGRESS | | | THROUGH KITCHENS IS PROHIBITTED BY FBC | | | 1001.1.3.SEE ALSO FBC 1012. | | | | | | PLEASE REVISE AS NECESSARY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-02 |
Time |
20:00 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-09-02 |
Time |
20:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-07-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-22 |
Time |
07:52 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-07-22 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2003-07-22 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF | | | FAC 61G15-23.002 FOR REQ'D INFORMATION | | | ON TITLE BLOCK FOR METRO DESIGN GROUP. | | | | | | 2)NOTE: PLEASE SEE ANY OTHER COMMENTS | | | FROM OTHER REVIEWERS THAT MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-09-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-04 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-04 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-25 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-25 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2003-07-25 00:00:00 | 1) PLAN INDICATES IA SEATING CAPACITY | | | OF 50 PERSONS. FRONT DOOR SWINGS | | | INWARD. EXIT DOORS SUBJECT TO 50 OR | | | MORE PERSONS SHALL SWING IN THE | | | DIRECTION OF EXIT TRAVEL. RE: NFPA 101, | | | SECTION 7.2.1.4.2. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-09-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-15 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-15 |
Time |
16:08 |
Sent To |
P |
|
| Notes |
| 2003-09-15 00:00:00 | TO KS DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-08-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-27 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-08-27 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2003-08-27 00:00:00 | TO COMM BD#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-21 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | COMM BD# 1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-08-09 |
Time |
11:49 |
Rev Time |
0.10 |
| Received By |
pkrauss |
Date |
2003-08-09 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2003-08-09 00:00:00 | NO HVAC PLANS SUBMITTED FOR REVIEW. | | | SEE PROVISO FOR HOOD ON PERMIT 03071467 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-09-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-22 |
Time |
14:23 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-09-22 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-09-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-15 |
Time |
16:08 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-09-13 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2003-09-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FLORIDA STATUTES | | | | | | 1) SHT 3 FLOOR SINK UNDER 6-BURNER WITH | | | OVEN. INDICATE WHAT DRAINS INTO THIS | | | FLOOR SINK. IF IT IS A FLOOR DRAIN IT | | | SHALL BE LOCATED WHERE IT CAN BE SERV- | | | ICED. 412.2 | | | 2) COVER SHEET STILL SHOWS A DEMO PLAN | | | D-1. THIS SHEET STILL NOT FOUND. PLEASE | | | CLAIRFY. 104.2.1 | | | 3) SHOW ALL PIPE SIZES FOR GAS LINES. | | | NOT ADDRESSED FROM PREVIOUS REVIEW. | | | 4) ALL GAS APPLIANCE MANUFACTURE SHEETS | | | NOT SUBMITTED. RICE COOKERS NOT SUBMITT- | | | ED. FRYERS MANUF. SHEETS INDICATE 105K | | | BTU, BUT RISER SHOWS 90K. PLEASE CLAIRFY | | | CHARBROILER - RISER SHOWS 120K BTU, GAS | | | CALCULATION CHART SHOWS 90K BTU, AND | | | MANUF. INFORMATION INDIACATES 60K BTU'S | | | PLEASE CLAIRFY. 6 BURNER W/OVEN ON RISER | | | SHOWS 270K BTU, GAS CALCULATION CHART | | | SHOWS 203K BTU, MANUF. INFORMATION DOES | | | NOT CALL OUT WHICH MODEL IS BEING USED. | | | PLEASE CLAIRFY. | | | 5) PLUMBING PERMIT REQUIRED. | | | 6) SEE ATTACHED SHEET CONCERNING FLORIDA | | | STATUTE 553.80(2)(B) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-08-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-08-07 |
Time |
12:26 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-08-07 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2003-08-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHT 3 FLOOR SINKS AT 6-BURNER W/OVEN | | | SHALL DRAIN TO GREASE LINE. | | | 2) COVER SHEET SHOWS DEMO PLAN D-1 BUT | | | THIS SHEET NOT FOUND. PLEASE CLAIRFY. | | | 3) ALL CAPPED AND DEMO'ED PIPING SHALL | | | BE INSPECTED PRIOR TO COVERING. | | | 4) SEPARATE GAS PERMIT REQUIRED. | | | 5) SHOW ALL PIPE SIZES FOR GAS LINES. | | | 6) TYPE OF GAS, (LP OR NATURAL) | | | 7) INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 8) SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | 9) GAS RISER DIAGRAM SHOWS 76,000 BTU'S | | | FOR WATER HEATER, BUT GAS CALCULATION | | | CHART SHOW 160,000. PLEASE CLAIRFY. | | | 10) 61G15-23.002(2) CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|