| 2003-08-11 00:00:00 | ******CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)TITLE BLOCK FOR THE ENGINEER IS |
| | REQUIRED TO BE ON THE PLAN; FAC61G15- |
| | 23.002. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)PROVIDE THE RECEIPT FOR THE IMPACT |
| | FEES. |
| | |
| | 4.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN - EXISTING, PROPOSED, NEW TOTAL. |
| | ADDITIONS OF GREATER THAN 25% ARE |
| | REQUIRED TO COMPLY WITH FBC3401.7.1.2. |
| | |
| | 5.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 6.)WHEN RESUBMITTING, SIGN THE |
| | OWNER/AGENT LINE OF THE ENERGY CALC |
| | FBC13-101.2. |
| | |
| | 7.)PROVIDE A ROOF FRAMING PLAN. |
| | |
| | 8.)FIREBLOCKING SHALL BE PROVIDED IN |
| | ALL WALLS AND PARTITIONS, FBC705.3. |
| | |
| | 9.)1 1/2" WATERSTOP REQUIRED, CITY OF |
| | WEST PALM BEACH AMENDMENTS TO THE FBC, |
| | 2111.1.9. |
| | |
| | 10.)THIS PROPERTY IS IN AN AREA OF |
| | QUESTIONABLE SOILS.PROVIDE A SOILS |
| | INVESTIGATION FOR THE PROPOSED ADDITION. |
| | HAVE THE STRUCTURAL ENGINEER CERTIFY |
| | THAT THE SLAB AND FOOTER ARE EXISTING AS |
| | DRAWN ON THE PLAN. |
| | |
| | 11.)ADDITIONAL FEES REQUIRED (VALUE |
| | ADJUSTMENT AND RADON). |
| | |
| | 12.)CLARIFY - TWO PRODUCT APPROVALS |
| | WERE SUBMITTED FOR HORIZONTAL ROLLERS; |
| | IMPACT AND NON IMPACT.THERE ARE ONLY |
| | TWO WINDOWS ON THE PLAN.IS ONE OF EACH |
| | TO BE INSTALLED? |
| | |
| | 13.)CLARIFY - TWO PRODUCT APPROVALS |
| | WERE SUBMITTED FOR THE SGDS.THE NON- |
| | IMPACT PRODUCT APPROVAL IS EXPIRED. |
| | WHAT ARE YOU INSTALLING? |
| | |
| | 14.)IF YOU ARE INSTALLING IMPACT GLASS |
| | HURRICANE SHUTTERS ARE NOT REQUIRED. |