Plan Review Details - Permit 03071240
Plan Review Stops For Permit 03071240
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-10-09 Cont ID  
Sent By sthyng Date 2003-10-09 Time 16:40 Rev Time 0.50
Received By sthyng Date 2003-10-09 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-10-07 Time 13:49 Rev Time 0.50
Received By sthyng Date 2003-09-23 Time 15:44 Sent To  
Notes
2003-09-23 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TITLE BLOCK REQUIRED FOR PAGES
 WHICH NOW HAVE AN ENGINEER'S SEAL.
 ALSO INCLUDE LICENSE NUMBER ON EACH
 SHEET.FAC61G15-23.002

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-23 Time 11:25 Rev Time 2.50
Received By sthyng Date 2003-09-16 Time 12:45 Sent To  
Notes
2003-09-16 00:00:00******CORRECTIONS******
  
 NOTE - AS PER CONVERSATION WITH OWNER,
 MOST SHEETS ON THE PLAN WERE
 INFORMATIONAL ONLY AND DO NOT REFLECT
 WORK TO BE PERFORMED.THIS IS A
 SFD, NOT A ROOMING HOUSE AS INDICATED
 ON THE PLAN.
  
 1.)THE PLANS PREPARED BY THE ENGINEER
 SHALL BE SEALED, SIGNED AND DATED.THE
 ENGINEER SHALL INCLUDE THEIR LICENSE
 NUMBER ON EACH SHEET, FAC61G15-23.002(1)
  
 2.)ROOF SHINGLE PRODUCT APPROVALS MAY
 BE SUBMITTED NOW OR WITH THE ROOF
 PERMIT APPLICATION.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)ZONING HAS DISAPPROVED THE PLANS.
 REVISE THE PLANS FOR ZONING RESUBMITTAL.
  
 5.)AS DISCUSSED, REMOVE THE PLUMBING
 PAGE FROM THE PLAN AS THERE IS NO
 PLUMBING WORK BEING PERFORMED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-06 Cont ID  
Sent By sthyng Date 2003-08-05 Time 14:23 Rev Time 8.00
Received By sthyng Date 2003-08-05 Time 13:46 Sent To  
Notes
2003-08-05 00:00:00*******CORRECTIONS*******
  
 NOTE - THIS PLAN HAS BEEN REVIEWED AS
 AN R1 BOARDING HOUSE.THE OWNER HAS
 INDICATED THAT HE IS CHANGING THIS TO
 AN R3 SINGLE FAMILY DWELLING.SOME OF
 THE COMMENTS WILL NOT APPLY TO AN R3
 OCCUPANCY.DISREGARD ANY COMMENTS
 WHICH DO NOT APPLY IF THIS IS
 RESUBMITTED AS AN R3.
  
 1.)EACH SHEET OF PLANS PREPARED BY
 THE ENGINEER SHALL BE SEALED, SIGNED
 AND DATED.THE ENGINEER SHALL INCLUDE
 THEIR LICENSE NUMBER ON EACH SHEET.
 FAC61G15-23.002(1); SEE ATTACHED.
  
 2.)ACCORDING TO THE PALM BEACH COUNTY
 PROPERTY APPRAISER, THE BUILDING VALUE
 IS $23,901.THIS REPAIR HAS A VALUE
 WHICH EXCEEDS 50% OF THE EXISTING; MUST
 COMPLY WITH FBC 3401.7.2.6.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)THIS JOB IS NOT COVERED BY FLORIDA
 STATUTE EXEMPTIONS FROM ARCHITECT
 LICENSURE.HAVE A LICENSED PROFESSIONAL
 PREPARE AND SEAL DRAWINGS; FS481.229.
  
 5.)BY FBC202 DEFINITION, A "ROOMING
 HOUSE" CONTAINS NOT MORE THAN FIVE
 GUEST ROOMS.THIS BUILDING WOULD BE
 CONSIDERED R1, BOARDING HOUSE, FBC311.2.
 INDICATE THE CORRECT OCCUPANCY
 CLASSIFICATION ON THE PLAN.
  
 6.)THE SCOPE OF WORK IS NOT CLEAR.
 HAVE THE PLAN INDICATE THE SCOPE OF
 WORK, TO BE CONSISTENT WITH THE PERMIT
 APPLICATION.FOR EXAMPLE, THE ELEVATION
 SHOWS A SHINGLE ROOF, BUT NO WORK TO BE
 DONE TO THE ROOF.APPLICATION SHOWS
 ROOF REPAIR.A FLOOR PLAN IS SHOWN; IS
 EVERYTHING EXISTING?
  
 7.)PROVIDE A HAND RAIL DETAIL; COMPLY
 WITH FBC 1007.5.
  
 8.)PROVIDE A DETAIL FOR THE CONCRETE
 STEPS, REAR EXIT DOOR, 1ST FLOOR.SHOW
 ALL DIMENSIONS, INCLUDING THE LANDING.
 STAIRS ARE REQUIRED TO HAVE HANDRAILS,
 FBC 1007.5.
  
 9.)PROVIDE A DETAIL FOR THE EXTERIOR
 STAIR, SHOWING ALL DIMENSIONS, INCLUDING
 THE LANDINGS.
  
 10.)PROVIDE A GUARD RAIL DETAIL FOR
 THE EXTERIOR STAIR LANDING; FBC1015,
 FBC1608.2.2.
  
 11.)FIREBLOCKING REQUIRED AT STAIRS
 FOR WOOD CONTRUCTION; FBC2305.1.4.
  
 12.)DRAFTSTOPPING REQUIRED; PROVIDE A
 SCHEDULE, FBC705.3.
  
 13.)FIRESTOP REQUIRED FOR WALLS; FBC
 705.3.
  
 14.)THE STAIR RAILING IS TO COMPLY
 WITH FBC1608.2.1.
  
 15.) PROVIDE A STRUCTURAL DETAIL FOR THE
 STAIRS.THERE IS A STAIR DETAIL BUT IT
 IS NOT CLEAR AS TO WHETHER THEY ARE
 EXISTING OR BEING REBUILT.
  
 14.) SLEEPING ROOMS ARE REQUIRED TO
 HAVE EMERGENCY EGRESS FBC1005.4; SHOW
 COMPLIANCE.
  
 15.)WINDOWS AT THE BATHTUBS ARE TO
 BE SAFETY GLASS, FBC2405.
  
 16.)THE NOTES STATE THAT THE EXISTING
 WINDOWS ARE IMPACT WITH PRODUCT
 APPROVALS.IS THIS CORRECT?HISTORIC
 MADE A NOTE THAT WINDOWS ARE TO BE
 REPAIRED, NOT REPLACED.CORRECT THE
 NOTES TO REFLECT THE SCOPE OF WORK.
  
 17.) SHOW ATTIC ACCESS SIZE, FBC2309.6.
  
 18.) SEPARATE PERMITS REQUIRED.
  
 19.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 20.) SOFFIT VENTS TO COMPLY WITH FBC
 2309.7.
  
 21.) CRAWL SPACE VENTILATION REQUIRED,
 FBC1804.6.3.1.
  
 22.) IMPACT PROTECTION REQUIRED FOR
 WINDOWS; FBC1606.1.4.PROVIDE TWO
 COPIES OF PRODUCT APPROVALS AND A
 HURRICANE SHUTTER ATTACHMENT SCHEDULE
 (IF EXISTING WINDOWS ARE NOT IMPACT).
  
 23.) 1 HOUR TENANT SEPARATION REQUIRED;
 FBC704.3.SHOW ON THE FLOOR PLAN AND
 PROVIDE A DETAIL.
  
 24.)A 36" MINIMUM CORRIDOR WIDTH IS
 REQUIRED, FBC TABLE 1004.SHOW
 COMPLIANCE ON THE PLAN.
  
 25.)EXIT ACCESS CORRIDOR IS REQUIRED
 TO HAVE 1 HR FIRE RATING, FBC TABLE
 704.2.4.
  
 26.) OPENINGS IN EXIT ACCESS DOORS ARE
 REQUIRED TO HAVE A 20 MINUTE OPENING
 PROTECTIVE, FBC TABLE 705.1.2.
  
 27.) TWO EXITS REQUIRED; FBC1004.2.
 SHOW COMPLIANCE.
  
 28.) SMOKE DETECTOR REQUIRED IN CLOSE
 PROXIMITY TO THE STAIR, FBC905.2.2.
  
 29.) SMOKE DETECTORS REQUIRED IN
 CORRIDORS, FBC905.2.2.
  
 30.) PROVIDE A DETAIL FOR THE STAIRS
 AND FRONT PORCH, INCLUDING STAIR RAILS,
 GUARD RAILS, STAIRS; FBC 1007.5, FBC
 1015, FBC1012.1.3.
  
 31.) STAIRWAYS ARE REQUIRED TO HAVE
 HANDRAILS ON EACH SIDE, FBC1007.5.2.
  
 32.) INTERIOR FINISHES REQUIRED TO
 BE CLASS B FOR EXITS AND EXIT ACCESS;
 CLASS C FOR OTHER SPACES, FBC TABLE
 803.3.PROVIDE PRODUCT INFORMATION.
  
 33.) PROVIDE PRODUCT INFORMATION FOR
 DOORS REQUIRED TO BE FIRE RATED.
  
 34.)IF THE INTERIOR STAIRS WILL BE
 USED AS A MEANS OF EGRESS, SHOW
 COMPLIANCE WITH FBC1006 AND FBC1007.
  
 35.)EXTERIOR STAIRS SHALL COMPLY WITH
 FBC1006 AND FBC1007.
  
 36.)ALL CHANGES TO THE PLAN REQUIRE
 APPROVAL BY THE HISTORIC PRESERVATION
 DIVISION.
  
 37.) IF ROOF SHINGLES ARE TO BE
 INSTALLED, PRODUCT APPROVALS ARE
 REQUIRED.THEY MAY BE SUBMITTED NOW
 FOR REVIEW OR WITH THE ROOF PERMIT
 APPLICATION.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-09-16 Cont ID  
Sent By dpalmer Date 2003-09-16 Time 12:43 Rev Time 0.00
Received By dpalmer Date 2003-09-16 Time 12:43 Sent To  
Notes
2003-09-16 00:00:00NO ELECTRICAL WORK BEING DONE.
 BLDG REPAIRS ONLY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:16 Rev Time 1.00
Received By dpalmer Date 2003-07-23 Time 06:25 Sent To  
Notes
2003-07-23 00:00:00************** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 EM/EXT LTS PER 700.12E
  
 3)NOTE: PLEASE CLARIFY WHERE SWITCHING
 CONTROLS ARE FOR STAIR LIGHTING ON
 FIRST FLOOR. LIFE SAFETY 101 5-8
  
 4)NOTE: CIRCUITING FOR BATHS PER 210.11.
 C.3, 210.52D
  
 5)NOTE: PLEASE SEE MISSING SD`S INSIDE
 AND OUTSIDE ALL SLEEPING RMS. NFPA-72
 8-1.4.2
  
 6)NOTE: PLEASE SEE 210.52.C.1 FOR RECEPT
 SPACING ON KITCEHN COUNTERSPACE.
 GFI 210.8.A.6
  
 7)NOTE: PLEASE CLARIFY ILLUMINATION FROM
 SECOND FLOOR OUTSIDE EXITING. LS101 5-8
  
 8)NOTE: PLEASE SUBMIT LOAD CALCS AND
 SERVICE , NEW OR EXISTING?
  
 PLEASE NOTE, UNABLE TO DO A COMPLETE
 REVIEW AT THIS TIME. PLEASE SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2003-09-16 Cont ID  
Sent By sthyng Date 2003-09-16 Time 12:44 Rev Time 0.00
Received By sthyng Date 2003-09-16 Time 12:44 Sent To  
Notes
2003-09-16 00:00:00NOT A ROOMING HOUSE; SINGLE FAMILY HOME
 OK PER MC

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 09:15 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 09:15 Sent To  
Notes
2003-07-25 00:00:00FIRE RESCUE RECORDS INDICATE THAT THIS
 BUILDING WAS FORMERLY USED AS A
 ROOMING HOUSE. SINCE IT CAN BE
 CONSIDERED AN EXISTING ROOMING HOUSE
 NO FIRE SPRINKLER SYSTEM WILL BE
 REQUIRED.
  
 1) PLANS MAKE NO REFERENCE ABOUT THE
 EXISTING FIRE ALARM SYSTEM. THE
 EXISTING SYSTEM MUST BE REPLACED IF
 IT IS STILL THE 110 VOLT USED
 PREVIOUSLY. SEPARATE PLANS AND PERMITS
 REQUIRED. A FIRE ALARM SYSTEM IS
 REQUIRED FOR ROOMING HOUSES.
  
 2) THE EXISTING SMOKE DETECTORS IF
 ELECTRIC CONTAINED WITHIN THE
 SLEEPING ROOMS SHALL BE BROUGHT TO
 FULL WORKING ORDER.
  
 3) NO MENTION ABOUT SELF-CLOSING
 DEVICES ON SLEEPING ROOM DOORS.
  
 4) NO MENTION ABOUT PORTABLE FIRE
 EXTINGUISHERS.
  
 5) NO EMERGENCY LIGHTS SHOWN.
  
 6) DOORS ARE REQUIRED THAT PROVIDE AT
 LEAST A 30 MINUTE FIRE BARRIER ON THE
 INTERIOR STAIRS BOTH TOP AND BOTTOM.
 DOORS WERE PREVIOUSLY PRESENT AT THESE
 LOCATIONS.
  
 7) ALL WALLS SHALL BE SMOKE RESISTANT.
  
 8) NO INFORMATION CONCERNING INTERIOR
 FINISH FOR WALLS AND CEILINGS.
  
 9) BATHROOM AND CLOSET DOORS SHALL
 ALLOW ENTRY FROM THE OUTSIDE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-07 Time 13:49 Rev Time 0.00
Received By csiegber Date 2003-10-07 Time 13:49 Sent To B
Notes
2003-10-07 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 11:23 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 11:23 Sent To B
Notes
2003-09-23 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-19 Cont ID  
Sent By mmclean Date 2003-09-23 Time 08:29 Rev Time 0.00
Received By sthyng Date 2003-09-19 Time 14:40 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:16 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:16 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By mmclean Date 2003-09-23 Time 08:29 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-23 00:00:009/23/03 OK PER SHIRLEY GRAHAM MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By sthyng Date 2003-09-19 Time 14:40 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-07-31 00:00:00DENIED,
 THE ROOM HOUSE HAS BEEN CLOSED FOR MORE
 THAN SIX MONTHS, THE USE WAS LOST.


Account Summary | Usage Policy | Privacy Policy