Plan Review Details - Permit 03071035
Plan Review Stops For Permit 03071035
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-12-13 Cont ID  
Sent By shill Date 2004-12-13 Time 11:51 Rev Time 0.50
Received By shill Date 2004-12-13 Time 11:51 Sent To  
Notes
2004-12-13 00:00:00REVISED A2 DATED 8/22/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-13 Time 13:31 Rev Time 0.50
Received By shill Date 2004-10-13 Time 13:31 Sent To P
Notes
2004-10-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SUBMIT A SECOND COPY OF SHEET A2.
 ONLY ONE WAS SUBMITTED.THE OTHER SHEET
 MARKED "B" ON THE OUTSIDE IS AN ELECTRIC
 SHEET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 08:22 Rev Time 0.50
Received By shill Date 2004-04-12 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-03-26 Cont ID  
Sent By shill Date 2004-03-26 Time 13:54 Rev Time 0.00
Received By shill Date 2004-03-26 Time 13:54 Sent To  
Notes
2004-03-26 00:00:00NEED SEALED ORIGINAL ELEVATION
 CERTIFICATE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-25 Cont ID  
Sent By shill Date 2004-03-25 Time 14:00 Rev Time 2.00
Received By shill Date 2004-03-25 Time 13:23 Sent To  
Notes
2004-03-25 00:00:00**PROVISO**ELEVATION CERTIFICATE BEFORE
 ISSUANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-09 Cont ID  
Sent By kstevens Date 2004-03-22 Time 16:55 Rev Time 1.50
Received By shill Date 2003-12-09 Time 11:57 Sent To  
Notes
2003-12-09 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.4X FEE
 FOR PLUMBING AND ELECTRIC.
  
 2.)ADDITIONAL FEES DUE (VALUE
 ADJUSTMENT, 4X FEE, RADON), $5211.03.
 SEE ATTACHED.BZ231389
  
 3.)WHEN RESUBMITTING, SUBMIT ALL OLD
 PLANS PREVIOUSLY REVIEWED.
  
 4.)SEE PREVIOUS LIST, ITEM #8. ENERGY
 CALCS REQUIRED FBC13-103.1.2.MANUAL
 J ONLY SUBMITTED.
  
 5.)SOILS REPORT IS FOR THE POOL.
 SUBMIT TWO SEALED COPIES OF A SOILS
 REPORT FOR THE ADDITION.
  
 6.)BOTTOM CORD LIVE LOAD FOR THE
 TRUSSES SHOULD BE 10 FOR ATTICS WITHOUT
 STORAGE, 30 FOR ATTICS WITH STORAGE,
 FBC TABLE 1604.1.
  
 7.)PREVIOUS COMMENT #19 IN REGARDS TO
 THE FLOOD ZONE WA ADDRESSED BY AN
 ELEVATION CERTIFICATE SHOWING EXISTING
 TOP OF BOTTOM FLOOR AT 10'.SUBMIT
 A SEALED ELEVATION CERTIFICATE (COPY
 ONLY SUBMITTED).
  
 8.)IF THE HURRICANE SHUTTER
 INSTALLATION SCHEDULE IS NOT SUBMITTED,
 A SEPARATE PERMIT WILL BE REQUIRED FOR
 SHUTTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By pkrauss Date 2003-12-03 Time 12:33 Rev Time 4.00
Received By sthyng Date 2003-08-07 Time 12:37 Sent To  
Notes
2003-08-07 00:00:00******CORRECTIONS******
  
 1.)THERE ARE HOLDS ON THIS PROPERTY,
 SEE ATTACHED.
  
 2.)THE POOL IS TO BE PERMITTED
 SEPARATELY.REMOVE FROM THE PERMIT
 APPLICATION.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THE SITE PLAN SHOWS "ONE STORY
 RESIDENCE"; SHOULD SHOW EXISTING AND
 PROPOSED.
  
 5.)IS THE PRIVACY WALL A PART OF THIS
 PERMIT?IF IT IS, IINDICATE AS PROPOSED
 AND INCLUDE ON THE FOUNDATION PLAN.THE
 FOOTER CANNOT ENCROACH THE PROPERTY
 LINE.INCLUDE A DETAIL FOR THE WALL.
 IS THE NEW CONCRETE DRIVE A PART OF THIS
 PERMIT?INCLUDE ON THE APPLICATION.
  
 6.) PROVIDE AREA CALCULATIONS ON THE
 PLAN; INCLUDE EXISTING AND PROPOSED.
 ADDITIONS OVER 25% MUST COMPLY WITH
 FBC3401.7.1.2.1 AS AMENDED 7/1/03.
  
 7.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED, AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 8.)ENERGY CALCS REQUIRED FBC13-103.1.2
 SIGN THE OWNER/AGENT LINE AS WELL AS
 THE PREPARER LINE OF THE ENERGY CALC.
  
 9.)ADDITIONAL FEES ARE REQUIRED DUE
 TO VALUE ADJUSTMENT.ADDITIONAL FEES
 MAY BE ADDED AFTER THE SCOPE OF WORK
 IS DETERMINED.ADJUSTMENT WAS MADE FOR
 THE ADDITION ONLY; NO INTERIOR
 RENOVATIONS, DRIVEWAY, OR ENTRY WALL
 AND GATES.PROVIDE AN ESTIMATED VALUE
 FOR THESE ITEMS, PROVIDING CONTRACTS IF
 AVAILABLE.
  
 10.) WILL THE EXISTING FOOTER AND TIE
 BEAM TIE INTO THE EXISTING?IF NOT,
 NOTE ON THE PLAN.
  
 11.) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 ROOF TILE (MAY BE SUBMITTED WITH THE
 ROOF PERMIT APPLICATION)
 SINGLE HUNG WINDOW
 IMPACT PROTECTION FBC1606.1.4
 FRENCH DOORS
  
 12.) IF THE ROOF TILE IS FOAM SET (1-A1)
 PROVIDE PRODUCT APPROVALS FOR THE
 POLY FOAM.
  
 13.) CRAWL SPACE SHALL HAVE CROSS
 VENTILATION; SIZE TO CONFORM TO FBC
 1804.6.3.
  
 14.) WOOD FLOOR JOISTS TO BE OF
 NATURALLY DURABLE WOOD OR PRESSURE
 TREATED, FBC2304.3.4.
  
 15.) CHANGES DRAWN ON THE PLAN BY THE
 DESIGNER SHOULD BE INITIALED AND DATED.
  
 16.) SPECIFY A GIRDER CONNECTION ON
 THE ROOF FRAMING PLAN.
  
 17.) TRUSS ENGINEERING IS FOR 110 MPH
 WIND, SBCCI 97.THIS IS AN INCORRECT
 WIND AND CODE DESIGNATION, FBC FIGURE
 1606.
  
 18.) PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 19.) THIS PROPERTY IS IN A FLOOD ZONE.
 THE LOWEST FLOOR IS TO BE ELEVATED TO
 A MINIMUM OF 6" ABOVE THE BASE FLOOD
 ELEVATION; INDICATE ON THE PLAN, CITY
 OF WEST PALM BEACH MUNICIPAL CODE.
  
 20.) SUBMIT A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE, SEE ATTACHED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 14:20 Rev Time 0.60
Received By dpalmer Date 2005-10-08 Time 14:12 Sent To  
Notes
2005-10-08 00:00:00********* UNSAT ***********
  
 PLEASE SEE THERE ARE ITEMS NOT CORRECT
 FROM REDLINED PLANS IN SEPT 04.
  
 1)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR TO BE SIZED PER
 250.66 1/0 MIN.
  
 2)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS STILL BEING SHOWN FOR RECEPTS ONLY.
 210.12 2002 PLANS SUBMITTED FOR PERMIT
 AFTER JULY 1ST, 2003 WHEN CODE CHANGED
 TO 2002 NEC.
  
 3)NOTE: PLEASE SEE MISSING SD'S REQUIRED
 IN EXISTING DWELLING INSIDE AND OUTSIDE
 ALL SLEEPING RMS. NFAP-72 8-1.4.2
 CHAPTER 34 FBC.
  
 4)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 BATHRM IN NEW ADDTION IS REQUIRED TO
 INDICATE GFI RECEPT. 210.8
  
 5)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPTS
 REQUIRED ALONG KTICHEN COUNTERSPACE.
 210.52C1,210.8A6
  
 7)NOTE: PLEASE CORRELATE AND COMPLETE
 RISER DIAGRAM FOR CODE COMPLIANCE.
 PLEASE SHOW ALL CONDUCTORS.
 PLEASE SEE ONLY ONE 2/0 FOR 200A PANEL.
 PLEASE SEE CONDUCTOS FOR PANEL "C" ARE
 SHOWN AS 3/0'S FOR 100A OCP AND IN 1 1/4
 PIPE. PLEASE SEE MIN SIZE REQUIRED FOR
 CONDUCTORS TO BE CALCULATED FROMNEC
 TABLES.
 PLEASE SEE FEEDERS INDICATE ON PANEL "B"
 TO FEED PANEL "C" DO NOT MEET CODE
 COMPLIANCE. 240.4,310.16
  
 8)NOTE: PLEASE SEE"HOT TUB" IS BEING
 SHOWN ON PANEL SCHEDULE, HOWEVER PLANS
 DO NOT SHOW THIS??
 PLEASEALSO SEE PANEL SCHEDULE SHOWS
 300A OCP?? ON #6??
 215.5,240.4,310.16 ETC.
  
 9)NOTE: PLEASE SHOW ALL EXISTING
 DWELLING ELECTRICAL AS EITHER EXISTING
 MEETING 2002 NEC OR NEW TO BE BROUGHT UP
 TO CODE.
 FBC CHAPTER 34 ADDITIONS AND REMODELING
 EXISTING.
 THIS WAS REDLINED ON PLANS FROM SEPT 04.
 PLEASE SEE PLANS REFERENCE 2001??
 2002 NEC IS CODE IN EFFECT.
  
 10)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED CIRCUIT(S) FOR BATH(S).
 210.52D,210.11C3, MUST BE 20A AND #12.
  
 11)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110,250.122
 250.24 ETC.
  
 12)NOTE: PLEASE INCLUDE NEW OR EXISTING
 SEC'S WHICH MEETS THE 350A SERVICE
 SHOWN.
 PLEASE INLCUDE SIZE OF RISER.
 310.15B6,310.16, 240.4, 215.5 ETC.
  
 13)NOTE: PLEASE SEE SWITCHES NOT SHOWN
 AS 3-WAYS, WHEN WIRING ON PLANS SHOULD
 INDICATE THIS.
  
 14)NOTE: PLEASE SEE NUMEROUS BRKRS ON
 PANEL SCHEDULES WHICH DO NOT SEEM TO
 CORRELATE WITH AWG SHOWN.
 30A OCP, #6, 15A, #12
  
 15)NOTE: PLEASE SEE MISSING FRONT GFI
 210.52E
  
 16)NOTE: PLEASE SEE MISSING EGRESS LT??
 FRONT DOOR. 210.70
 PLEASE SEE GFI REQUIRED IN GARAGE.
 210.52G, 210.8
  
 17)NOTE: PLEASE SEE A GFI CIRCUIT IS
 BEING SHOWN AS "OPT" ON PANEL SCHEDULE??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 06:44 Rev Time 0.33
Received By dpalmer Date 2004-09-24 Time 06:34 Sent To M
Notes
2004-09-24 00:00:00*** NOTES FROM FIRST TWO REVIEWS**
  
 PLEASE SEE RISER HAS NOW BEEN REVISED.
  
 SIZE OF GROUNDING ELECTRODE CONDUCTOR
 TO BE PER 250.66.#2
  
 EXISITNG TO MEET 2002 NEC AS REQUIRED
 PER FBC CHAPTER 34 3407.7.1
  
 SD'S PER NFPA-72 8-1.4.1.6.2
 GFI'S

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-09-20 Time 13:51 Rev Time 0.50
Received By btrobaug Date 2004-03-22 Time 07:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-07 Cont ID  
Sent By shill Date 2004-03-15 Time 11:30 Rev Time 1.00
Received By dpalmer Date 2003-11-07 Time 13:01 Sent To P
Notes
2003-11-07 00:00:00************ UNSAT **************
  
 PLEASE SEE THAT SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE 2002 NEC, ARC FAULT
 PROTECTION IS NO LONGER JUST FOR RECEPTS
 PLEASE SEE 210.12. PLEASE LIST ON PANEL
  
 SCHEDULE.
 2)NOTE: PLEASE SEE RECEPT NEXT TO BAR
 SINK, GFI PER 210.8
  
 3)NOTE: PLEASE SHOW SERVICE ON PLANS,
 PLANS SHOW ONE PANEL IN GARAGE ONLY?
 PLEASE SEE RISER DIAGRAM.
 215.5
  
 4)NOTE: PLEASE SEE RISER SHOWS NEW
 PANEL BUT NOTHING ON HOW THIS PANEL IS
 BEING FED? CONDUCTORS, CONDUIT ETC ETC.
 PLANS SHOWS 150 A SERVICE AND 200A MAINS
 W/ 200A LOAD ETC? PLEASE CORRELATE
 PLANS AND RISER TO NEC. 230.42, 240,
 310.15B6ETC. 215.5
  
 5)NOTE: PLEASE SEE AHU#2, SHOWS 10KW AND
 4.5 KW ETC. PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE PLANS REF 2001 NEC,
 WE ARE UNDER THE 2002 NEC.
  
 7)NOTE: PLEASE SEEOTHER OCP/BRKR
 SIZES ON PANEL SCHEDULE.
 PLEASE CORRELATE OCP/KW/ AWG.
 AHU'S PUMP' ETC.
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS,553.80.(2)(B).
  
 PLEASE REMOVE OLD SHEETS AND INSERT NEW
 SHEETS INTO COMPLETE STES FOR REVIEW AND
 STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-24 Cont ID  
Sent By csiegber Date 2003-11-06 Time 15:27 Rev Time 2.00
Received By dpalmer Date 2003-07-24 Time 09:07 Sent To P
Notes
2003-07-24 00:00:00****************UNSAT **************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF THE
 FAC 61G1-16.004 FOR REQ'D INFORMATION
 IN TITLE BLOCK.
  
 2)NOTE: PLEASE SEE 2001 FBC CHAPTER 34
 3401.7.1 PLEASE SHOW ALL EXSITINGS ROOMS
 BEING UPGRADED TO TODAYS NEC STANDARDS.
 RECEPTS, SWITCHES,LTS , WIRING ETC ETC.
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING
 FOR NEW SERVICE EQUIPMENT.
  
 4)NOTE: PLEASE CLARIFY HOW MANY A/C
 SYSTEMS THERE ARE? SHOWS A AHU IN NEW
 ADDTION, BUT NOTHING SHOWN FOR DISC?
 440.11 AND LOAD CALCS?220
  
 5)NOTE: PLANS MENTION BEDROOM RECEPTS TO
 BE ARC FAULT TYPE. PLEASE LIST ALL THE
 REQ'D ARC FAULT PROTECTED CIRCUIT ON
 PANEL SCHEDULE INCLUDING ALL EXISTING
 BEDRROMS. 210.12
 AN ARC FAULT RECEPT IS NOT AVAILABLE
 AT THIS TIME.
  
 6)NOTE: PLEASE SHOW RECEPT NEXT TO BAR
 SINK AS GFI ALSO. 210.8
  
 7)NOTE: PLEASE SHOW SERVICE LOCATION
 /PANEL/ METER ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 15:27 Sent To E
Notes
2005-10-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-02 Cont ID  
Sent By csiegber Date 2004-11-02 Time 12:49 Rev Time 0.00
Received By csiegber Date 2004-11-02 Time 12:47 Sent To M
Notes
2004-11-02 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 13:50 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 13:50 Sent To E
Notes
2004-09-20 00:00:00TO COMM BD#
 TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-15 Cont ID  
Sent By shill Date 2004-03-15 Time 11:30 Rev Time 0.00
Received By shill Date 2004-03-15 Time 11:29 Sent To E
Notes
2004-03-15 00:00:00REMOVED FROM BOARD, TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-02 Time 11:09 Rev Time 0.00
Received By csiegber Date 2004-03-02 Time 11:09 Sent To  
Notes
2004-03-02 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 15:27 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 15:27 Sent To E
Notes
2003-11-06 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-21 Time 16:51 Rev Time 0.00
Received By shernand Date 2003-07-21 Time 16:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-15 Cont ID  
Sent By mmclean Date 2003-07-21 Time 10:11 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 14:08 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-11-22 Cont ID  
Sent By pkrauss Date 2004-11-22 Time 17:43 Rev Time 0.35
Received By pkrauss Date 2004-11-22 Time 17:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-10-07 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 07:53 Rev Time 0.35
Received By pkrauss Date 2004-10-07 Time 07:42 Sent To B
Notes
2004-10-07 00:00:00DENIED:
 1.PLEASE PROVIDE DUCT SIZE FOR ALL
 NEW DUCTWORK INDICATED ON THE PLAN.
  
 2.PLANS WERE SUBMITTED WITH A TITLE
 BLOCK AND SHALL BE SIGNED SEALED AND
 DATED BY THE ARCHITECT PER FS 481.221
 & FAC 61G1-16.001 THROUGH .004.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-03 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 06:44 Rev Time 0.33
Received By pkrauss Date 2003-12-03 Time 10:06 Sent To B
Notes
2003-12-03 00:00:00PROVISO:
 PER 2001 FBC(M) 601.4 - PLEASE SEE
 ATTACHED FOR PROPER SIZING OF THE RETURN
 AIR JUMPERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-25 Cont ID  
Sent By kstevens Date 2003-11-20 Time 07:51 Rev Time 0.15
Received By pkrauss Date 2003-07-25 Time 15:23 Sent To B
Notes
2003-07-25 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE ENERGY AND
 MANUAL J CALCULATIONS WITH PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-10-14 Cont ID  
Sent By kstevens Date 2004-10-14 Time 07:53 Rev Time 0.50
Received By kstevens Date 2004-10-14 Time 07:53 Sent To  
Notes
2004-10-14 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FAC 61G1-16.003/FS481.2055 THE PERSONAL
 SEAL, SIGNATURE AND DATE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By shill Date 2004-10-13 Time 13:31 Rev Time 0.33
Received By kstevens Date 2004-03-22 Time 16:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-11-20 Cont ID  
Sent By btrobaug Date 2004-03-22 Time 10:50 Rev Time 0.33
Received By kstevens Date 2003-11-20 Time 07:51 Sent To M
Notes
2003-11-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN,
 NOR DOES IT MEET CODE REQUIREMENTS.
 THE BAR SINK IS NOT SHOWN ON THE SANT.
 RISER DIAGRAM. THE WASH MACHINE AND BAR
 SINK SHALL CONNECT DOWNSTREAM OF THE
 BATHROOM FIXTURES. 909.1. THE SHOWER AND
 BIDET ARE NOT VENTED. 901.2.1. THE BIDET
 REQUIRES A TRAP, 1002.1
 SEE ORIGINAL PLAN FOR RED LINE CORRECT-
 IONS GIVEN TO ASSIST IN SUBMITTING A
 SANT. RISER THAT REFLECTS FLOOR PLAN AND
 MEETS CODE REQUIREMENTS.
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 533.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-24 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 13:41 Rev Time 0.33
Received By kstevens Date 2003-07-24 Time 15:53 Sent To M
Notes
2003-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) ONLY THE FIXTURES WITH-IN THE BATH-
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES (BAR SINK/WASH MACH-
 INE) SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. SECTION 909.1 (SEE RED LINE
 CORRECTIONS ON RISER DIAGRAM).
  
 2) SEE ATTACHED SHEET CONCERNING SEALS
 AND PLANS. 61G1-16
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-15 Time 14:08 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***