| Plan Review Stops For Permit 03070923 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-09-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-09-16 |
Time |
15:42 |
Rev Time |
0.85 |
| Received By |
jwitmer |
Date |
2003-09-16 |
Time |
15:42 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-07-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-07-25 |
Time |
10:05 |
Rev Time |
2.25 |
| Received By |
jwitmer |
Date |
2003-07-25 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2003-07-25 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 03070923 | | | ADD: 606 N OLIVE AVENUE | | | CONT: ANDRIOFF CONSTRUCTION | | | TEL: (561)271-5750 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | | | | 1) 11-4.1.6(1)(K)(III) NOTHING IN THIS | | | SECTION SHALL BE CONSTRUED TO RELIEVE | | | THE OWNER OF ANY BUILDING TO PROVIDE | | | VERTICAL ACCESSIBILITY. A ELEVATOR MAY | | | NOT BE REQUIRED (K) (I) LESS THAN 3,000 | | | SQ. FT. BUT THE REQUIREMENT TO PROVIDE | | | SOME OTHER ACCEPTED MEANS OF VERTICAL | | | ACCESSIBILITY STILL EXIST. A RAMP, OR | | | AN APPROVED CHAIR LIFT. | | | | | | 2) EXTERIOR STAIR VS. WALL OPENINGS. | | | 1006.2.4 EXTERIOR STAIRS SHALL BE SEPER- | | | ATED FROM THE INTERIOR OF THE BUILDING | | | BY A WALL WITH A FIRE RESISTANCE RATING | | | OF NOT LESS THAN 1 HR. WITH FIXED OR | | | SEAL CLOSING OPENING PROTECTIVES AS | | | REQUIRED FOR ENCLOSED STAIRS. SEE | | | AFFIXEDDIAGRAM. THE EXISTING EXIT DOOR | | | WILL REQUIRE RATING AS WELL AS EXISTING | | | DOOR BELOW. | | | | | | 3) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED. MISSING REPORT: | | | A) WINDOWS | | | B) MULLIONS | | | C) NEW EXTERIOR DOORS IF NOT 1 HR RATED. | | | | | | 4) NEW AWNING UNDER SEPERATE PERMIT. | | | | | | 5)11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. SEE DOOR NUMBER10,12&13. | | | | | | 6) DOOR SCHEDULE INDICATES THE USE OF | | | NARROW DOORS, 11-4.13.5 DOORWAYS SHALL | | | HAVE A MINIMUM CLEAR OPENING OF 32" | | | WITH THE DOOR OPEN 90 DEGREES, MEASURED | | | BETWEEN THE FACE OF THE DOOR AND THE | | | OPPOSITE DOOR STOP. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-02 |
Time |
16:25 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-10-02 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-10 |
Time |
15:03 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-09-10 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2003-09-10 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR | | | -S, SHOWS AN EQUIPMENT GROUNDING | | | CONDUCTOR W/ SEC'S, PLEASE SEE 250.24 | | | EGC IS ONLY INSTALLED AFTER FIRST MEANS | | | OF DISC. | | | | | | 2)NOTE: PLEASE CLARIFY TWO WHAT APPEARS | | | TO BE EM LT ON SECOND LEVEL OUTSIDE? | | | PLEASE SEE THAT EGRESS LIGHTING IS NOW | | | SHOWN FOR STAIRS OUTSIDE, HOWEVER | | | SHOWS A SINGLE MEANS OF CONTROL FROM | | | SECOND FLOOR AREA? LIFE SAFETY CODE | | | WOULD REQUIRE EITHER AN AUTOMATED MEANS | | | OF CONTROL(TIMECLOCK,PHOTOCELL) OR | | | A MEANS OF CONTROL FROM FIRST FLOOR ANF | | | AT EACH END OF STAIRS. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RQATING FOR | | | ALL NEW EQUIPMENT. MAINS, BRKRS AND | | | PANELS ARE ALL TO BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. 110.9/215.5 | | | IT WAS NOTED ON THE BOTTOM OF PANEL | | | THAT AIC RATING FOR PANELS ARE 10,000 | | | PLEASE NOTE, ANY HANDWRITTEN CHANGES TO | | | PLANS, MUST BE DONE IN INK AND ALSO | | | MUST HAVE,,EACH CHANGE,, INITIALED, | | | DATED BY ARCH/ENGINEER OF RECORD. | | | PER FS'S 471, 481. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL.. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-07-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-22 |
Time |
12:19 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-07-22 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2003-07-22 00:00:00 | ********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | TWO NEW MAIN DISCS. 110.9 | | | | | | 2)NOTE: PLEASE PROVIDE SIZE OF EXISTING | | | CONDUCTORS IN GUTTER/METE. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE SIGN | | | CIRCUIT IS. PANEL SCHEDULE SHOWS REQ'D | | | CIRCUIT BUT NOT SHOWN ON PLANS. | | | | | | 4)NOTE: PLEASE SHOW "SHOW WINDOW" RECEPT | | | -S REQ'D PER 210.62 | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 230.42/215.3 | | | | | | 6)NOTE: PLEASE CLARIFY WATER HEATER ON | | | PANEL "A"/ SHOWN AS 1-POLE AND KW LOAD | | | IS SHOWN FOR A&B PHASE AS A 220V UNIT? | | | | | | 7)NOTE: PLEASE CLARIFY WHERE THE REQ'D | | | MEANS OF EGRESS LIGHTING IS FOR STAIRS? | | | TO SECOND FLOOR. LS 101 CHAP 5-8 | | | | | | 8)NOTE: PLEASE CLARIFY METHOD OF EQUIP-- | | | -MENT GROUNDING BETWEEN MAIN DSIC'S AND | | | PANELS A/B. 250.110/ 250.122 | | | | | | 9)NOTE: PLEASE SEE THAT LOAD CALCS ARE | | | TO BE SHOWN PER 220.3,220.10,220.11, | | | 220.13 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-10 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-10 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-23 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-23 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2003-07-23 00:00:00 | 1) DEMOLITION PLAN FIRST FLOOR INDICATES | | | "THESE STAIRS TO BE DEMOLISHED". OTHER | | | DRAWINGS INDICATE TWO STAIRS IN | | | DIFFERENT DIRECTIONS AFTER LEAVING | | | THE LANDING. PLEASE CLARIFY. IF ONLY | | | ONE SET OF STAIRS REMAIN, PLEASE SEE | | | PROTECTION OF OUTSIDE STAIRS. | | | | | | 2) BUILDING ADDRESS REQUIRED ON PROPER | | | ELEVATION. | | | | | | 3) PLEASE INDICATE EMERGENCY LIGHT | | | FIXTURES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-01 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2003-10-01 00:00:00 | TO COMM BD#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-02 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-02 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2003-09-02 00:00:00 | TO COMM BD #7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-07-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-15 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-15 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2003-07-15 00:00:00 | COMM BOARD #5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-01 |
Time |
11:27 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-10-01 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-07-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-28 |
Time |
16:15 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-07-28 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2003-07-28 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET M-1 INDICATES A RETURN | | | AIR TRANSFER FROM THE BATHROOM AREA. PER | | | 2001 FBC(M) TABLE 403.3, 50 CFM OF | | | EXHAUST PER WATER CLOSET OR URNIAL IS | | | REQUIRED FOR A BATHROOM.THIS SHALL NOT | | | BE RE-CIRCULATED. | | | | | | 2.RETURN/TRANSFER AIR DUCTS ARE NOT | | | SIZED. | | | | | | 3.NOTE 9 UNDER THE SPECFICATIONS | | | INDICATES THE CONDENSATE CAN TERMINATE | | | INTO THE SANITARY.PER CITY CODE SEC. | | | 90-125 (B) (5), CONDENSATE SHALL NOT | | | DISCHARGE INTO THE THE WASTE WATER | | | FACILTY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-02 |
Time |
17:09 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-02 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-30 |
Time |
18:06 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-09-30 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2003-09-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTPER 1 | | | | | | 1) SECTION 1503.4.4 CONDENSATE SHALL | | | DISCHARGE AT LEAST 1 FOOT FROM THE | | | STRUCTURE SIDE WALL. SHOW DETAIL. | | | 2) SHT P1 W/HEATER EMERGENCY PAN DRAIN | | | SHALL BE CPVC. | | | 3) FROM PREVIOUS REVIEW. SHOW P/T LINE | | | PROVIDE AN ISOMETRIC AND INDICATE THE | | | TERMINATION POINT FOR BOTH WATER HEATERS | | | ALSO PROVIDE AN ISOMETRIC FOR THE PAN | | | DRAIN WATER HEATER ON THE SECOND FLOOR. | | | SHOW TERMINATION POINT FOR PAN DRAIN. | | | SECTION 104.2.1 | | | 4) FROM PREVIOUS REVIEW. THERMAL EXPAN- | | | SION CONTROL REQUIRED, 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-07-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-26 |
Time |
12:34 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-07-26 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2003-07-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | CITY WPB CODE | | | | | | 1) SHT P1 DWV ISOMETRIC, CONDENSATE | | | SHALL DRAIN SEPARATELY FROM THE BLDG. TO | | | STORM, CATCH BASIN, OR DRYWELL NOT INTO | | | SANITARY PER SECTION 90-125(B)(5). | | | SUBMIT RISER AND DETAILS. | | | 2) SHT P1 DWV ISOMETRIC, WATER COOLER IS | | | NOT VENTED. - NO HORIZONTAL DRY VENTS | | | SECTION 905.3 | | | 3) SHT P1 PLUMBING SPECIFICATIONS #4 AND | | | WATER SUPPLY ISOMETRIC, AIR CHAMBERS ARE | | | NOT APPROVED. DELETE FROM REFERENCE & | | | ISOMETRIC. 604.9 | | | 4) SHT P1 WATER HEATER, EMERGENCY PAN | | | DRAIN IS REQUIRED. 504.8-INDICATE | | | WHAT WILL HAPPEN TO THE RELIEF VALVE | | | (T/P) DISCHARGE. SUBMIT DETAIL FOR PAN | | | DRAIN LINE AND RELIEF VALVE DISCHARGE | | | LINE. SHOW PIPE SIZE, MATERIAL, AND | | | TERMINATION POINT FOR BOTH SYSTEMS. | | | 5) THERMAL EXPANSION CONTROL REQUIRED | | | SECTION 607.3.2 | | | 6) RPZ BACKFLOW REQUIRED. SECTION 608.13 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-09-25 |
|
|
Cont ID |
|
| Sent By |
dlittle |
Date |
2003-09-25 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
dlittle |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|