Plan Review Details - Permit 03070923
Plan Review Stops For Permit 03070923
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-16 Cont ID  
Sent By jwitmer Date 2003-09-16 Time 15:42 Rev Time 0.85
Received By jwitmer Date 2003-09-16 Time 15:42 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By jwitmer Date 2003-07-25 Time 10:05 Rev Time 2.25
Received By jwitmer Date 2003-07-25 Time 10:04 Sent To  
Notes
2003-07-25 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03070923
 ADD: 606 N OLIVE AVENUE
 CONT: ANDRIOFF CONSTRUCTION
 TEL: (561)271-5750
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 11-4.1.6(1)(K)(III) NOTHING IN THIS
 SECTION SHALL BE CONSTRUED TO RELIEVE
 THE OWNER OF ANY BUILDING TO PROVIDE
 VERTICAL ACCESSIBILITY. A ELEVATOR MAY
 NOT BE REQUIRED (K) (I) LESS THAN 3,000
 SQ. FT. BUT THE REQUIREMENT TO PROVIDE
 SOME OTHER ACCEPTED MEANS OF VERTICAL
 ACCESSIBILITY STILL EXIST. A RAMP, OR
 AN APPROVED CHAIR LIFT.
  
 2) EXTERIOR STAIR VS. WALL OPENINGS.
 1006.2.4 EXTERIOR STAIRS SHALL BE SEPER-
 ATED FROM THE INTERIOR OF THE BUILDING
 BY A WALL WITH A FIRE RESISTANCE RATING
 OF NOT LESS THAN 1 HR. WITH FIXED OR
 SEAL CLOSING OPENING PROTECTIVES AS
 REQUIRED FOR ENCLOSED STAIRS. SEE
 AFFIXEDDIAGRAM. THE EXISTING EXIT DOOR
 WILL REQUIRE RATING AS WELL AS EXISTING
 DOOR BELOW.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) WINDOWS
 B) MULLIONS
 C) NEW EXTERIOR DOORS IF NOT 1 HR RATED.
  
 4) NEW AWNING UNDER SEPERATE PERMIT.
  
 5)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. SEE DOOR NUMBER10,12&13.
  
 6) DOOR SCHEDULE INDICATES THE USE OF
 NARROW DOORS, 11-4.13.5 DOORWAYS SHALL
 HAVE A MINIMUM CLEAR OPENING OF 32"
 WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE DOOR STOP.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2003-10-02 Time 16:25 Rev Time 0.75
Received By dpalmer Date 2003-10-02 Time 16:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-09-10 Time 15:03 Rev Time 0.75
Received By dpalmer Date 2003-09-10 Time 15:03 Sent To  
Notes
2003-09-10 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR
 -S, SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR W/ SEC'S, PLEASE SEE 250.24
 EGC IS ONLY INSTALLED AFTER FIRST MEANS
 OF DISC.
  
 2)NOTE: PLEASE CLARIFY TWO WHAT APPEARS
 TO BE EM LT ON SECOND LEVEL OUTSIDE?
 PLEASE SEE THAT EGRESS LIGHTING IS NOW
 SHOWN FOR STAIRS OUTSIDE, HOWEVER
 SHOWS A SINGLE MEANS OF CONTROL FROM
 SECOND FLOOR AREA? LIFE SAFETY CODE
 WOULD REQUIRE EITHER AN AUTOMATED MEANS
 OF CONTROL(TIMECLOCK,PHOTOCELL) OR
 A MEANS OF CONTROL FROM FIRST FLOOR ANF
 AT EACH END OF STAIRS.
  
 3)NOTE: PLEASE SUBMIT AIC RQATING FOR
 ALL NEW EQUIPMENT. MAINS, BRKRS AND
 PANELS ARE ALL TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110.9/215.5
 IT WAS NOTED ON THE BOTTOM OF PANEL
 THAT AIC RATING FOR PANELS ARE 10,000
 PLEASE NOTE, ANY HANDWRITTEN CHANGES TO
 PLANS, MUST BE DONE IN INK AND ALSO
 MUST HAVE,,EACH CHANGE,, INITIALED,
 DATED BY ARCH/ENGINEER OF RECORD.
 PER FS'S 471, 481.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL..
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 12:19 Rev Time 0.75
Received By dpalmer Date 2003-07-22 Time 12:19 Sent To  
Notes
2003-07-22 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 TWO NEW MAIN DISCS. 110.9
  
 2)NOTE: PLEASE PROVIDE SIZE OF EXISTING
 CONDUCTORS IN GUTTER/METE.
  
 3)NOTE: PLEASE CLARIFY WHERE SIGN
 CIRCUIT IS. PANEL SCHEDULE SHOWS REQ'D
 CIRCUIT BUT NOT SHOWN ON PLANS.
  
 4)NOTE: PLEASE SHOW "SHOW WINDOW" RECEPT
 -S REQ'D PER 210.62
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 230.42/215.3
  
 6)NOTE: PLEASE CLARIFY WATER HEATER ON
 PANEL "A"/ SHOWN AS 1-POLE AND KW LOAD
 IS SHOWN FOR A&B PHASE AS A 220V UNIT?
  
 7)NOTE: PLEASE CLARIFY WHERE THE REQ'D
 MEANS OF EGRESS LIGHTING IS FOR STAIRS?
 TO SECOND FLOOR. LS 101 CHAP 5-8
  
 8)NOTE: PLEASE CLARIFY METHOD OF EQUIP--
 -MENT GROUNDING BETWEEN MAIN DSIC'S AND
 PANELS A/B. 250.110/ 250.122
  
 9)NOTE: PLEASE SEE THAT LOAD CALCS ARE
 TO BE SHOWN PER 220.3,220.10,220.11,
 220.13 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-10 Cont ID  
Sent By mcarsill Date 2003-09-10 Time 15:59 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By mcarsill Date 2003-07-23 Time 17:06 Rev Time 0.00
Received By mcarsill Date 2003-07-23 Time 17:06 Sent To  
Notes
2003-07-23 00:00:001) DEMOLITION PLAN FIRST FLOOR INDICATES
 "THESE STAIRS TO BE DEMOLISHED". OTHER
 DRAWINGS INDICATE TWO STAIRS IN
 DIFFERENT DIRECTIONS AFTER LEAVING
 THE LANDING. PLEASE CLARIFY. IF ONLY
 ONE SET OF STAIRS REMAIN, PLEASE SEE
 PROTECTION OF OUTSIDE STAIRS.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) PLEASE INDICATE EMERGENCY LIGHT
 FIXTURES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-01 Cont ID  
Sent By csiegber Date 2003-10-01 Time 14:50 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 14:50 Sent To  
Notes
2003-10-01 00:00:00TO COMM BD#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By csiegber Date 2003-09-02 Time 14:16 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 14:15 Sent To  
Notes
2003-09-02 00:00:00TO COMM BD #7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 08:06 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 08:06 Sent To  
Notes
2003-07-15 00:00:00COMM BOARD #5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 11:27 Rev Time 0.40
Received By pkrauss Date 2003-10-01 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-28 Cont ID  
Sent By pkrauss Date 2003-07-28 Time 16:15 Rev Time 0.45
Received By pkrauss Date 2003-07-28 Time 16:15 Sent To  
Notes
2003-07-28 00:00:00DENIED:
  
 1.PLAN SHEET M-1 INDICATES A RETURN
 AIR TRANSFER FROM THE BATHROOM AREA. PER
 2001 FBC(M) TABLE 403.3, 50 CFM OF
 EXHAUST PER WATER CLOSET OR URNIAL IS
 REQUIRED FOR A BATHROOM.THIS SHALL NOT
 BE RE-CIRCULATED.
  
 2.RETURN/TRANSFER AIR DUCTS ARE NOT
 SIZED.
  
 3.NOTE 9 UNDER THE SPECFICATIONS
 INDICATES THE CONDENSATE CAN TERMINATE
 INTO THE SANITARY.PER CITY CODE SEC.
 90-125 (B) (5), CONDENSATE SHALL NOT
 DISCHARGE INTO THE THE WASTE WATER
 FACILTY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-02 Cont ID  
Sent By kstevens Date 2003-10-02 Time 17:09 Rev Time 0.50
Received By kstevens Date 2003-10-02 Time 17:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 18:06 Rev Time 0.50
Received By kstevens Date 2003-09-30 Time 18:06 Sent To  
Notes
2003-09-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTPER 1
  
 1) SECTION 1503.4.4 CONDENSATE SHALL
 DISCHARGE AT LEAST 1 FOOT FROM THE
 STRUCTURE SIDE WALL. SHOW DETAIL.
 2) SHT P1 W/HEATER EMERGENCY PAN DRAIN
 SHALL BE CPVC.
 3) FROM PREVIOUS REVIEW. SHOW P/T LINE
 PROVIDE AN ISOMETRIC AND INDICATE THE
 TERMINATION POINT FOR BOTH WATER HEATERS
 ALSO PROVIDE AN ISOMETRIC FOR THE PAN
 DRAIN WATER HEATER ON THE SECOND FLOOR.
 SHOW TERMINATION POINT FOR PAN DRAIN.
 SECTION 104.2.1
 4) FROM PREVIOUS REVIEW. THERMAL EXPAN-
 SION CONTROL REQUIRED, 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-26 Cont ID  
Sent By kstevens Date 2003-07-26 Time 12:34 Rev Time 1.00
Received By kstevens Date 2003-07-26 Time 12:33 Sent To  
Notes
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SHT P1 DWV ISOMETRIC, CONDENSATE
 SHALL DRAIN SEPARATELY FROM THE BLDG. TO
 STORM, CATCH BASIN, OR DRYWELL NOT INTO
 SANITARY PER SECTION 90-125(B)(5).
 SUBMIT RISER AND DETAILS.
 2) SHT P1 DWV ISOMETRIC, WATER COOLER IS
 NOT VENTED. - NO HORIZONTAL DRY VENTS
 SECTION 905.3
 3) SHT P1 PLUMBING SPECIFICATIONS #4 AND
 WATER SUPPLY ISOMETRIC, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM REFERENCE &
 ISOMETRIC. 604.9
 4) SHT P1 WATER HEATER, EMERGENCY PAN
 DRAIN IS REQUIRED. 504.8-INDICATE
 WHAT WILL HAPPEN TO THE RELIEF VALVE
 (T/P) DISCHARGE. SUBMIT DETAIL FOR PAN
 DRAIN LINE AND RELIEF VALVE DISCHARGE
 LINE. SHOW PIPE SIZE, MATERIAL, AND
 TERMINATION POINT FOR BOTH SYSTEMS.
 5) THERMAL EXPANSION CONTROL REQUIRED
 SECTION 607.3.2
 6) RPZ BACKFLOW REQUIRED. SECTION 608.13
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-25 Cont ID  
Sent By dlittle Date 2003-09-25 Time 15:45 Rev Time 0.00
Received By dlittle Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved