| 2003-09-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | NOT ALL COMMENTS FROM THE FIRST REVIEW |
| | HAV NOT BEEN ADDRESSED. THE FEW THAT |
| | HAVE BEEN ADDRESSED ARE NOT APPROVED. |
| | ANY CHANGES TO A SIGNED & SEALED SET OF |
| | PLANS SHALL BE DATED AND INITIALED BY |
| | THE ENGINEER OF RECORD. |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| | DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| | ANSI/NSPI-5. (ADD TO NOTES) |
| | 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) |
| | 3) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. |
| | 4) FBC-2001424.2.7.1 POOL CIRCULATING |
| | PUMPS SHALL BE EQUIPPED ON THE INLET |
| | SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| | STRAINER WHEN USED WITH A PRESSURE FIL- |
| | TER. (DETAIL) |
| | 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| | MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| | BASE IN A MANNER THAT WILL ELIMINATE |
| | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| | AL 4" THICK. (DETAIL) (TO BE DATED AND |
| | SIGNED BY ENGINEER OF RECORD) |
| | 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| | ORD. #2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) (SIGNED & |
| | DATED BY ENGINEER OF RECORD) |
| | 7) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 8) FBC-2001 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | 9) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 10) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 11) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| | WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| | LED WITH FLANGES OR UNION CONNECTIONS |
| | ADJACENT TO THE HEATER. (ADD TO NOTES) |
| | 12) POOL LAY-OUT SHEET SHOWS 2 JETS ON |
| | BENCH WHICH WILL BE REQUIRED TO BE SIGN- |
| | ED AND DATED BY THE ENGINEER OF RECORD, |
| | OR NEW SHEETS. THE PIPING SCHEMATIC DOES |
| | NOT REFLECT THE JETS. |
| | 13) PIPING SCHEMATIC STILL DOES NOT SHOW |
| | THE VACUUM LINE. |
| | |
| | REVIEW BY KEN STEVENS |