Plan Review Details - Permit 03070811
Plan Review Stops For Permit 03070811
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-10 Cont ID  
Sent By jwitmer Date 2003-10-10 Time 07:45 Rev Time 0.75
Received By jwitmer Date 2003-10-10 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-07 Cont ID  
Sent By jwitmer Date 2003-08-07 Time 13:41 Rev Time 0.75
Received By jwitmer Date 2003-08-07 Time 13:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-16 Cont ID  
Sent By jwitmer Date 2003-07-16 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2003-07-16 Time 16:47 Sent To  
Notes
2003-07-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070811
 ADD: 400 N. FLAGLER# 2206
 CONT: CASTLE FLORIDA BUILDING
 TEL: (561)662-7426
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) FL.S.S. 481.221.1(B) EACH REGISTERED
 INTERIOR DESIGNER SHALL OBTAIN A SEAL AS
 PRESCRIBED BY THE BOARD, AND ALL DRAW-
 INGS, PLANS,SPECIFICATIONS, OR REPORTS
 PREPARED OR ISSUED BY THE REGISTERED
 INTERIOR DESIGNER AND BEING FILED FOR
 PUBLIC RECORD SHALL BEAR THE SIGNATURE
 AND THE SEAL OF THE REGISTERED INTERIOR
 DESIGNER WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE
 SEALED. THE SIGNATURE, DATE AND SEAL
 SHALL BE EVIDENCE OF THE AUTHORITY OF
 THAT TO WHICH THEY ARE AFFIXED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLAN DOES NOT GIVE A COMPLETE LAY-
 OUT OF THE UNIT, HARD TO VISULIZE THE
 COMPLETE SUITE.
  
 3) DOORS 11& 25 INDICATE NEW DOORS,
 NO RATING IS GIVEN FOR THESE DOORS.
  
 4)R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION. NO DIMENSION
 ON WIDTH OF NEW DOOR.
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
 FLAME SPREAD/ SMOKE DEVELOPMENT.
  
 6)905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
  
 7) TYPE II BUILDING, IF ANY DOOR BUCKS
 ARE REPLACED OR IF WOOD BACKING IS IN-
 STALLED IN WALLS, FIRE RETARDANT TREATED
 WOOD IS TO BE USED.
  
 8) IN BUILDING OF TYPEI ORII CONSTRUC-
 TION FLOOR FINISH IF OF COMBUSTIBLE MATE
 RIAL, SHALL BE APPLIED DIRECTLY UPON THE
 FLOOR CONSTRUCTION. IF WOOD SLEEPERS ARE
 USED SEE CODE SECTION.803.7.1
  
 9) 803.7.2 COMBUSTIBLE INSULATING BOARDS
 MAY BE USED FOR SOUND DEADENING OR INSUL
 ATING OF FLOORS, EXCEPT THAT IN BUILD-
 INGS REQUIRED TO BE TYPE I OR II
 CONSTUCTION, SUCH INSULATING BOARDS
 SHALL NOT BE MORE THAN 1/2" THICK AND CE
 MENTED DIRECTLY TO THE FLOOR SLAB.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 09:55 Rev Time 0.33
Received By dpalmer Date 2003-10-27 Time 09:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:40 Rev Time 0.50
Received By dpalmer Date 2003-09-29 Time 17:52 Sent To  
Notes
2003-09-29 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE NOW
 SHOWING A COMPLETE REWIRE OF APARTMENT
 FROM ORIGINAL PLANS.
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. 210.8A6
 PLEASE SEE THAT RECEPTS IN BAR AREA ARE
 ALSO REQ'D TO BE SHOWN AS GFI PER LOCAL
 AMENDMENTS. 210.8 AND NEC 2002
  
 3)NOTE: PLEASE SEE SD LOCATION OUTSIDE
 MIDDLE BEDROOM NEEDS TO BE MOVED INTO
 HALL IF SERVING AS ONE SD OUTSIDE ALL
 THREE BEDRROMS. NFPA-72 8-1.4.2
  
 4)NOTE: PLEASE SHOW ALL BATH RECEPTS
 ALSO AS GFI/GFI PROTECTED.210.8
  
 5)NOTE: PLEASE CLARIFY AND SHOW CONTROL
 FOR LOBBY HI-HATS. PLEASE SEE 210.70 AND
 LS 101 5-8. PLEASE NOTE, A SINGLE MEANS
 BY ELEVATOR WILL NOT MEET CONTROL FOR
 EGRESS.
  
 6)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 FOR ALL MIN CIRCUITS REQD' AND LIST THE
 ARC FAULT PROTECTED CIRCUITS FOR ALL
 BEDROOMS PER 210.12
  
 7)NOTE: PLEASE CLARIFY AND SEE THAT AHU
 IS SHOWN INSIDE TOILET???
  
 8)NOTE: PLEASE SEE DEVICE HEIGHTS TO
 MEET FHAR 24 CFR 100.205
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-08 Cont ID  
Sent By dpalmer Date 2003-08-08 Time 16:41 Rev Time 0.33
Received By dpalmer Date 2003-08-08 Time 16:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 13:20 Rev Time 0.33
Received By dpalmer Date 2003-07-17 Time 12:38 Sent To  
Notes
2003-07-17 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR FS AND FAC 471/481 AND 61G15-23.002
 AND 61G1-16.004 FOR ARCH/ENG/DESIGNERS
 TITLE BLOCK INFORMATION REQ'D.
  
  
 2)NOTE: PLEASE SHOW LOCATION FOR SD'S
 RED'D PER NFPA-72 8-1 INSIDE/OUTSIDE BR
  
 3)NOTE: PLEASE CLARIFY NEW CIRCUITS/
 OUTLETS PER 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS,PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-06 Cont ID  
Sent By nmccray Date 2003-10-06 Time 10:56 Rev Time 0.00
Received By nmccray Date 2003-10-06 Time 10:54 Sent To  
Notes
2003-10-06 00:00:00*************PROVISO********************
 PLEASE MOVE SMOKE DETECTOR INTO THE HALL
 TO BETTER SERVE ALL THREE BEDROOMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By nmccray Date 2003-08-11 Time 14:33 Rev Time 0.00
Received By nmccray Date 2003-08-11 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-23 Cont ID  
Sent By mcarsill Date 2003-07-23 Time 17:03 Rev Time 0.00
Received By mcarsill Date 2003-07-23 Time 17:02 Sent To  
Notes
2003-07-23 00:00:001) ENSURE THAT ANY EXISTING ELECTRIC
 POWERED SMOKE DETECTORS ARE IN WORKING
 ORDER. IF NO SMOKE DETECTORS ARE
 PRESENT, ELECTRIC POWERED SMOKE
 DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE OF THE SLEEPING ROOMS.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:40 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 16:40 Sent To E
Notes
2003-10-24 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 15:11 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 15:11 Sent To  
Notes
2003-09-24 00:00:00TO COMM BD #23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 13:45 Rev Time 0.00
Received By alange Date 2003-08-01 Time 13:45 Sent To  
Notes
2003-08-01 00:00:00TO COMM BD #64

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 14:37 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 14:37 Sent To  
Notes
2003-07-11 00:00:00COMM BOARD #15

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-26 Cont ID  
Sent By kstevens Date 2003-07-26 Time 10:04 Rev Time 0.33
Received By kstevens Date 2003-07-26 Time 10:04 Sent To  
Notes
2003-07-26 00:00:00NO PLUMBING PLANS SUBMITTED - PLUMBING
 PERMIT REQUIRED