Plan Review Details - Permit 03070793
Plan Review Stops For Permit 03070793
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-18 Cont ID  
Sent By rmcdouga Date 2004-02-18 Time 14:24 Rev Time 0.50
Received By rmcdouga Date 2004-02-18 Time 14:24 Sent To  
Notes
2004-02-18 00:00:00SUBMITTED REVISED COVENANTS FOR EGRESS
 EASEMENT AT ZERO LOT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-11-06 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:18 Rev Time 1.00
Received By rmcdouga Date 2003-11-06 Time 07:58 Sent To  
Notes
2003-11-06 00:00:00 
  
 1) PRODUCT APPROVAL FOR IMPACT WINDOW IS
 OK.
  
 2) THE COVENANTS THAT WERE SUBMITTED DO
 NOT MENTION AN EGRESS EASEMENT AND ARE
 NOT ACCEPTABLE. THE ORIGINAL COVENANTS
 NEED TO BE AMENDED TO SPECIFY AN EGRESS
 EASEMENT FOR EMERGENCY ESCAPE AND RESCUE
 SEE THE ATTACHED FOR REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-11-04 Time 15:13 Rev Time 2.00
Received By rmcdouga Date 2003-10-09 Time 10:00 Sent To  
Notes
2003-10-09 00:00:00PROVISO
  
 1) SUBMIT PRODUCT APPROVAL FOR THE
 SINGLE HUNG IMPACT WINDOW FOR EGRESS IN
 THE DEN.
  
 2) 1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT. THE DECLARATION OF COVENANTS
 THAT WERE SUBMITTED DO NOT SPECIFICALLY
 ADDRESS THE REQUIRED EGRESS EASEMENT AT
 THE ZERO LOT LINE. SUBMIT A RECORDED
 COPY OF REVISED COVENANTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-10-08 Time 09:10 Rev Time 2.50
Received By rmcdouga Date 2003-08-07 Time 13:42 Sent To  
Notes
2003-08-07 00:00:00DENIED
  
 1) SAME COMMENTS AS PERMIT # 03070787.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 08:39 Rev Time 0.33
Received By dpalmer Date 2003-10-27 Time 08:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:51 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 13:59 Sent To P
Notes
2003-10-07 00:00:00**************** USNAT **************
  
 1)NOTE: PLEASE SEE THAT NEW ELECTRICAL
 RISER DIAGRAM IS NOW SUBMITTED.
 PLEASE SEE MISSING REQ'D FOOTER STEEL
 AND COLD WATER PER 250.50.
  
 2)NOTE: PLEASE CORRELATE LOADS/RISER/AND
 PANEL SCHEDULES. NO PANEL SCHEDULE/LOADS
 SHOWN FOR A/C SUB PANEL?
  
 3)NOTE: PLANS SHOW 2 A/C SYSTEMS AND YET
 MAIN PANEL SCHEDUL ONY SHOWS ONE FEED
 FOR AHU AND LOAD CALCS ONLY SHOW ONE
 ALSO. PLEASE CORRELATE?
  
 4)NOTE: PLEASE SEE MIN LOAD FOR DRYER
 TO BE 5KW 220.18
  
 5)NOTE: PLEASE SEE 210.12. THE 2002 NEC
 WENT INTO EFFECT 7/1/2003, AT THAT TIME
 ARC FAULT PROTECTION IS REQ'D FOR MORE
 THAN RECEPTS AS NOTED ON PLAN.
  
 PLEASE SEE COPY OFFS 553.80(2)(B),WITH
 RESPECT TO DESIGNPROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:20 Rev Time 0.33
Received By dpalmer Date 2003-07-25 Time 07:01 Sent To M
Notes
2003-07-25 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE. 200A PANEL SHOWS
 POOL PANEL, NOT SHOWN ON RISER.
  
 2)NOTE: PLEASE SEE OCP/BRKR AND SIZING
 FOR DRYER. PLEASE ALSO SEE WIRE SIZE.
  
 PLEASE NOTE, ALL OPTIONS AND PLANS WILL
 NEED TO BE REVISED BEFORE ROUGH TO
 WHEATHER THEY WERE INSTALLED OR NOT.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 MCB SINCE THE FUSED DISC HAS BEEN
 DELETED FROM RISER. NOTES STILL MENTION
 FUSES TO BE USED.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:18 Sent To  
Notes
2004-02-18 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 15:13 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 15:13 Sent To B
Notes
2003-11-04 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:51 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 08:50 Sent To E
Notes
2003-10-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:20 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 09:20 Sent To E
Notes
2003-10-06 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-11 Cont ID  
Sent By mmclean Date 2003-07-15 Time 12:40 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 12:03 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-25 Time 07:19 Rev Time 0.25
Received By pkrauss Date 2003-07-29 Time 11:30 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By kstevens Date 2003-10-08 Time 09:10 Rev Time 0.25
Received By kstevens Date 2003-10-08 Time 09:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 14:01 Rev Time 0.33
Received By kstevens Date 2003-08-04 Time 14:48 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-11 Time 12:03 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***