Plan Review Details - Permit 03070787
Plan Review Stops For Permit 03070787
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-18 Cont ID  
Sent By rmcdouga Date 2004-02-18 Time 14:01 Rev Time 0.50
Received By rmcdouga Date 2004-02-18 Time 14:00 Sent To  
Notes
2004-02-18 00:00:00SUBMITTED REVISED COVENANTS FOR EGRESS
 EASEMENT AT ZERO LOT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-11-06 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:18 Rev Time 1.00
Received By rmcdouga Date 2003-11-06 Time 07:08 Sent To  
Notes
2003-11-06 00:00:00 
  
 1) PRODUCT APPROVAL FOR IMPACT WINDOW IS
 OK.
 2) THE SUBDIVISION COVENANTS THAT WERE
 SUBMITTED DO NOT MENTION AN EGRESS
 EASEMENT AND ARE NOT ACCEPTABLE. THE
 ORIGIONAL COVENANTS NEED TO BE AMENDED
 TO SPECIFICALLY INDICATE THAT AN EGRESS
 EASEMENT FOR EMERGENCY ESCAPE AND RESCUE
 WILL BE PROVIDED AND MAINTAINED. SEE THE
 ATTACHED FOR DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-11-04 Time 15:30 Rev Time 2.00
Received By rmcdouga Date 2003-10-09 Time 13:47 Sent To  
Notes
2003-10-09 00:00:00PROVISO
  
 1) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE HUNG IMPACT RESISTANT WINDOW FOR
 EGRESS IN THE DEN.
  
 2) 1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT. THE DECLARATION OF COVENANTS
 THAT WERE SUBMITTED DO NOT SPECIFICALLY
 ADDRESS THE REQUIRED EGRESS EASEMENT AT
 THE ZERO LOT LINE. SUBMIT A RECORDED
 COPY OF REVISED COVENANTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-10-08 Time 09:35 Rev Time 2.50
Received By rmcdouga Date 2003-08-07 Time 11:08 Sent To  
Notes
2003-08-07 00:00:00DENIED
  
 1)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 2) FBC 1909.3 REQUIRES THE WWM IS THE
 SLAB TO BE SUPPORTED ON APPROVED
 MATERIALS AT NO MORE THAN 3 FEET OC.
 PLEASE INDICATE ON PLANS.
  
 3) SPECIFY ON THE FLOOR PLAN THAT GLASS
 BLOCK AT ZERO LOT LINE IS REQUIRED TO
 BE ONE HOUR FIRE RATED.
  
 4) THE GLASS BLOCK AT THE MASTER BATH
 TUB IS IN A HAZARDOUS LOCATION AND IS
 REQUIRED TO HAVE A MINIMUM UNIFORM FACE
 THICKNESS OF 0.25" PER 2405.2. PLEASE
 SPECIFY ON THE PLANS.
  
 5) THE DOOR IN THE GARAGE WALL ADJACENT
 TO THE CONDITIONED SPACE IS REQUIRED TO
 BE SOLID CORE OR INSULATED PER FBC
 CHAPTER 13.
  
 6) SHEET 2 OF THE PLANS LIST THE A/C
 AREA AS 2590 SQFT AND THE ENERGY CALCS.
 HAS 2579 SQFT. PLEASE CORRECT.
  
 7) THE WINDOWS IN THE DEN EXCEED THE 20
 PERCENT OF WALL AREA ALLOWED AS OPENINGS
 BY FBC TABLE 600. (21 SQFT ALLOWED)
  
 8) THE LETTER FROM THE ENGINEER FOR THE
 GLASS BLOCK IS REQUIRED TO BE SIGNED AND
 SEALED WHEN SUBMITTED FOR PUBLIC RECORD
 PER FAC 61G15-23.002.
  
 9) FBC 1609.4.3 DOES NOT ALLOW THE ONE-
 THIRD INCREASE ON THE STEEL CALCULATIONS
 FOR CONNECTORS. PLEASE REVISE THE
 CONNECTOR SCHEDULE ON SHEET 6 TO VALUES
 WHICH DO NOT INCLUDE THIS INCREASE. SEE
 THE 2003 USP AND 2002 SIMPSON HIGH WIND
 RESISTANT CONSTRUCTION CATALOGS.
  
 10) HUGHES WAS PURCHASED BY USP SOME
 TIME AGO. PLEASE UPDATE THE HUGHES
 CONNECTORS SPECIFIED ON SHEET 6 AND IN
 THE DETAILS ON SHEET 8, TO A CURRENT
 MANUFACTURER.
  
 11) PLEASE REVISE THE BUILDING CATEGORY
 ON SHEET 6 TO CATEGORY II. SEE TABLE 1-1
 IN ASCE 7-98. R3 IS THE OCCUPANCY
 CLASSIFICATION.
  
 12) NOTE 10 ON SHEET 8 REFERENCES THE
 WRONG CODE. PLEASE UPDATE TO 2001 FBC.
  
 13) PROVIDE A DETAIL FOR STRUCTURAL 2X
 BUCKS AS REQUIRED BY THE PRODUCT
 APPROVAL FOR THE ENTRY DOOR.
  
 14)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 15) THERE ARE TWO ARCHITECT'S TITLE
 BLOCKS ON THE PLAN. PLEASE REMOVE THE
 ONE THAT DOES NOT BELONG TO THE DESIGNER
 OF RECORD.
  
 16) STORM PANELS: THE SAFEGUARD COMPANY
 IS NO LONGER IN BUSINESS AND WEATHER-
 GUARD HAS NOT COMPLETED THE PROCESS OF
 ASSUMING THE PRODUCT APPROVAL FROM SBCCI
 THE BUILDING OFFICIAL HAS DETERMINED
 THAT WE CAN NOT ACCEPT THIS PRODUCT FOR
 INSTALLATION IN THE CITY OF WPB AT THIS
 TIME.
  
 17) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
  
 18) THE TRUSS DRAWINGS AND LAYOUT FOR
 SINGLE FAMILY DWELLINGS ARE NO LONGER
 REQUIRED TO BE SUBMITTED FOR PLAN REVIEW
 THEY ARE TO BE GIVEN TO THE INSPECTOR IN
 THE FIELD AT THE TRUSS INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 08:40 Rev Time 0.33
Received By dpalmer Date 2003-10-27 Time 08:40 Sent To B
Notes
2003-10-27 00:00:00REDLINED, OPTIONS AND REV'S BEFORE
 ROUGH.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:56 Rev Time 0.75
Received By dpalmer Date 2003-10-07 Time 13:26 Sent To P
Notes
2003-10-07 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE A NEW RISER DIAGRAM
 IS NOW SUBMITTED. PLEASE SEE MISSING
 GROUNDING ELECTRODE CONDUCTOR TO BLDG/
 FOOTER STEEL AND COLD WATER. 250.50
  
 2)NOTE: PLEASE SEE THAT A/C SUB PANEL
 IS NOT ON LOAD CALCS. NO LOADS/ OCO/
 CONDCUTOR SIZES ARE SHOWN??
  
 3)NOTE: PLEASE SEE AS OF 7/1/2003 ARC
 FAULT PROTECTION IS NO LONGER JUST FOR
 RECEPTS AS NOTED ON PLANS.
  
 4)NOTE: PLEASE SEE LOAD FOR DRYER TO BE
 5KW MIN.220.18
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONALS
 .
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-25 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:25 Rev Time 0.50
Received By dpalmer Date 2003-07-25 Time 07:32 Sent To M
Notes
2003-07-25 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MCB PANEL. PLANS NOTE USE OF FUSES
 AND THERE IS NO LONGER A FUSED MAIN
 DISCONNECT BEING SHOWN ON RISER DIAGRAM?
 110.9/215.5
  
 2)NOTE: PLEASE SEE MAIN PANEL, SHOWS
 POOL PANEL BUT POOL PANEL IS NOT SHOWN
 ON RISER.PLEASE CORRELATE.
  
 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR
 RANGE? SHOWS 3.6KW W/ A 2P-50?
  
 4)NOTE: PLEASE SEE PLANS, STILL SHOW
 MAIN DISC NEXT TO METER?
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:18 Sent To B
Notes
2004-02-18 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 15:30 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 15:30 Sent To B
Notes
2003-11-04 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:54 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 08:54 Sent To E
Notes
2003-10-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 09:24 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 09:24 Sent To E
Notes
2003-10-06 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-11 Cont ID  
Sent By mmclean Date 2003-07-15 Time 12:31 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 12:03 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-07 Cont ID  
Sent By dpalmer Date 2003-07-25 Time 07:32 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-08-07 00:00:00OK PER P. KRAUSS 7-25-03

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By kstevens Date 2003-10-08 Time 09:35 Rev Time 0.33
Received By kstevens Date 2003-10-08 Time 09:35 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 13:40 Rev Time 0.33
Received By kstevens Date 2003-08-04 Time 14:05 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-11 Time 12:03 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***