Plan Review Details - Permit 03070535
Plan Review Stops For Permit 03070535
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By jwitmer Date 2003-08-08 Time 08:43 Rev Time 1.20
Received By jwitmer Date 2003-08-08 Time 08:43 Sent To  
Notes
2003-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070535
 ADD: 1801 PALM BEACH LAKES/ 158
 CONT: RECTENWALD BROTHERS
 TEL: (724)772-8282
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: PROVISO
  
 1) COMMENT # 1 FROM FIRST REVIEW ONLY
 THE SECOND HALF WAS COMPLIED WITH.
 EDGE PROTECTION FOR RAMP AND UPPER LAND-
 ING NEVER COMPLIED WITH. 1013.8/
 11-4.8.7 RAMPS AND LANDINGS WITH DROP
 OFFS SHALL HAVE CURBS, WALLS, RAILINGS
 OR PROTECTING SURFACES THAT PREVENT
 PEOPLE FROM SLIPPING OFF THE RAMP. CURBS
 SHALL BE A MINIMUM OF 2" IN HIGH (SEE
 FIGURE 17).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-22 Cont ID  
Sent By jwitmer Date 2003-07-22 Time 07:50 Rev Time 1.50
Received By jwitmer Date 2003-07-22 Time 07:50 Sent To  
Notes
2003-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070535
 ADD:1801 PALM BCH LAKES BLVD/ 158
 CONT:PLAN REVIEW
 RECTENWALD BROTHERS
 TEL: (724)772-8282
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 1013.8 EDGE PROTECTION. EDGE PROTEC-
 TION OF RAMP SHALL COMPLY WITH 1013.8.1
 OR 1013.8.2. EDGE PROTECTION OF RAMP
 SHALL NOT INTERFERE WITH THE CLEAR FLOOR
 SPACE REQUIRED WITH DOOR SWING INTO THE
 HANDICAPPED RESTROOM.
  
 2)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. THE DOOR LEADING INTO THE
 HANDICAPPED CHANGING ROOM TO BE 18"
 CLEAR ON THE LATCH SIDE.
  
 4) 11-4.35 DRESSING & FITTING ROOMS.
 BENCH 11-4.35.4 A 24"X48" BENCH SHALL BE
 FIXED TO THE WALL ALONG THE LONGER DIMEN
 SION.11-4.35.2 CLEAR FLOOR SPACE FOR A
 WHEELCHAIR TO BE ABLE TO MAKE A 180
 DEGREE TURN. 11-4.35.5 MIRRORS SEE
 CODE SECTION.
  
 5)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 6)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
 PROVIDE TIE DOWN INFORMATION OF THE
 ROOF TOP UNITS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By dpalmer Date 2003-08-11 Time 12:38 Rev Time 1.00
Received By dpalmer Date 2003-08-11 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By dpalmer Date 2003-07-21 Time 07:37 Rev Time 0.75
Received By dpalmer Date 2003-07-21 Time 07:17 Sent To  
Notes
2003-07-21 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE 310.16 FOR SIZING
 OF FEEDERS/CONDUCTORS TO PANEL FROM 400A
 MAIN. SHOWN AS 250MCM (RATED FOR255A)
 110.14.PLEASE ADJUST OCP OR CONDUCTORS
  
 2)NOTE: PLEASE SHOW TRACK LIGHTING LOADS
 PER 220.12B
  
 3)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% 215.3/230.42 ETC.
  
 4)NOTE: PLEASE SHOW CIRCUITING OF EM/EXT
 LTS PER 700.12E
  
 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING FROM MAIN TO PANEL AND
 FROM PANEL TO RTU`S. 250.110/250.122
  
 6)NOTE: PLEASE SEE ATTACHED COPIES OF
 FAC 61G15-23.002 FOR ENGINEER AND
 61G1-16.004 FOR ARCH. PLEASE SEE MISSING
 INFORMATION REQ'D ON TITLE BLOCKS FOR
 BOTH ARCH AND ENGINEER OF RECORD. PLEASE
 SEE THAT TITLE BLOC K IS MISSING FOR
 ENGINEER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By nmccray Date 2003-08-20 Time 14:33 Rev Time 0.00
Received By nmccray Date 2003-08-20 Time 14:33 Sent To  
Notes
2003-08-20 00:00:00***********PROVISO**********************
 HANDRAILS REQUIRED ON RAMP.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By mcarsill Date 2003-07-17 Time 16:09 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:09 Sent To  
Notes
2003-07-17 00:00:001) HANDRAILS REQUIRED ON RAMP.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 14:24 Rev Time 0.00
Received By alange Date 2003-08-01 Time 14:24 Sent To  
Notes
2003-08-01 00:00:00COMM BD #56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:35 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 16:35 Sent To  
Notes
2003-07-08 00:00:00COMM BOARD #33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-18 Cont ID  
Sent By pkrauss Date 2003-08-18 Time 14:12 Rev Time 0.40
Received By pkrauss Date 2003-08-18 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-26 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 10:48 Rev Time 0.50
Received By pkrauss Date 2003-07-26 Time 10:43 Sent To  
Notes
2003-07-26 00:00:00PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-18 Cont ID  
Sent By kstevens Date 2003-08-18 Time 11:02 Rev Time 1.50
Received By kstevens Date 2003-08-18 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-19 Cont ID  
Sent By kstevens Date 2003-07-19 Time 14:17 Rev Time 1.00
Received By kstevens Date 2003-07-19 Time 14:17 Sent To  
Notes
2003-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 DRINKING FOUNTAIN, SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH 11-4.15 &
 ALL SUBSECTIONS. SHOW SPOUT HEIGHT, (11-
 4.15.2), CLEARANCES/CLEAR FLOOR SPACE,
 (11-4.15.5) ECT. - DOOR SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. 11-4.22.2/4.23.2.
 2) SHT A-1 HANDICAP FITTING ROOM, BENCH
 SHALL BE FIXED TO THE WALL ALONG THE
 LONGEST DIMENSION. 11-4.35.4
 3) SHT A-10 DETAILS A/A-10 & B/A-10,
 PROVIDE A CLEARANCE OF AT LEAST 29"
 ABOVE THE FINISHED FLOOR TO THE BOTTOM
 OF THE APRON. (27" SHOWN) - RIM SHALL BE
 NO HIGHER THAN 34" (A.F.F). 11-4.19.2
 4) SHT M-2 WATER RISER DIAGRAM. BACKFLOW
 SHALL BE LOCATED NO MORE THAN 4' ABOVE
 THE FLOOR FOR SERVICING AND TESTING.
 5) SHT M-2 WATER RISER DIAGRAM, FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR T/P & PAN DRAIN FROM THE
 WATER HEATER. 802.3 & 802.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692