| 2003-08-21 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY FBC 1804.2.2. |
| | |
| | 4) THE GLASS BLOCK IN THE MASTER BATH |
| | SHOWER AND AT THE TUB IN SECOND FLOOR |
| | BATH 2 ARE IN HAZARDOUS LOCATIONS AND |
| | ARE REQUIRED TO HAVE A MINIMUM UNIFORM |
| | FACE THICKNESS OF 0.25" PER FBC 2405.2. |
| | |
| | 5) THE FULL BATH ON THE FIRST FLOOR IS |
| | REQUIRED TO HAVE A DOOR WITH A 29" CLEAR |
| | OPENING PER FBC 11-4.23.2. |
| | |
| | 6) THE GIRDER ABOVE THE FAMILY ROOM NEAR |
| | THE KITCHEN HAS A TAG THAT CALLS FOR 2 |
| | 9/11 ANCHORS. PLEASE CLARIFY. |
| | |
| | 7) SPECIFY WHAT ANCHORS WILL BE USED FOR |
| | EACH END OF THE TRIPLE 2X8 INSERT HEADER |
| | AT THE COVERED LANAI. SPECIFY THE |
| | ANCHORS THAT WILL BE USED TO ATTACH THE |
| | TRUSSES TO THE HEADER. INDICATE HOW |
| | THESE TRUSSES WILL BE ATTACHED TO THE |
| | SECOND FLOOR WALL. PROVIDE DETAILS. |
| | SEE FBC 104.2.1.2 |
| | |
| | 8) THE OVERHEAD GARAGE DOOR PRODUCT |
| | APPROVAL DOES NOT MEET THE PRESSURES |
| | LISTED IN THE WINDLOAD SCHEDULE ON A1. |
| | |
| | 9) THE SH35 WINDOWS (W) AND (Y) WILL |
| | REQUIRE 3/16" TEMPERED GLASS TO MEET THE |
| | SPECIFIED WINDLOADS ACCORDING TO THE |
| | PRODUCT APPROVAL THAT WAS SUBMITTED. |
| | |
| | 10) THE PRODUCT APPROVAL FOR THE DOUBLE |
| | OUTSWING ENTRY DOOR DOES NOT MEET THE |
| | WINDLOAD PRESSURES LISTED ON THE PLANS. |
| | |
| | 11) THE 66" X 72" F.G. WINDOW (I) DOES |
| | NOT MEET THE WINDLOAD PRESSURES LISTED |
| | ON THE PLANS. |
| | |
| | 12) PLEASE REVIEW THE WINDLOAD PRESSURES |
| | ON THE PLANS, THEY MAY BE HIGHER THAN |
| | REQUIRED FOR EXPOSURE B. |
| | |
| | 13) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR THE ARCHED TOP FIXED GLASS |
| | (TOMBSTONE) WINDOWS (A2,A3,A4 AND F). |
| | |
| | 14) THE STORM PANEL KEY PLAN AND |
| | SCHEEDULE ARE MISSING AN OPENING ON THE |
| | SECOND FLOOR. THE OPENING SIZES LISTED |
| | ON THE SCHEDULE DO NOT CORRESPOND WITH |
| | THE WINDLOAD SCHEDULE OPENING SIZES FOR |
| | SOME OF THE GLAZED OPENINGS. SOME OF THE |
| | SPECIFIED PANEL LENGTHS ARE LESS THAN |
| | THE MINIMUM LENGTHS PERMITTED BY THE |
| | PRODUCT APPROVALS. THE CALK-IN ANCHORS |
| | SPECIFIED ARE NOT ALLOWED FOR C1 |
| | CONNECTION TYPES IN HOLLOW CONC. BLOCK. |
| | PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |