Plan Review Details - Permit 03070530
Plan Review Stops For Permit 03070530
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-01 Cont ID  
Sent By rmcdouga Date 2003-12-01 Time 16:54 Rev Time 1.00
Received By rmcdouga Date 2003-12-01 Time 16:54 Sent To  
Notes
2003-12-02 00:00:00REVISED SHEETS A3,A4,A5,A9 & A10 ARE
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-15 Cont ID  
Sent By pschmitz Date 2003-11-24 Time 14:17 Rev Time 2.50
Received By rmcdouga Date 2003-09-15 Time 14:14 Sent To  
Notes
2003-09-15 00:00:00PROVISO
  
 1) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2, PRIOR TO
 POURING THE FOUNDATION.
  
 2) SUBMIT A SIGNED AND SEALED LETTER
 FROM KNEZEVICH AND ASSOC. CLARIFYING
 THAT TABLE NUMBER 7, ON PAGE 9 OF 9 OF
 THE STORM PANEL DRAWINGS SUPERCEDES THE
 ANCHOR SCHEDULE ON PAGE 7 OF 9, FOR THE
 POWERS CALK-IN ANCHORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-09-11 Time 12:33 Rev Time 3.00
Received By rmcdouga Date 2003-08-21 Time 08:39 Sent To  
Notes
2003-08-21 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 SHOWER AND AT THE TUB IN SECOND FLOOR
 BATH 2 ARE IN HAZARDOUS LOCATIONS AND
 ARE REQUIRED TO HAVE A MINIMUM UNIFORM
 FACE THICKNESS OF 0.25" PER FBC 2405.2.
  
 5) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING PER FBC 11-4.23.2.
  
 6) THE GIRDER ABOVE THE FAMILY ROOM NEAR
 THE KITCHEN HAS A TAG THAT CALLS FOR 2
 9/11 ANCHORS. PLEASE CLARIFY.
  
 7) SPECIFY WHAT ANCHORS WILL BE USED FOR
 EACH END OF THE TRIPLE 2X8 INSERT HEADER
 AT THE COVERED LANAI. SPECIFY THE
 ANCHORS THAT WILL BE USED TO ATTACH THE
 TRUSSES TO THE HEADER. INDICATE HOW
 THESE TRUSSES WILL BE ATTACHED TO THE
 SECOND FLOOR WALL. PROVIDE DETAILS.
 SEE FBC 104.2.1.2
  
 8) THE OVERHEAD GARAGE DOOR PRODUCT
 APPROVAL DOES NOT MEET THE PRESSURES
 LISTED IN THE WINDLOAD SCHEDULE ON A1.
  
 9) THE SH35 WINDOWS (W) AND (Y) WILL
 REQUIRE 3/16" TEMPERED GLASS TO MEET THE
 SPECIFIED WINDLOADS ACCORDING TO THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
  
 10) THE PRODUCT APPROVAL FOR THE DOUBLE
 OUTSWING ENTRY DOOR DOES NOT MEET THE
 WINDLOAD PRESSURES LISTED ON THE PLANS.
  
 11) THE 66" X 72" F.G. WINDOW (I) DOES
 NOT MEET THE WINDLOAD PRESSURES LISTED
 ON THE PLANS.
  
 12) PLEASE REVIEW THE WINDLOAD PRESSURES
 ON THE PLANS, THEY MAY BE HIGHER THAN
 REQUIRED FOR EXPOSURE B.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE ARCHED TOP FIXED GLASS
 (TOMBSTONE) WINDOWS (A2,A3,A4 AND F).
  
 14) THE STORM PANEL KEY PLAN AND
 SCHEEDULE ARE MISSING AN OPENING ON THE
 SECOND FLOOR. THE OPENING SIZES LISTED
 ON THE SCHEDULE DO NOT CORRESPOND WITH
 THE WINDLOAD SCHEDULE OPENING SIZES FOR
 SOME OF THE GLAZED OPENINGS. SOME OF THE
 SPECIFIED PANEL LENGTHS ARE LESS THAN
 THE MINIMUM LENGTHS PERMITTED BY THE
 PRODUCT APPROVALS. THE CALK-IN ANCHORS
 SPECIFIED ARE NOT ALLOWED FOR C1
 CONNECTION TYPES IN HOLLOW CONC. BLOCK.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By btrobaug Date 2003-11-24 Time 10:12 Rev Time 0.50
Received By btrobaug Date 2003-11-24 Time 10:09 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-13 Cont ID  
Sent By csiegber Date 2003-11-21 Time 15:23 Rev Time 0.33
Received By dpalmer Date 2003-08-13 Time 06:35 Sent To M
Notes
2003-08-13 00:00:00*********** NOTE *********
  
 1)NOTE: PLEASE SEE THAT OCP AND AWG
 FOR GEN LTS IS STILL BEING SHOWN AT
 60A AND #6.
 THIS HAS BEEN REDLINED ON ALL PREVIOUS
 PLANS BUT NEEDS TO BE CORRECTED FOR
 FUTURE SETS.
  
 2)NOTE: PLANS ARE ALSO MISSING REQ`D SD
 AT BOTTOM OF STAIRS. SD'S TO BE IN THE
 IMMEDIATE VICINITY LEADING TO THE FLOOR
 ABOVE. NFPA-72 2-5.2.1.6, 8-1.4.2
 SD OUTSIDE MASTER BEDROOM CAN BE MOVED
 OVER TO MEET BOTH OUTSIDE BEDRM AND
 SERVING FOR STAIRS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 12:26 Sent To P
Notes
2004-01-27 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-11-21 Time 15:23 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 15:23 Sent To E
Notes
2003-11-21 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 11:59 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 11:59 Sent To B
Notes
2003-09-19 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 12:33 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 12:33 Sent To B
Notes
2003-09-11 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 13:36 Rev Time 0.00
Received By alange Date 2003-08-05 Time 13:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-01 Cont ID  
Sent By mmclean Date 2003-08-05 Time 10:37 Rev Time 0.00
Received By alange Date 2003-08-01 Time 10:36 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-18 Cont ID  
Sent By dpalmer Date 2003-08-13 Time 06:35 Rev Time 0.25
Received By pkrauss Date 2003-08-18 Time 07:01 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-28 Cont ID  
Sent By kstevens Date 2004-01-28 Time 15:44 Rev Time 0.50
Received By kstevens Date 2004-01-28 Time 15:44 Sent To  
Notes
2004-01-28 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:26 Rev Time 0.50
Received By pschmitz Date 2003-11-24 Time 14:13 Sent To B
Notes
2003-11-24 00:00:00REVISION,
 MOVE LAUNDRY SINK.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By btrobaug Date 2003-11-24 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2003-08-21 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-01 Time 10:36 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***