Plan Review Details - Permit 03070452
Plan Review Stops For Permit 03070452
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-24 Cont ID  
Sent By rmcdouga Date 2003-09-24 Time 14:42 Rev Time 3.00
Received By rmcdouga Date 2003-09-24 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:56 Rev Time 2.00
Received By rmcdouga Date 2003-09-08 Time 16:28 Sent To  
Notes
2003-09-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ONE SET OF ENERGY CALCULATIONS IS
 FOR ANOTHER MODEL. TWO SETS ARE REQUIRED
 PLEASE REMOVE THE INCORRECT SET AND
 SUBMIT TWO COMPLETE SETS.
  
 3) THE REVISED DETAIL 1 ON SHEET 4 IS
 STILL INCORRECT. FBC 1707.4.4.2 REQUIRES
 THE BUCK TO EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.
  
 4) SHEET 2 OF THE PLANS CONTAINS
 STRUCTURAL INFORMATION AND THE TITLE
 BLOCK OF THE ENGINEER. THE ENGINEER IS
 RESPONSIBLE FOR THE STRUCTURAL DESIGN
 AND IS REQUIRED TO SIGN AND SEAL THIS
 SHEET. SEE FAC 61G15-23.002.
  
 5) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGNER OF RECORD. IF THE
 DESIGNER OF RECORD DOES NOT WISH TO SEAL
 THE FORM, A SIGNED AND SEALED LETTER
 FROM THE DESIGNER OF RECORD SPECIFYING
 THE PRODUCT AND SPECIFIC SITE LOCATION,
 STATING THAT THE PRODUCT HAS BEEN
 REVIEWED AND IS ACCEPTABLE FOR USE IN
 THE STRUCTURE.
  
 6) THE PRODUCT APPROVALS FOR THE STORM
 PANELS ARE ILLEGIBLE. SUBMIT CLEAR
 COPIES. THE STORM PANEL DRAWINGS ARE
 STAMPED FOR ONE PERMIT ONLY. THEREFORE,
 A SIGNED AND SEALED COPY OF THE DRAWINGS
 IS REQUIRED FOR EACH PERMIT.
  
 7) THE TWO "USP" TA STRAPS LISTED AS A-4
 IN THE TRUSS CONNECTOR SCHEDULE WITH
 (5) 10D X 1-1/2" NAILS AND AN UPLIFT OF
 1432# IS INCORRECT. THE UPLIFT VALUE
 LISTED IN THE 2003 "USP" CATALOG IS
 1230#. PLEASE CORRECT. SEE ATTACHED.
  
 8) THE SURVEY INDICATES THAT THE
 STRUCTURE IS LOCATED IN A "B" FLOOD
 ZONE. THE CITY'S RECORDS SHOW IT IN AN
 "AO" FLOOD ZONE. PLEASE SUBMIT CORRECTED
 SURVEY.
  
 9) SUBMIT CLEAR READABLE COPIES OF THE
 PRODUCT APPROVALS FOR THE OUTSWING DOOR
 WITH SIDELITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-09-04 Time 15:41 Rev Time 4.00
Received By rmcdouga Date 2003-07-31 Time 10:52 Sent To  
Notes
2003-07-31 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ONE SET OF THE ENERGY CALCULATIONS IS
 FOR THE WRONG MODEL.
  
 3) PLEASE REVISE DETAIL 1 ON SHEET 4.
 THE BUCK IS REQUIRED TO EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.)
  
 4) SPECIFY THE SIZE OF THE COLUMN AT THE
 REAR PORCH.
  
 5) SPECIFY THE CONNECTOR FOR THE WOOD
 BEAM AT THE REAR PORCH WHERE IT CONNECTS
 TO THE WALL AT THE MASTER BED ROOM.
  
 6) THE ENGINEER IS REQUIRED TO SIGN AND
 SEAL THE STRUCTURAL PLAN SHEETS ON
 WHICH HIS TITLE BLOCK APPEARS. SEE FAC
 61G15-23.002.
  
 7) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. THE ENGINEER'S
 NAME, ADDRESS AND NUMBER ARE REQUIRED TO
 BE ON THE FORM. SEE FAC 61G15-23.002.
  
 8) PLEASE REVIEW THE REQUIRED DESIGN
 PRESSURES FOR THE GARAGE DOOR ON SHEET
 3C. THEY APPEAR TO BE INCORRECT.
  
 9) THE PRESSURES FOR THE GARAGE DOOR ON
 SHEET 3A ARE BOTH NEGATIVE. PLEASE
 CORRECT.
  
 10) THE PRODUCT APPROVALS FOR THE STORM
 PANELS ARE ILLEGIBLE AND THE CIRCLED
 INSTALLATION INFORMATION DOES NOT APPEAR
 TO CORRESPOND WITH THE STORM PANEL
 CONNECTION DETAILS ON SHEET TWO OF THE
 PLANS. ONE OF THE KEY PLANS AND SCHEDULE
 IS FOR ANOTHER MODEL. THE DRAWINGS HAVE
 BEEN STAMPED BY THE ENGINEER FOR ONE
 PERMIT ONLY. AN ORIGINAL SIGNED AND
 SEALED COPY OF THE DRAWING IS REQUIRED.
  
 11) THE TWO USP TA STRAPS LISTED AS A-4
 IN THE TRUSS CONNECTOR SCHEDULE HAVE AN
 UPLIFT VALUE OF 1230# ON A 1 PLY TRUSS.
 PLEASE REVISE. FBC 1609.4 NO LONGER
 ALLOWS A ONE-THIRD INCREASE IN THE
 STEEL CALCULATIONS OF CONNECTORS. PLEASE
 REVIEW THE VALUES LISTED AND REVISE IF
 REQUIRED. SEE FBC 1609.4 AND 2003 USC
 CATALOG.
  
 12) SURVEY INCORRECTLY LISTS FLOOD ZONE
 AS B. CITY RECORDS SHOW THAT PROPERETY
 IS IN AN AO FLOOD ZONE. PLEASE CORRECT.
 AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-21 Cont ID  
Sent By btrobaug Date 2003-07-21 Time 09:40 Rev Time 0.50
Received By btrobaug Date 2003-07-21 Time 09:20 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:56 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 11:56 Sent To B
Notes
2003-09-16 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 15:41 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 15:41 Sent To B
Notes
2003-09-04 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-08 Cont ID  
Sent By mmclean Date 2003-07-11 Time 13:06 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 11:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-22 Cont ID  
Sent By pkrauss Date 2003-07-22 Time 14:16 Rev Time 0.25
Received By pkrauss Date 2003-07-22 Time 14:16 Sent To  
Notes
2003-07-22 00:00:00PROVISO:
  
 ONE SET OF ENERGY CALCULATIONS DO NOT
 MATCH SQUARE FOOTAGE OR EQUIPMENT SIZE
 REQUIRED.PLEASE SUBMIT CORRECT ENERGY
 CALCULATION TO MATCH PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By rmcdouga Date 2003-09-24 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2003-09-24 Time 14:41 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-29 Cont ID  
Sent By btrobaug Date 2003-07-21 Time 09:40 Rev Time 0.25
Received By jleech Date 2003-07-29 Time 19:18 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-08 Time 11:05 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***