| 2003-07-31 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE SURVEY INCORRECTLY LISTS FLOOD |
| | ZONE AS B. CITY RECORDS SHOW THAT THE |
| | PROPERTY IS LOCATED IN AN "AO" FLOOD |
| | ZONE. PLEASE CORRECT. AN ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. |
| | |
| | 3) FBC 1609.4 NO LONGER ALLOWS THE ONE- |
| | THIRD INCREASE IN THE STEEL CALCULATIONS |
| | FOR TRUSS CONNECTORS. THE TRUSS ANCHOR |
| | SCHEDULE ON SHEET 2 LISTS INCORRECT |
| | UPLIFT VALUES. PLEASE REVISE. |
| | THE "USP" RT STRAPS REQUIRE THE NAILS TO |
| | BE EQUALLY DISTRIBUTED ON BOTH SIDES OF |
| | THE CONNECTION. SEE 2003 USP CATALOG. |
| | |
| | 4) SHEET 2 WHICH CONTAINS STRUCTURAL |
| | INFORMATION AND THE ENGINEER'S TITLE |
| | BLOCK IS NOT SIGNED AND SEALED BY THE |
| | ENGINEER. FAC 61G15-23.002 |
| | |
| | 5) PLEASE REVISE DETAIL 1 ON SHEET 4. |
| | THE BUCK IS REQUIRED TO EXTEND BEYOND |
| | THE INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.) |
| | |
| | 6) SPECIFY THE SIZE OF THE COLUMN AT THE |
| | REAR PORCH. |
| | |
| | 7) SPECIFY THE CONNECTOR FOR THE WOOD |
| | BEAM AT THE REAR PORCH WHERE IT CONNECTS |
| | TO THE WALL AT THE MASTER BEDROOM. |
| | |
| | 8) THE ENERGY CALCULATIONS DO NOT STATE |
| | THAT THEY ARE WORST CASE AND THEREFORE |
| | CAN NOT BE USED GENERICALLY, DUE TO THE |
| | DIFFERENT ORIENTATIONS OF THE STRUCTURES |
| | ON THE LOTS. PLEASE CORRECT. SEE FBC |
| | CHAPTER 13. |
| | |
| | 9) THE NORANDEX SITE SPECIFIC PRODUCT |
| | APPROVALS ARE REQUIRED TO BE SEALED BY |
| | THE DESIGNER OF RECORD. THE ENGINEER'S |
| | NAME, ADDRESS AND NUMBER ARE REQUIRED TO |
| | BE ON THE FORM. SEE FAC 61G15-23.002. |
| | |
| | 10) PLEASE REVIEW THE LISTED DESIGN |
| | PRESSURES FOR THE GARAGE DOOR ON SHEET |
| | 3C, THEY APPEAR TO BE INCORRECT. |
| | |
| | 11) THE PRESSURES FOR THE GARAGE DOOR ON |
| | SHEET 3A ARE BOTH NGATIVE. PLEASE |
| | CORRECT. |
| | |
| | 12) THE PRODUCT APPROVALS FOR THE STORM |
| | PANELS ARE ILLEGIBLE AND TH CIRCLED |
| | INSTALLATION INFORMATION DOES NOT APPEAR |
| | DOES NOT APPEAR TO CORRESPOND WITH THE |
| | STORM PANEL CONNECTION DETAILS ON SHEET |
| | 2 OF THE PLANS. THE STORM PANEL DRAWINGS |
| | ARE STAMPED FOR ONE PERMIT ONLY. AN |
| | ORIGINAL SIGNED AND SEALED COPY OF THE |
| | DRAWING IS REQUIRED. SUBMIT KEY PLAN AND |
| | INSTALLATION SCHEDULE. |
| | |
| | 13) THE PRODUCT APPROVAL FOR THE OUT- |
| | SWING DOOR WITH SIDELITE IS ILLEGIBLE. |
| | SUBMIT CLEAR COPIES. |
| | |