| 2003-08-06 00:00:00 | DENIED |
| | |
| | 1) 1001.1.3/ 1005.4 ZERO LOT LINE |
| | EGRESS:WHEN ACCESS TO OR FROM A RE- |
| | QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| | ING OF A STRUCTURE TO THE PUBLIC WAY, |
| | REQUIRES TRANSVERSING A PROPERTY |
| | (ADJOINING LOT) THAT IS NOT PART OF THE |
| | ONE WHICH THE STRUCTURE IS LOCATED, AN |
| | EGRESS EASEMENT THROUGH THE ADJOINING |
| | PROPERTY IS REQUIRED AND SHALL BE RECORD |
| | ED IN THE COUNTY RECORDS. THIS EASEMENT |
| | SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| | ING SHALL BE PLACED WITHIN THE EASEMENT |
| | AREA WHICH WOULD BLOCK ACCESS TO THE |
| | EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| | FROM THE RESCUE OPENING TO THE PUBLIC |
| | WAY. NO LANDSCAPING, FENCES OR OTHER |
| | IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| | EASEMENT. SUBMIT RECORDED COPY OF THE |
| | SUBDIVISION COVENANTS SPECIFYING AN |
| | EGRESS EASEMENT. |
| | |
| | 2) FBC 1909.3 REQUIRES THE WWM IN THE |
| | SLAB TO BE SUPPORTED ON APPROVED |
| | MATERIALS AT NO MORE THAN 3'OC. PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 3) THE GLASS BLOCK AT THE MASTER BATH |
| | TUB IS IN A HAZARDOUS LOCATION AND IS |
| | REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| | THICKNESS OF 0.25" PER FBC 2405.2. |
| | PLEASE SPECIFY ON THE PLANS. |
| | |
| | 4) THE DOOR IN THE GARAGE WALL ADJACENT |
| | TO THE CONDITIONED SPACE IS REQUIRED TO |
| | BE SOLID CORE OR INSULATED BY FBC |
| | CHAPTER 13. |
| | |
| | 5) THE WINDOWS IN THE DEN EXCEED THE 20 |
| | PERCENT OF WALL ALLOWED AS OPENINGS BY |
| | FBC TABLE 600. (21SQFT ALLOWED) |
| | |
| | 6) THE LETTER FROM THE ENGINEER FOR THE |
| | GLASS BLOCK IS REQUIRED TO BE SIGNED AND |
| | SEALED WHEN SUBMITTED FOR PUBLIC RECORD |
| | PER FAC 61G15-23.002. |
| | |
| | 7) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| | THIRD INCREASE ON STEEL CALCULATIONS FOR |
| | CONNECTORS. PLEASE REVISE THE CONNECTOR |
| | SCHEDULE ON SHEET TO VALUES WHICH DO NOT |
| | INCLUDE THIS INCREASE. SEE THE 2003 USP |
| | AND SIMPSON HIGH WIND-RESISTANT CONST. |
| | CATALOGS. |
| | |
| | 8) HUGHES WAS PURCHASED BY USP SO TIME |
| | AGO. PLEASE UPDATE THE HUGHES CONNECTORS |
| | SPECIFIED ON SHEET 6 AND IN THE DETAILS |
| | ON SHEET 8 TO A CURRENT MANUFACTURER. |
| | |
| | 9) PLEASE REVISE THE BUILDING CATEGORY |
| | ON SHEET 6 TO CATEGORY II. SEE TABLE 1-1 |
| | IN ASCE 7-98. R3 IS THE OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 10) NOTE 10 ON SHEET 8 REFERENCES THE |
| | WRONG CODE. PLEASE UPDATE TO 2001 FBC. |
| | |
| | 11) PROVIDE A DETAIL FOR STRUCTURAL 2X |
| | BUCKS AS REQUIRED BY THE PRODUCT |
| | APPROVAL FOR THE ENTRY DOOR. |
| | |
| | 13) FBC 1005.4.5 (GLITCH AMENDMENTS) |
| | REQUIRES AT LEAST ONE MEANS OF ESCAPE |
| | FROM A DWELLING WHEN SHUTTERED FOR |
| | IMPACT PROTECTION. THE MEANS OF ESCAPE |
| | SHALL BE WITHIN THE FIRST FLOOR OF THE |
| | DWELLING AND CAN NOT BE LOCATED IN A |
| | GARAGE. OCCUPANTS IN ANY PART OF THE |
| | DWELLING SHALL HAVE ACCESS TO IT WITHOUT |
| | HAVING TO PASS THROUGH A LOCKABLE DOOR |
| | NOT UNDER THEIR CONTROL. INDICATE HOW |
| | COMPLIANCE WILL BE ACHIEVED. |
| | |
| | 14) THERE ARE TWO ARCHITECT'S TITLE |
| | BLOCKS ON SOME OF THE PLAN SHEETS. |
| | PLEASE REMOVE THE ONE THAT DOES NOT |
| | BELONG TO THE DESIGNER OF RECORD. |
| | |
| | 15) STORM PANELS : THE SAFEGUARD COMPANY |
| | IS NO LONGER IN BUSINESS AND WEATHER- |
| | GUARD HAS NOT COMPLETED THE PROCESS OF |
| | ASSUMING THE PRODUCT APPROVAL FROM SBCCI |
| | THE BUILDING OFFICIAL HAS DETERMINED |
| | THAT WE CAN NOT ACCEPT THIS PRODUCT FOR |
| | USE IN THE CITY OF WPB AT THIS TIME. |
| | |
| | 16) THE TRUSS DRAWINGS AND LAYOUT FOR |
| | SINGLE FAMILY DWELLINGS ARE NO LONGER |
| | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| | THEY ARE TO BE GIVEN TO THE INSPECTOR IN |
| | THE FIELD AT THE TRUSS INSPECTION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |