| 2004-02-11 00:00:00 | DENIED |
| | ~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE ORIGINAL PLANS SHOW A 225 AMP |
| | SERVICE ON THE GARAGE AND A 150 AMP |
| | EXTERIOR PANEL ON THE HOUSE.THE |
| | "REVISED LOW VOLTAGE PLANS" SHOW A 200 |
| | AMP SERVICE ON THE HOUSE AND ALSO |
| | SUBMITTED WAS A LOAD CALC FOR A 100 AMP |
| | SUB PANEL,PLEASE CORRELATE. |
| | |
| | 2} SUBMIT A RISER DIAGRAM SHOWING THE |
| | INTENDED SCOPE OF WORK INCLUDING ALL |
| | CONDUIT,FEEDER AND GROUND SIZES.ALSO |
| | SHOW COMPLIANCE WITH 230.31 & 250.32 IF |
| | APPLICABLE. |
| | |
| | 3} SHOW ALL EQUIPMENT LOCATIONS ON |
| | PLANS. |
| | |
| | 4} SUBMIT LOAD CALCULATIONS FOR THE |
| | ENTIRE ELECTRICAL SCOPE OF WORK. |
| | |
| | 5} THE "COVERED PORCH" ON THE 8- 1/2" BY |
| | 11" THAT WAS SUBMITTED WITH THE LOW |
| | VOLTAGE APPLICATION DOES NOT APPEAR ON |
| | THE ORIGINAL PLANS,ELECTRICAL OR |
| | BUILDING.IF THIS IS NEW A PERMIT IS |
| | REQUIRED, IF EXISTING AND BEING WIRED |
| | NOW PLEASE ADD TO THE PLAN FOR |
| | REVERENCE. ALSO ADJUST THE VALUE OF THE |
| | REVISION TO INCLUDE ALL WORK BEING DONE. |
| | |
| | 6} THE SMOKE DETECTOR THAT WAS ADDED IN |
| | THE KITCHEN AREA MUST BE 3' AWAY FROM |
| | THE DOOR AND 20' AWAY FROM A COOKING |
| | APPLIANCE OR MUST COMPLY WITH 8-1.4.2 |
| | NFPA-72. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |