Plan Review Details - Permit 03070374
Plan Review Stops For Permit 03070374
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-28 Cont ID  
Sent By rmcdouga Date 2003-10-28 Time 10:02 Rev Time 2.00
Received By rmcdouga Date 2003-10-28 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:48 Rev Time 3.00
Received By rmcdouga Date 2003-09-23 Time 08:40 Sent To  
Notes
2003-09-23 00:00:00DENIED
  
 1) THE ENGINEER'S NAME, ADDRESS AND
 LICENSE NUMBER IS REQUIRED ON THE PLANS
 AND IF PRACTICING THROUGH AN AUTHORIZED
 BUSINESS THE BUSINESS NAME AND LICENSE
 NUMBER IS REQUIRED PER FAC 61G15-23.002.
 THE ROOF FRAMING PLAN AND ROYALL WALL
 DRAWINGS ARE MISSING THIS INFORMATION.
  
 2) THE ROOF FRAMING PLAN AND ROYALL WALL
 DRAWINGS HAVE NOT BEEN SEALED BY THE
 ENGINEER.
  
 3) THE MANUFACTURER'S SPECS. AND LISTING
 INFORMATION IS REQUIRED IF INSTALLING
 THE OPTIONAL PREFAB FIREPLACE. IF NOT
 BEING INSTALLED CROSS IT OFF ON THE
 PLANS.
  
 4) SUBMIT STRUCTURAL DRAWINGS FOR THE
 CHIMNEY. INDICATE FRAMING, STRAPPING,
 EXTERIOR COVERING, DIMENSIONS, ETC.
  
 5) SEMCO AND HUGHES ARE NO LONGER IN
 BUSINESS. UPDATE SHEETS 6 , RF-1 AND THE
 ROYALL WALL DRAWINGS TO CONNECTORS THAT
 ARE LISTED IN THE CURRENT USP, SIMPSON,
 ETC. CATALOGS.
  
 6)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 7) THE STORM PANEL INFORMATION THAT WAS
 SUBMITTED IS NOT ACCEPTABLE. THE SBCCI
 REPORT FROM AMERICAN ALUMINUM IS NO
 LONGER LISTED. SAFEGUARD IS NO LONGER IN
 BUSINESS AND WEATHERGUARD HAS NOT YET
 HAD SAFEGUARD'S REPORT TRANSFERED TO
 THEM BY SBCCI.
  
 8) THE PRODUCT APPROVAL FOR THE MULLIONS
 DOES NOT APPEAR TO WORK FOR THE 12 FT. X
 10 FT.2 IN. FIXED GLASS WINDOW WITH
 ARCHED F.G. ABOVE LOCATED IN THE GRAND
 ROOM. INDICATE THE LOCATIONS AND SIZES
 OF THE MULLIONS FOR THIS WINDOW.
  
 9) THE TRUSS LAYOUT AND DRAWINGS ARE NOT
 REQUIRED TO BE SUBMITTED FOR PLAN REVIEW
 THE SIGNED AND SEALED SET IS REQUIRED TO
 BE GIVEN TO THE BUILDING INSPECTOR AT
 THE ROOF FRAMING INSPECTION.
  
 IF YOU HAVE QUESTIONS CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-30 Cont ID  
Sent By kstevens Date 2003-07-31 Time 07:26 Rev Time 3.00
Received By lhatten Date 2003-07-26 Time 18:43 Sent To  
Notes
2003-07-30 00:00:00REVIEW & STAMPED PLANS 07/26/2003

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-16 Cont ID  
Sent By dpalmer Date 2003-09-16 Time 12:42 Rev Time 0.50
Received By dpalmer Date 2003-09-16 Time 12:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-09-13 Time 18:55 Rev Time 0.50
Received By btrobaug Date 2003-07-18 Time 15:56 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:38 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 14:38 Sent To M
Notes
2004-01-13 00:00:00PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 08:47 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 08:47 Sent To B
Notes
2003-10-24 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 08:29 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 08:29 Sent To P
Notes
2003-09-08 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By mmclean Date 2003-07-08 Time 15:18 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 16:23 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 14:48 Rev Time 0.25
Received By pkrauss Date 2004-01-26 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-22 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:38 Rev Time 0.25
Received By pkrauss Date 2003-07-22 Time 11:23 Sent To P
Notes
2003-07-22 00:00:00PROVISO:
  
 PLEASE REVISE CU-1 ON PLAN INDICATES
 10.70 SEER, THE ENERGY CALCULATIONS
 INDICATE A 11 SEER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-13 Cont ID  
Sent By kstevens Date 2003-09-13 Time 18:55 Rev Time 0.50
Received By kstevens Date 2003-09-13 Time 18:54 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-09-08 Time 08:29 Rev Time 0.33
Received By kstevens Date 2003-07-31 Time 07:25 Sent To B
Notes
2003-07-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN OR MEET CODE RE-
 QUIREMENTS. THE OPTIONAL LAUNDRY TRAY IN
 THE LAUNDRY ROOM IS NOT SHOWN ON RISER.
 2) THE OPTIONAL LAUNDRY TRAY IN THE
 GARAGE SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENT FOR GUEST BATH #3.
 909.1
 3) SEE ATTACHED SHEET CONCERNING THE
 ARCHITECT'S TITLE BLOCK. NO ARCHITECT
 NUMBER SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-07 Time 16:23 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***