Plan Review Details - Permit 03070369
Plan Review Stops For Permit 03070369
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-22 Cont ID  
Sent By jwitmer Date 2003-08-22 Time 09:36 Rev Time 0.75
Received By jwitmer Date 2003-08-22 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-18 Cont ID  
Sent By jwitmer Date 2003-07-18 Time 15:52 Rev Time 1.50
Received By jwitmer Date 2003-07-18 Time 15:26 Sent To  
Notes
2003-07-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070369
 ADD:2200 FLORIDA MANGO ROAD
 CONT: C. VAN BLAKEMAN
 TEL: (561)329-4175
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE COPY OF SIGNED CONTRACT,
 VALUE LOW!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 2) SHEET A2-01 DETAIL# 6 INDICATES A NEW
 EXTERIOR DOOR. PROVIDE PRODUCT APPROVAL.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
  
 3) SAME DETAIL SHOWS A EXISTING WALKWAY,
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) OFFICE DOOR# 110 TO MEET 4.13.6
 MANEUVERING CLEARENCE AT DOORS.SEE
 ATTACHMENT.
  
 5) NOTE 5 OF DEMO PAGE TO REMOVE DRYWALL
 FOR NEW FIRE RATED PARTITION.
 TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; IF THE SAME TYPE OF OCCUPA
 NCY ONLY 1 HR TENANT SEPERATION REQUIRED
 PROVIDE EITHER U. L. LISTING OR GYPSUM
 ASSOCIAN LISTING NUMBER.
  
 6)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 7)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 8)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By dpalmer Date 2003-08-25 Time 14:19 Rev Time 0.50
Received By dpalmer Date 2003-08-25 Time 14:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-19 Cont ID  
Sent By dpalmer Date 2003-08-19 Time 13:18 Rev Time 1.50
Received By dpalmer Date 2003-08-19 Time 13:18 Sent To  
Notes
2003-08-19 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE 424.3B FOR OCP FOR
 AHU/HEAT @ 125%. SHOWN AS 2P50`S.
  
 2)NOTE: PLEASE CORRELATE PANELS/PLANS
 AND LOAD CALCULATIONS. SHOWS 3 A/C SYST-
 -EMS ON LOAD CALCS AND 4 ON PLANS AND
 PANEL SCHEDULES.?
  
 3)NOTE: PLEASE SEE PLANS STILL NOTE
 STANDARD BLDG CODE. WE ARE UNDER FBC
 2001.
  
 4)NOTE: PLEASE SEE 110.26 AND PROVIDE
 CLEAR FLOOR SPACE MARKINGS FOR PANELS.
 ESP STORAGE AREAS.
  
 5)NOTE: PLEASE CLARIFY WHY NEW LIGHTING
 LOADS ARE NOT REVISED TO 125% FOR
 CONTINUOUS LOADS AND SHOWN @125% ON
 EXISTING?
 215.3/230.42 ETC.
  
 6)NOTE: PLEASE REMOVE ALL OLD VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 NEW COMPLETE SETS FOR REVIEW AND STAMP-
 -ING.
  
 7)NOTE; PLEASE ALSO SEE THAT VALUATION
 FOR SCOPE OF WORK HAS NOT BEEN CHANGED
 AND CONTRACT FOR COMPLETE SCOPE OF WORK
 HAS NOT BEEN PROVIDED. FAC/FBC/ CITY
 ADMIN CODE,104.6.5
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By alange Date 2003-08-07 Time 13:49 Rev Time 0.50
Received By dpalmer Date 2003-07-21 Time 06:10 Sent To FIRE
Notes
2003-07-21 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT PANEL(S) SCHEDULES
 TO CORRELATE WITH CIRCUITING SHOWN ON
 PLANS.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 E2.1
  
 3)NOTE: PLEASE CLARFIY SIZE OF FPL METER
 ALONG W/ LOAD CALCULATIONS DUE TO
 ADDITION OF NEW A/C EQUIPMENT ETC.215.5
  
 4)NOTE: PLEASE PROVIDE NEW AND EXISTING
 EXT/ EM LTS IN BOTH SPACES/ PLEASE LABEL
 AS E FOR EXSITING.NOTE ALREADY MENTION
 -S CIRCUIT PER 700-12E
  
 5)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 FOR ALL WORK BEING PERFORMED. VALUE ON
 APPLICATION IS SHOWN AT $2000.00 THIS
 VALUE SHOULD INCLUDE ALL TRADES/LABOR
 AND ALL MATERIALS, EVEN IF OWNER
 SUPPLIED. PER 104.6.5 ADMIM CODE FBC.
 AND LOCAL ADMIN CODE.
 PLEASE ADJUST
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-21 Time 06:29 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 15:18 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 15:18 Sent To  
Notes
2003-08-22 00:00:00COMM BOX #38

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 15:13 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 13:46 Rev Time 0.00
Received By alange Date 2003-08-07 Time 13:46 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 09:28 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 09:27 Sent To  
Notes
2003-07-08 00:00:00COMM BOARD #21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-03 Cont ID  
Sent By pkrauss Date 2003-10-03 Time 11:01 Rev Time 0.25
Received By pkrauss Date 2003-10-03 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By pkrauss Date 2003-07-17 Time 13:48 Rev Time 0.45
Received By pkrauss Date 2003-07-17 Time 13:21 Sent To  
Notes
2003-07-17 00:00:00PROVISO:
  
 PLEASE CLARIFY ENERGY CALCULATIONS, PAGE
 1 "MAX TONNAGE" 4.PLANS INDICATE A
 NEW 5 TON SYSTEM ALONG WITH EXISTING
 SYSTEMS.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By kstevens Date 2003-08-25 Time 16:30 Rev Time 1.50
Received By kstevens Date 2003-08-25 Time 16:30 Sent To  
Notes
2003-08-25 00:00:00PASSED/PROVISO - MANUF. SPEC SHEETS RE-
 QUIRED AT TIME OF PLUMBING FINAL FOR
 WATER COOLER. ARI-1010

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-08-19 Cont ID  
Sent By kstevens Date 2003-08-19 Time 10:22 Rev Time 1.00
Received By kstevens Date 2003-08-19 Time 10:22 Sent To  
Notes
2003-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT A1.02 BOTTLED WATER COOLER SHALL
 BE ARI-1010 COMPLIANT. MANUF. SPEC. SHTS
 REQUIRED.
 2) SHT A2.01 BREAK ROOM SINK - FROM PRE-
 VIOUS REVIEW, SHOW CLEAR FLOOR SPACE FOR
 SINK.
 3) FROM PREVIOUS REVIEW, SUBMIT A WATER
 RISER DIAGRAM. NO REVISED PLUMBING SHEET
 FOUND. SHOW ALL PIPE SIZES ECT.
 4) MANUF. SPEC. SHEETS FOR PUMP DO NOT
 INDICATE A LISTING FOR THE PRODUCT. SEC
 303.4 REQUIRES LABELING BY AN APPROVED
 AGENCY.
 5) FROM PREVIOUS REVIEW, NO VENTING RE-
 VISION SUBMITTED. (PUMP SHALL VENT TO
 EXISTING VENT SYSTEM).
 6) WHEN RESUBMITTING PLANS (TWO SETS),
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-19 Cont ID  
Sent By kstevens Date 2003-07-19 Time 13:10 Rev Time 0.50
Received By kstevens Date 2003-07-19 Time 13:10 Sent To  
Notes
2003-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. (ALSO SEE SECTION 410.1)
 2) SHT A2/01 BREAK ROOM SINK SHALL COMP-
 LY WITH SECTION 11-4.24 AND ALL SUBSECT-
 IONS. PLEASE SHOW ON DETAIL HEIGHT, 11-
 4.24.2, KNEE CLEARANCE, 11-4.24.3, DEPTH
 11-4.24.4, CLEAR FLOOR SPACE, 11-4.24.5,
 EXPOSED PIPES, 11-4.24.6 ECT.
 3) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.2.1
 4) SUBMIT MANUFACTURE INFORMATION FOR
 MYERS PUMP FOR SERVICE SINK. 303.2/303.4
 5) PUMP SHALL VENT TO EXISTING VENT SYS-
 TEM. SHOW ON RISER DIAGRAM.
 6) SIZE ALL PIPE ON WATER RISER DIAGRAM.
 7) SHT A-1 INDICATE MEASUREMENTS FOR
 TOILET ROOMS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692