Plan Review Details - Permit 03070279
Plan Review Stops For Permit 03070279
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By jwitmer Date 2003-08-21 Time 13:12 Rev Time 1.00
Received By jwitmer Date 2003-08-21 Time 13:12 Sent To  
Notes
2003-08-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070279
 ADD: 700 S ROSEMARY AVE/ 106
 CONT: ALBENATE CONST
 TEL: (239)821-7912
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: BUILDING PROVISO
  
 1) PROVIDE (2) COPIES OF A MULLION
 REPORT (EITHER DADE COUNTY OR SBCCI)
 FOR THE HORIZONTAL MEMBER SEPERATING THE
 EXISTING STOREFRONT AND THE NEW. THE
 REPORT PROVIDED WAS TESTED TO THE SPAN
 OF 96". THE OPENING MEASURES APPROX.
 120".
 2)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By jwitmer Date 2003-07-21 Time 07:52 Rev Time 1.50
Received By jwitmer Date 2003-07-21 Time 07:48 Sent To  
Notes
2003-07-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070279
 ADD: 700 S. ROSEMARY AVE
 CONT: ALBENATE CONSTRUCTION
 TEL: (239)821-7912
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PLANS REQUIRE CITY PLACE STAMP, WORK
 ON ELEVATIONS.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A)STOREFRONT GLAZING SYSTEM
 B)MULLION HORIZONTAL/ VERTICAL
 1) HORIZONTAL EXIST DOOR/ NEW STORE-
 FRONT ABOVE
 2) VERTICAL BETWEEN GLAZED PANELS
 EITHER LARGE MISSLE IMPACT GLAZ-
 ING OR STORM SHUTTERS
  
 3) PRODUCT APPROVAL FOR ROLL-UP SHUTTERS
 BUT NO INFORMATION AS TO WHERE IT IS TO
 BE INSTALLED???????
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. INDICATE
 WIND PRESSURES ON ELEVATIONS.
  
 5) SHEET A-5 DETAIL 2 INDICATES REWORK-
 ING OF FRONT ENTRY BUT NO MENTION AS TO
 USE OF STRUCTURAL STUDS, GUAGE OR SPAC-
 ING.
  
 6) SHEET A-5 ALSO INDICATES THE USE OF
 SOFFITS ATTACHED TO THE CEILING BUT
 THERE IS NO MENTION AS TO SPACING OR HOW
 TO ATTACH TO THE DECK ABOVE.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-14 Cont ID  
Sent By dpalmer Date 2003-08-14 Time 07:14 Rev Time 0.50
Received By dpalmer Date 2003-08-14 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 06:33 Rev Time 0.75
Received By dpalmer Date 2003-07-17 Time 06:33 Sent To  
Notes
2003-07-17 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE SHOW NEW OR EXISTING
 SHOW WINDOW RECEPTS? 210.62
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EM/EXT LTS? PLEASE CIRCUIT PER
 700.12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By nmccray Date 2003-08-21 Time 14:11 Rev Time 0.00
Received By nmccray Date 2003-08-21 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By mcarsill Date 2003-07-17 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:04 Sent To  
Notes
2003-07-17 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 2) MEP-3 IS DIFFICULT TO FOLLOW. PLEASE
 DISPLAY ALL EMERGENCY LIGHTS AND
 EXIT SIGNS.
  
 3)MEP-2 AND MEP-3 DISPLAY DIFFERENT
 EXIT SIGN INFORMATION.
  
 4) PLEASE CLEARLY DISPLAY ALL EXISTING
 AND NEW FIRE ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 16:15 Rev Time 0.00
Received By alange Date 2003-08-06 Time 16:15 Sent To  
Notes
2003-08-06 00:00:00TO COMM BD #5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 10:13 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 10:13 Sent To  
Notes
2003-07-07 00:00:00COMM BOARD #30

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-09-30 Cont ID  
Sent By pkrauss Date 2003-09-30 Time 08:50 Rev Time 0.55
Received By pkrauss Date 2003-09-30 Time 08:47 Sent To  
Notes
2003-09-30 00:00:00PROVISO
  
 1.MATERIALS EXPOSED WITHIN PLENUMS
 SHALL BE NONCOMBUSTIBLE AS PER 2001 FBC,
 MECHANICAL 601.2.2.1.
  
 2.PERFORM TEST & BALANCE, SUBMIT
 TEST & BALANCE REPORT FOR FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-08-20 Time 12:18 Rev Time 0.40
Received By pkrauss Date 2003-08-20 Time 12:18 Sent To  
Notes
2003-08-20 00:00:00PROVISO:
  
 MATERIALS EXPOSED WITHIN PLENUMS SHALL
 BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 25 AND
 A SMOKE-DEVELOPED INDEX OF NOT MORE THAN
 50 WHEN TESTED IN ACCORDANCE WITH
 ASTM E 84.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-21 Cont ID  
Sent By jwitmer Date 2003-07-21 Time 09:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-19 Cont ID  
Sent By kstevens Date 2003-07-19 Time 12:55 Rev Time 0.33
Received By kstevens Date 2003-07-19 Time 12:55 Sent To  
Notes
2003-07-19 00:00:00NO PLUMBING WORK/PLANS SHOWN.


Account Summary | Usage Policy | Privacy Policy