Plan Review Details - Permit 03070273
Plan Review Stops For Permit 03070273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-07 Cont ID  
Sent By jwitmer Date 2003-08-07 Time 09:18 Rev Time 0.50
Received By jwitmer Date 2003-08-07 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By jwitmer Date 2003-07-21 Time 16:00 Rev Time 1.50
Received By jwitmer Date 2003-07-21 Time 13:42 Sent To  
Notes
2003-07-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070273
 ADD: 777 S. FLAGLER DRIVE
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)DOOR 619 TO MEET FLORIDA ACCESSIBILITY
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 16:22 Rev Time 3.00
Received By dpalmer Date 2003-11-07 Time 16:22 Sent To  
Notes
2003-11-07 00:00:00NEW SIGNED AND SEALED PLANS. OK

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-11-05 Cont ID  
Sent By dpalmer Date 2003-11-05 Time 12:33 Rev Time 0.50
Received By dpalmer Date 2003-11-05 Time 12:33 Sent To  
Notes
2003-11-05 00:00:00************ UNSAT ***************
  
 1)NOTE: PLANS SHALL CONTAIN A "SIGNATURE
 FOR THE ENGINEER OF RECORD.
 CONFORMATION HAS BEEN GIVEN TO THIS
 OFFICE FROM THE FBPE THAT THIS IS
 REQUIRED PER FS 471.025 AND FAC 61G15-23
 .002.
 PLEASE SEE THAT THIS OFFICE HAS NOW
 RETAINED ONE SET OF SAID PLANS FOR
 RECORD.
  
 PLEASESUBMIT CORRECTED PLANS WITH
 SIGNATURE OF ENGINEER CONTAINING A MIN
 PER FBPE FIRST AND LAST NAME.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 WILLIAM STAPLES
 ASST BLDG OFFICAL
 561-805-6652

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-10-15 Cont ID  
Sent By dpalmer Date 2003-10-15 Time 12:45 Rev Time 0.25
Received By dpalmer Date 2003-10-15 Time 12:45 Sent To  
Notes
2003-10-15 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FS 471.025 PLANS
 MUST BE SIGNED,DATED AND SEALED BY THE
 ENGINEER OF RECORD.PLEASE NOTE, IT IS
 KNOWN BY THIS OFFICE THAT THE SIGNATURE
 ON PLANS IS NOT THE SIGNATURE OF RECORD
 FOR MR CARTER.
  
 PLEASE MAKE THE ABOVE CORRECTION, AND
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:39 Rev Time 0.50
Received By dpalmer Date 2003-09-23 Time 12:40 Sent To  
Notes
2003-09-23 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE HAVE PLANS "SIGNED",DATED
 AND SEALED BY ENGINEER. PER FS 471.025
 AND FAC 61G15-23.002
 PLEASE NOTE CONFORMATION FROM THE FBPE
 HAS BEEN GIVEN TO THIS OFFICE FOR
 THE ABOVE REQ'D FS.
 ONE SET OF PLANS ARE BEING KEPT FOR
 RECORD AND MAY BE TURNED IN TO FBPE FOR
 REVIEW.
  
 PLEASE SUBMIT CORRECTED PLANS FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 WILLIAM STAPLES
 ASST BLDG OFFICIAL
 561-805-6652

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 07:17 Rev Time 0.50
Received By dpalmer Date 2003-07-17 Time 07:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-12-01 Cont ID  
Sent By nmccray Date 2003-12-01 Time 11:48 Rev Time 0.00
Received By nmccray Date 2003-12-01 Time 11:48 Sent To  
Notes
2003-12-01 00:00:00REVISION SIGN & SEALED 11-07-03 OK NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2003-10-29 Cont ID  
Sent By nmccray Date 2003-10-29 Time 11:41 Rev Time 0.00
Received By nmccray Date 2003-10-29 Time 11:41 Sent To  
Notes
2003-10-29 00:00:00NO FIRE COMPLIANCE REQUIRED. NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-23 Cont ID  
Sent By nmccray Date 2003-09-23 Time 14:13 Rev Time 0.00
Received By nmccray Date 2003-09-23 Time 14:13 Sent To  
Notes
2003-09-23 00:00:00REVISION DATED FOR 8-25-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-12 Cont ID  
Sent By nmccray Date 2003-08-12 Time 14:02 Rev Time 0.00
Received By nmccray Date 2003-08-12 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-16 Cont ID  
Sent By mcarsill Date 2003-07-16 Time 17:13 Rev Time 0.00
Received By mcarsill Date 2003-07-16 Time 17:13 Sent To  
Notes
2003-07-16 00:00:001) FIRE ALARM CIRCUIT NOTES INDICATE
 CLASS B, STYLE C CIRCUITS. ONLY CLASS
 A, STYLE D CIRCUITS ARE ALLOWED.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 16:25 Sent To  
Notes
2003-11-07 00:00:00TO COMM BD#21/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 08:35 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 08:21 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 08:21 Sent To  
Notes
2003-10-16 00:00:00TO COMM BD#44

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:38 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 15:38 Sent To E
Notes
2003-10-08 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 10:53 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 10:53 Sent To  
Notes
2003-08-25 00:00:00COMM BD #11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 09:11 Rev Time 0.00
Received By alange Date 2003-07-29 Time 09:09 Sent To  
Notes
2003-07-29 00:00:00TO COMM BD #42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 16:08 Sent To  
Notes
2003-07-07 00:00:00COMM BOARD #16

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-11-20 Cont ID  
Sent By pkrauss Date 2003-11-20 Time 15:48 Rev Time 0.40
Received By pkrauss Date 2003-11-20 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2003-11-06 Cont ID  
Sent By pkrauss Date 2003-11-06 Time 09:01 Rev Time 0.20
Received By pkrauss Date 2003-11-06 Time 08:43 Sent To  
Notes
2003-11-06 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-28 Time 13:57 Rev Time 0.35
Received By pkrauss Date 2003-10-28 Time 13:34 Sent To  
Notes
2003-10-28 00:00:00DENIED:
 PLEASE NOTE REVISION NOT SIGNED AND
 SEALED BY ENGINEER OF RECORD.ORIGINAL
 SUBMITTAL WAS DONE BY LON T. CARTER AND
 THE REVISION WAS DONE BY MIRCEA PELLA.
 AS PER F.S. 471.025 PLANS ARE TO BE
 SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 11:58 Rev Time 0.35
Received By pkrauss Date 2003-09-24 Time 11:57 Sent To  
Notes
2003-09-24 00:00:00APPROVED 8-29-03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By pkrauss Date 2003-07-16 Time 09:50 Rev Time 0.45
Received By pkrauss Date 2003-07-16 Time 08:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-12-09 Cont ID  
Sent By kstevens Date 2003-12-09 Time 10:46 Rev Time 0.50
Received By kstevens Date 2003-12-09 Time 10:46 Sent To  
Notes
2003-12-09 00:00:00REVISION ON SHTS P0.1 & P2.1 - ONLY REV.
 IS SEAL HAS SIGNATURE VERSUS INITALS

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-06 Cont ID  
Sent By kstevens Date 2003-12-06 Time 15:12 Rev Time 1.00
Received By kstevens Date 2003-12-06 Time 15:11 Sent To  
Notes
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 NO REVISIONS NOTED ON PLUMBING SHEETS
 PO.1 & P2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-19 Cont ID  
Sent By kstevens Date 2003-07-19 Time 12:28 Rev Time 0.33
Received By kstevens Date 2003-07-19 Time 12:27 Sent To  
Notes
2003-07-19 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR FIXTURE IN AN "EFFECTIVE RANGE"