Plan Review Details - Permit 03070239
Plan Review Stops For Permit 03070239
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-01 Cont ID  
Sent By lmartine Date 2003-08-01 Time 15:10 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-10 Time 10:01 Rev Time 0.75
Received By jwitmer Date 2003-07-21 Time 16:29 Sent To  
Notes
2003-07-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070239
 ADD: 1675B FORUM PLACE
 CONT: BEJAI P MANAGAR
 TEL: (561)239-1040
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 11.3.3 WIDTH. THE MINIMUM CLEAR WIDTH
 OF AN ACCESSIBLE ROUTE SHALL BE 36"
 EXCEPT AT DOORS. IF A PERSON IN A WHEEL-
 CHAIR MUST MAKE A TURN AROUND AROUND AN
 OBSTRUCTION, THE MINIMUM CLEAR WIDTH OF
 THE OBSTRUCTION, THE MINIMUM CLEAR WIDTH
 OF THE ACCESSIBLE ROUTE SHALL BE AS
 SHOWN IN FIGURE 7(A) AND (B).
  
 2)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) 11-4.23.3 CLEAR FLOOR SPACE, AN UN-
 OBSTRUCTED TURNING SPACE COMPLYING WITH
 11-4.2.3. A HANDICAPPED PERSON CAN'T
 EVEN MAKE IT TO THE WATER CLOSET, OR
 HOLD ON TO THE GRAB BARS TO MAKE A TRANS
 FER TO THE WATER CLOSET!!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-01 Cont ID  
Sent By dpalmer Date 2003-08-01 Time 13:06 Rev Time 0.25
Received By dpalmer Date 2003-08-01 Time 13:06 Sent To  
Notes
2003-08-01 00:00:00REDLINED EQUIPMENT GROUNDING CONDUCTOR.
 FROM MAIN TO PANEL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 07:46 Rev Time 0.50
Received By dpalmer Date 2003-07-17 Time 07:45 Sent To  
Notes
2003-07-17 00:00:00************* UNSAT *****************
  
 1)NOTE: : PLEASE SHOW ALL CIRCUITING ON
 PLANS. PLEASE CORRELATE W/ SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE REQ'D GFI PROTECTION
 FOR KITCHENS. 210.8B
  
 3)NOTE: PLEASE SEE ATTACHED SHEET FOR
 FAC 61G15-23.002 AND REQ'D INFORMATION
 FOR TITLE BLOCK INCLUDING AUTHORIZATION
 #.
  
 4)NOTE: PLEASE CORRELATE CIRCUITING AND
 PANEL SCHEDULES. CIRCUIT A-1 SHOWN AS
 KITCHEN COUNTER RECEPT AND PANEL SHOWS
 A/C UNITS.?
 ALOS SHOWS SAME CIRCUIT FEEDING OTHER
 RECEPTS FOR OTHER EQUIPMENT?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By nmccray Date 2003-07-16 Time 15:45 Rev Time 0.00
Received By nmccray Date 2003-07-16 Time 15:45 Sent To  
Notes
2003-07-16 00:00:00**********PROVISO***********************
 NO COOKING TO PREVENT FROM PRODUCING
 GREASE LADEN VAPORS.
 INTERIOR FINISH CLASSIFICATION SHALL BE
 CLASS "A" OR CLASS "B" FOR THE WALLS AND
 CEILINGS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 10:36 Rev Time 0.00
Received By alange Date 2003-07-30 Time 10:36 Sent To  
Notes
2003-07-30 00:00:00TO BLDG COMM BD #16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-10 Time 10:01 Rev Time 0.00
Received By shernand Date 2003-07-10 Time 10:01 Sent To  
Notes
2003-07-10 00:00:00COMM BOARD #9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:16 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 09:16 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-06 Cont ID  
Sent By kstevens Date 2003-08-06 Time 13:52 Rev Time 1.00
Received By kstevens Date 2003-08-06 Time 13:52 Sent To  
Notes
2003-08-06 00:00:00PROVISO - SAMPLE POINT REQUIRED - SHEET
 FROM METRO DESIGN TO BE SUBMITTED WITH
 STAMP FROM DBPR FOR FILE COPY

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By kstevens Date 2003-07-23 Time 14:36 Rev Time 1.50
Received By kstevens Date 2003-07-23 Time 14:36 Sent To  
Notes
2003-07-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE
 FLORIDA STATUTES
  
 1) BOTH SETS OF PLANS SHALL BE STAMPED
 BY THE DBPR HOTEL AND RESTURANT DIVISION
 AND RELATED SPECIFICATION SHEETS SHALL
 BE AFFIXED TO BOTH SETS. 104.2.1
 2) SHOW ALL DIMENTIONS FOR THE TOILET
 ROOM. SHOW CLEAR FLOOR SPACE PER SECTION
 11-4.16.2 & 11-4.19.3
 3) SUMBIT A WATER RISER DIAGRAM - SECT-
 ION 104.3.1.1 PLUMBING(3)
 4) SHT A2 PLUMBING NOTES/GAS NOTES, A
 SEPARATE PERMIT AND SET OF PLANS SHALL
 BE REQUIRED FOR GAS.
 5) 61G15-23.002(2) AUTHORIZATION NUMBER
 REQUIRED IN TITLE BLOCK.
 6) CONTACT RODNEY COMPO, INDUSTRIAL PRE-
 TREATMENT, ENVIRONMENTAL COMPLIANCE. HE
 SHALL DETERMINE IF A GREASE TRAP WILL BE
 REQUIRED, AND IF SO THE SIZE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:16 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
***NONE***