Plan Review Details - Permit 03070233
Plan Review Stops For Permit 03070233
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-11 Cont ID  
Sent By btrobaug Date 2003-07-11 Time 16:03 Rev Time 0.50
Received By btrobaug Date 2003-07-11 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By btrobaug Date 2003-07-09 Time 13:34 Rev Time 0.33
Received By btrobaug Date 2003-07-09 Time 13:31 Sent To  
Notes
2003-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 THE GROUNDING ELECTRODE SYSTEM PER
 250-50 OR 250-52, WHICHEVER IS USED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 13:18 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 13:18 Sent To E
Notes
***NONE***