| 2003-07-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03070057 |
| | ADD: CRANES POINTE WAY |
| | CONT: NORTHSTAR CUSTOM HOMES |
| | TEL: (561)799-7700 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE ENGINEERING CALCULATIONS FOR |
| | BUTT GLAZING AS PER FBC 2406.2. ENGINEER |
| | ING SHEET NOTES THERE COULS BE 1/2" |
| | DEFLECTION IN THE LENGHT OF GLASS BUT |
| | THE GLASS BITE IS ONLY 3/8", THIS WOULD |
| | ALLOW THE GLASS TO BE RELEASED FROM THE |
| | FRAME! |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PROVIDE A MULLION CHART WHICH WILL GIVE |
| | THE SIZE OF THE MULLION AND THE DIREC- |
| | TION THE MULLION WILL BE USED. |
| | |
| | 3) PLANS INDICATE THAT THE DESIGNER IS |
| | USING THE MORE STRINGENT WIND EXPOSURE |
| | CLASS"C" BUT THE PRESSURES DO NOT |
| | REFLECT THIS. SEE 2 EXAMPLES. |
| | |
| | 4) PLANS ALSO INDICATE THE SIDELIGHTS AS |
| | WELL AS DOORS TO HAVE TEMPERED GLASS, |
| | IF SO, HOW WILL LARGE MISSLE IMPACT GLAZ |
| | ING BE USED? |
| | |
| | 5) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 6) 1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | RE-EVALUATE TRUSS ANCHOR SCHEDULE, USP |
| | IS ELIMENATING THE TAPR216 IT IS NOT IN |
| | THE 2003 CATALOG. RE-EVALUATE TRUSS |
| | ANCHOR SCHEDULE. |
| | |
| | 7) PLEASE PROVIDE RATIONAL ANALYSIS FOR |
| | THE BEAM ABOVE THE BUTT GLASS, ECENTRIC |
| | LOADING. |
| | |
| | 8) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | ROOF FRAMING PLAN MISSING INFORMATION ON |
| | ROOF GIRDERS OVER THE COVERED PORCH |
| | AREA, SEE VALLEY, MISSING GIRDERS!!!! |
| | PROVIDE LOADS! |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |